Wärtsilä GridSolv Quantum High Energy
Official manufacturer GLOBAL перевірено 23 вересня 2026 р.
Identity
| category | battery_cabinets |
| manufacturer | Wärtsilä |
| model | GridSolv Quantum High Energy |
| region | GLOBAL |
Electrical
| auxiliary_peak_load_kw |
11.5
GridSolve(TM) Quantum High Energy solution sheet
|
| auxiliary_supply_voltage |
208/400 V 60 Hz and 380 - 415 V 50 Hz 4-wire
GridSolve(TM) Quantum High Energy solution sheet
|
| c_rate_range |
0.25 - 0.5 C
GridSolve(TM) Quantum High Energy solution sheet
|
| coolant_type |
Water and glycol mix
GridSolve(TM) Quantum High Energy solution sheet
|
| cooling |
liquid
GridSolve(TM) Quantum High Energy solution sheet
|
| dc_voltage_max_v |
1518
GridSolve(TM) Quantum High Energy solution sheet
|
| dc_voltage_min_v |
1040
GridSolve(TM) Quantum High Energy solution sheet
|
| fire_wall_rating_minutes |
240
GridSolve(TM) Quantum High Energy solution sheet
|
| module_configuration |
4P x 8 x 52S
GridSolve(TM) Quantum High Energy solution sheet
|
| nominal_dc_voltage_v |
1331
GridSolve(TM) Quantum High Energy solution sheet
|
| nominal_energy_kwh |
1629
GridSolve(TM) Quantum High Energy solution sheet
|
| topology |
cabinet
GridSolve(TM) BESS portfolio
|
Physical / mechanical
| height_mm |
2600
GridSolve(TM) Quantum High Energy solution sheet
|
| length_mm |
3300
GridSolve(TM) Quantum High Energy solution sheet
|
| weight_kg |
13500
GridSolve(TM) Quantum High Energy solution sheet
|
| width_mm |
2100
GridSolve(TM) Quantum High Energy solution sheet
|
Environment
| operating_temperature_max_c |
50
GridSolve(TM) Quantum High Energy solution sheet
|
| operating_temperature_min_c |
-30
GridSolve(TM) Quantum High Energy solution sheet
|
Документи
product_page
GridSolve(TM) BESS portfolio
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | One worldwide unit. The sheet prints a single auxiliary-supply row covering 208/400 V 60 Hz and 380-415 V 50 Hz, so the electrical specification is not split by market. |