⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Backup Switching Devices

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category backup_switching_devices
manufacturer Socomec
model 16000025
region GLOBAL
variant —

Electrical

compatible_transfer_switches ATyS r, ATyS S and ATyS d M
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
dead_band_timer_s 0 / 2
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
device_role ATS controller for remotely operated transfer switching equipment
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
digital_inputs 5
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
digital_outputs 4
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
door_cutout_mm 138 x 92
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
frequency_limits_hz 45 - 65
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
frequency_threshold_settings 5% / 10% of nominal frequency
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
impulse_withstand_kv 6/4
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
modbus_baud_rate 2400-38400
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
nominal_frequency_hz 50
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
overvoltage_category CAT 3
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
power_consumption_w < 10 W
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
rated_voltage_v 230 / 400
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
source_fail_timer_s 3 / 10
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
source_return_timer_min 0 (3s) / 3 / 10 / 30
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
supply_voltage_ac_v 184 - 300 VAC
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
supply_voltage_dc_v 10-30 VDC
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
voltage_threshold_settings 10% / 20% of Nominal voltage
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
weight_g 845
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)

Environment

operating_temperature_c -25 ... +70
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)

Interfaces & connectors

communications RS485
ATyS C25 ATS Controller - entry-level functionalities
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Product page - communication', 'quote': 'RS485 Modbus communication'}]
protocols ['Modbus RTU']
ATyS C25 ATS Controller - entry-level functionalities

Certifications

standards ['IEC 61010-2-201', 'IEC 60947-6-1', 'GB/T 14048.11 Annexe C']
ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)

Документи

application_note ATS controller for Transfer Switching Equipment (brochure EN)
datasheet ATyS C25 ATS Controller - catalogue pages (PCG021 EN V01)
product_page ATyS C25 ATS Controller - entry-level functionalities
quick_start_guide ATyS C25 ATS Controller - quick start guide

Зафіксовані конфлікти

interfaces.communications Resolved — kept current value
RS485 — stored value
RS485, 2 to 3 half duplex wires, MODBUS RTU — Interface type RS485. 2 to 3 half duplex wires / Protocol MODBUS RTU
Detected during import deep-enrich-2026-09-batch01

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesControl unit only, no power path. Declared to IEC 61010-2-201, IEC 60947-6-1 and GB/T 14048.11 Annex C, i.e. the same article is sold worldwide.