⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Commercial Ess

Official manufacturer GLOBAL перевірено 20 вересня 2026 р.

Identity

category commercial_ess
ean —
firmware {'documented_version': 'UNKNOWN', 'constraints': 'UNKNOWN'}
generation G3
manufacturer AlphaESS
market_version Multi-region: certification list names VDE 4105 / VDE 4110, EN 50549, AS4777, NRS 097, NC RFG, G99/G100
model STORION-H50-G3
mpn —
product_family STORION
product_status active
region GLOBAL
release_year —
series COMMERCIAL & INDUSTRIAL SERIES
sku —

Electrical

ac_connection 3L / N / PE
ac_voltage_range —
backup_max_output_apparent_power_off_grid_va 50000
backup_nominal_output_power_off_grid_w 50000
battery_capacity_range_kwh 120.5 kWh (standard rack, 5 x M77314-S)
battery_cell_configuration 3.2 V / 314 Ah @ 1P24S
battery_communication CAN
battery_max_charge_current_a 157
battery_max_charge_power_w —
battery_max_discharge_current_a 157
battery_max_discharge_power_w —
battery_module_connection 5 in series
battery_module_dimensions_mm 525 x 856 x 260 mm
battery_module_ingress_protection IP 20
battery_module_max_charge_discharge_current_a 157
battery_module_model M77314-S
battery_module_nominal_capacity_kwh 24.1
battery_module_nominal_voltage_v 76.8
battery_module_operating_voltage_range_v 69.6 V ~ 84 V
battery_module_weight_kg 168
battery_nominal_battery_voltage_v —
battery_number_of_battery_modules 5
battery_type LiFePO4
battery_voltage_range_v 348 ~ 420 V
eps_peak_power 150%, 10 s (Overload, Off-Grid)
eps_phase three-phase
eps_rated_power_va 50000
eps_switchover_time_ms 20
eps_voltage 3L / N / PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V
european_efficiency_pct 97.2
external_transfer_switch_required —
frequency_range_hz 50 / 60 Hz (± 5 Hz)
inrush_current —
max_ac_active_power_w 50000
max_ac_current_a 75.8
max_apparent_power_va —
max_backfeed_current_a —
max_dc_input_power_w 75000
max_dc_voltage_v —
max_efficiency_pct 97.8
max_input_current_per_mppt_a 50 A / 50 A / 50 A / 50 A
max_output_fault_current_a —
max_short_circuit_current_per_mppt_a —
mppt_efficiency_pct —
mppt_voltage_range_v 330 ~ 850 V
night_self_consumption_w —
nominal_ac_voltage 3L / N / PE, 220 V / 380 V; 230 V / 400 V; 240 V / 415 V
nominal_dc_voltage_v —
nominal_frequency_hz 50 / 60 Hz
number_of_mppt 4
parallel_capability Max. 10 systems on-grid parallel; max. 4 systems off-grid parallel
phase_count 3
power_factor_range 0.8 leading ... 0.8 lagging
rated_ac_power_w 50000
rated_mppt_voltage_range_v —
round_trip_efficiency_dc_to_ac_pct 92
startup_voltage_v —
strings_per_mppt 2
thd_pct < 3% (current); < 3% (voltage)

Physical / mechanical

_weight_note Printed as '1,700 kg (with 5*M77314-S)'. The H50 standard rack is 5 x M77314-S, so the parenthetical matches this model. Battery rack alone is printed as 1,600 kg.
ac_terminal —
cooling HVAC
dc_connector —
depth_mm 1300
dimensions_mm 1,120 x 1,300 x 2,050 mm
display —
enclosure_material —
height_mm 2050
mounting —
noise_db ≤ 65 dB @ 1m
weight_kg 1700
width_mm 1120

Installation

cable_requirements —
commissioning —
installation_angle —
mounting_clearances —
torque —

Environment

corrosion_protection_class C4
ingress_protection IP55
max_altitude_m 3000
operating_temperature_c -30 °C ~ 50 °C (PCS > 45°C derating)
pollution_degree —
protective_class —
relative_humidity_pct 0% ~ 90% (No Condensation)
storage_temperature_c —

Interfaces & connectors

app —
communication ['RS485', 'CAN', 'Ethernet', 'Modbus TCP']
dry_contact —
meter_interface DTSU666 optional meter (RS485/Modbus RTU, CAN) as named in the datasheet
monitoring_portal —
protocols ['Modbus TCP', 'API']

Protection

anti_islanding —
arc_fault —
dc_switch —
fire_fighting_system Aerosol + Smoke / Temperature Detection
insulation_monitoring —
overvoltage_category —
rcmu —
reverse_polarity —
surge_protection_ac —
surge_protection_dc —

Certifications

standards ['IEC 61000-1/-2/-3/-4', 'IEC 62109', 'IEC 62477', 'EN 50549', 'VDE 4105', 'VDE 4110', 'AS4777', 'NRS 097', 'NC RFG', 'G99/G100']

Warranty & service

battery_years 10
conditions Printed as '5 Years' product warranty and '10 Years' battery warranty
cycle_life 8,000@EOL 70% (under specific test conditions)
extension_options —
standard_years 5

Документи

datasheet STORION-H30/H50-G3 COMMERCIAL & INDUSTRIAL SERIES rev V09.19082025
product-page AlphaESS STORION-H30/H50-G3 commercial & industrial energy storage cabinet rev UNKNOWN

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

Cycle Life8,000@EOL 70%**
Internal Resistance≤ 10 mΩ
Max. Input Apparent Power (On-Grid)60 kVA (H30) / 80 kVA (H50)
Max. Short-circuit Currentread 1 of id=345 returned '210 V'; targeted re-read of the same PDF returned 'CANNOT READ'
Max. Systems On-Grid Parallel / Off-Grid Parallel10 / 4
Maximum battery racks per system2 battery racks per system; additional battery cabinet required for expansion
Module Operating Temp Range-20 °C ~ 50 °C***
Rack Weight1,600 kg (with 5 * M77314-S)
Round-trip efficiency, DC to AC92%
Start-up voltageread 1 of id=345 returned '210 V'; re-read returned '200 ~ 850 V' (H30) / '330 ~ 850 V' (H50), duplicating the MPPT voltage-range row
backup.max_output_apparent_power_off_grid_va50000
backup.nominal_output_power_off_grid_w50000
battery.cell_configuration3.2 V / 314 Ah @ 1P24S
battery.communicationCAN
battery.max_charge_current_a157
battery.max_charge_power_wUNKNOWN
battery.max_discharge_current_a157
battery.max_discharge_power_wUNKNOWN
battery.module_dimensions_mm525 x 856 x 260 mm
battery.module_ingress_protectionIP 20
battery.module_max_charge_discharge_current_a157
battery.module_modelM77314-S
battery.module_nominal_capacity_kwh24.1
battery.module_nominal_voltage_v76.8
battery.module_operating_voltage_range_v69.6 V ~ 84 V
battery.module_weight_kg168
battery.nominal_battery_voltage_vUNKNOWN
battery.number_of_battery_modules5