База знань › Backup Switching Devices
GoodWe STS200-80-10
Official manufacturer GLOBAL перевірено 23 вересня 2026 р.
Identity
| category | backup_switching_devices |
| manufacturer | GoodWe |
| model | STS200-80-10 |
| region | GLOBAL |
| variant | — |
Electrical
| ac_connection |
3L / N / PE
GoodWe STS Datasheet (EN)
|
| ac_side_relay_nominal_current_a |
200
GoodWe STS Datasheet (EN)
|
| backup_max_apparent_power_with_grid_va |
138000
GoodWe STS Datasheet (EN)
|
| backup_max_apparent_power_without_grid_va |
55000
GoodWe STS Datasheet (EN)
|
| backup_max_current_a |
83.3
GoodWe STS Datasheet (EN)
|
| cooling |
Natural Convection
GoodWe STS Datasheet (EN)
|
| emc_standards |
['EN61000-6-1', 'EN61000-6-2', 'EN61000-6-3', 'EN61000-6-4']
GoodWe STS Datasheet (EN)
|
| frequency_hz |
50 / 60
GoodWe STS Datasheet (EN)
|
| frequency_range_hz |
45 ~ 65
GoodWe STS Datasheet (EN)
|
| generator_side_max_apparent_power_va |
55000
GoodWe STS Datasheet (EN)
|
| generator_side_relay_nominal_current_a |
90
GoodWe STS Datasheet (EN)
|
| max_operating_altitude_m |
4000
GoodWe STS Datasheet (EN)
|
| nominal_apparent_power_va |
50000
GoodWe STS Datasheet (EN)
|
| output_voltage_range_v |
176 ~ 276
GoodWe STS Datasheet (EN)
|
| phase_count |
3
GoodWe STS Datasheet (EN)
|
| rated_current_a |
72.5
GoodWe STS Datasheet (EN)
|
| rated_voltage_v |
380 / 400
GoodWe STS Datasheet (EN)
|
| safety_standards |
['IEC62109-1', 'IEC62109-2']
GoodWe STS Datasheet (EN)
|
| topology |
Non-isolated
GoodWe STS Datasheet (EN)
|
| transfer_time_ms |
10
GoodWe STS Datasheet (EN)
|
Physical / mechanical
| dimensions_mm |
510 × 425 × 156
GoodWe STS Datasheet (EN)
|
| weight_kg |
16.5
GoodWe STS Datasheet (EN)
|
Installation
| mounting |
Wall Mounted
GoodWe STS Datasheet (EN)
|
Environment
| ip_rating |
IP65
GoodWe STS Datasheet (EN)
|
| operating_temperature_max_c |
60
GoodWe STS Datasheet (EN)
|
| operating_temperature_min_c |
-35
GoodWe STS Datasheet (EN)
|
Interfaces & connectors
| communications |
['RS485']
GoodWe STS Datasheet (EN)
|
| documented_ports | [{'port_role': 'GRID', 'port_label_from_manual': 'Grid Side', 'port_type': 'AC_TERMINAL', 'direction': 'INPUT', 'electrical_domain': 'AC', 'document': 0, 'page': "column 'STS200-80-10'", 'quote': 'Grid Side Data Nominal Current (A) 72.5'}, {'port_role': 'BACKUP_LOAD', 'port_label_from_manual': 'Back-up Side', 'port_type': 'AC_TERMINAL', 'direction': 'OUTPUT', 'electrical_domain': 'AC', 'document': 0, 'page': "column 'STS200-80-10'", 'quote': 'Back-up Side Data Max. Apparent Power with Grid (VA) 138000'}, {'port_role': 'AC_IN', 'port_label_from_manual': 'Inverter Side', 'port_type': 'AC_TERMINAL', 'direction': 'INPUT', 'electrical_domain': 'AC', 'document': 0, 'page': "column 'STS200-80-10'", 'quote': 'Inverter Side Data Nominal Apparent Power (VA) 50000'}, {'port_role': 'GENERATOR', 'port_label_from_manual': 'Generator / PV Inverter Side', 'port_type': 'AC_TERMINAL', 'direction': 'INPUT', 'electrical_domain': 'AC', 'document': 0, 'page': "column 'STS200-80-10'", 'quote': 'Generator / PV Inverter Side Data Max. Apparent Power (VA) 55000'}, {'port_role': 'RS485', 'port_label_from_manual': 'Communication with Inverter', 'port_type': 'RS485', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': "column 'STS200-80-10', General Data", 'quote': 'Communication with Inverter RS485'}] |
Документи
datasheet
GoodWe STS Datasheet (EN)
product_page
GoodWe STS Series (125-138 kW) - product page
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| withheld:backup_output | true |
| withheld:cooling | "Natural Convection" |
| withheld:grid_input | true |
| withheld:grid_isolation | true |
| withheld:inverter_input | true |
| withheld:mounting | "Wall-mounted" |
| withheld:whole_home_backup | false |