⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Batteries

Fortress Power eVault Classic 18.5kWh

Побудувати систему з цим продуктом

Official manufacturer NA перевірено 25 вересня 2026 р.

Identity

category batteries
manufacturer Fortress Power
model eVault Classic 18.5kWh
region —

Electrical

capacity_ah 360
eVault Classic 18.5kWh LFP Battery
dc_voltage_max_v 55
eVault Classic 18.5kWh LFP Battery
dc_voltage_min_v 48
eVault Classic 18.5kWh LFP Battery
depth_in 21.3
eVault Classic 18.5kWh LFP Battery
height_in 38.8
eVault Classic 18.5kWh LFP Battery
internal_breaker_a 250
eVault Classic 18.5kWh LFP Battery
max_charge_current_a 170
eVault Classic 18.5kWh LFP Battery
max_discharge_current_a 180
eVault Classic 18.5kWh LFP Battery
max_parallel_units 12
eVault Classic 18.5kWh LFP Battery
max_pulse_current_a 200 (10 s)
eVault Classic 18.5kWh LFP Battery
nominal_energy_kwh 18.5
eVault Classic 18.5kWh LFP Battery
nominal_voltage_v 51.2
eVault Classic 18.5kWh LFP Battery
recommended_charge_current_a 100
eVault Classic 18.5kWh LFP Battery
round_trip_efficiency_percent >98
eVault Classic 18.5kWh LFP Battery
scalability Maximum 12 in Parallel (222 kWh)
eVault Classic 18.5kWh LFP Battery
warranty 5/10 Years
eVault Classic 18.5kWh LFP Battery
weight_lbs 476
eVault Classic 18.5kWh LFP Battery
width_in 19.2
eVault Classic 18.5kWh LFP Battery

Installation

mounting Floor standing
eVault Classic 18.5kWh LFP Battery

Environment

charging_temperature_f 32 to 113
eVault Classic 18.5kWh LFP Battery
discharging_temperature_f 32 to 113
eVault Classic 18.5kWh LFP Battery
ip_rating IP21
eVault Classic 18.5kWh LFP Battery
recommended_storage_temperature_f 50 to 95
eVault Classic 18.5kWh LFP Battery

Interfaces & connectors

communications ['CAN', 'RS485']
eVault Classic 18.5kWh LFP Battery

Документи

application_note eVault disassembly and charging V1.3
installation_manual eVault 18.5 Installation Manual Rev. 9.6
product_page eVault Classic 18.5kWh LFP Battery

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesUS manufacturer; all published certification is North American (UL 1973 / UL 9540 / UL 9540A / CEC / SGIP / OGPe) and ANMA already stores Fortress Power under region NA.