Electrical
| ac_voltage_tolerance |
-12% ~ +10%
HyperCube II — 交直流一体户外柜 product page
|
| ac_voltage_v |
480
HyperCube II — 交直流一体户外柜 product page
|
| battery_configuration |
1P260S
HyperCube II — 交直流一体户外柜 product page
|
| battery_pack_ip_rating |
IP67
HyperCube II — 交直流一体户外柜 product page
|
| cell_capacity_ah |
280
HyperCube II — 交直流一体户外柜 product page
|
| chemistry |
LFP
HyperCube II — 交直流一体户外柜 product page
|
| cooling |
liquid
HyperCube II — 交直流一体户外柜 product page
|
| dc_voltage_max_v |
923
HyperCube II — 交直流一体户外柜 product page
|
| dc_voltage_min_v |
754
HyperCube II — 交直流一体户外柜 product page
|
| dc_voltage_nominal_v |
832
HyperCube II — 交直流一体户外柜 product page
|
| electrical_compartment_ip_rating |
IP54
HyperCube II — 交直流一体户外柜 product page
|
| enclosure_type |
交直流一体户外柜
HyperCube II — 交直流一体户外柜 product page
|
| fire_suppression |
可燃气体检测、温度检测、烟雾探测、舱级气溶胶、通风系统、水消防
HyperCube II — 交直流一体户外柜 product page
|
| grid_frequency_hz |
60
HyperCube II — 交直流一体户外柜 product page
|
| max_efficiency_percent |
91
HyperCube II — 交直流一体户外柜 product page
|
| nominal_energy_kwh |
232.9
HyperCube II — 交直流一体户外柜 product page
|
| operating_humidity_percent |
0~95
HyperCube II — 交直流一体户外柜 product page
|
| pcs_integrated |
True
HyperCube II — 交直流一体户外柜 product page
|
| power_factor_range |
-1~+1
HyperCube II — 交直流一体户外柜 product page
|
| rated_apparent_power_kva |
115
HyperCube II — 交直流一体户外柜 product page
|
| rated_power_kw |
115
HyperCube II — 交直流一体户外柜 product page
|
| topology |
cabinet
HyperCube II — 交直流一体户外柜 product page
|
Physical / mechanical
| dimensions_mm |
1030*1350*2400
HyperCube II — 交直流一体户外柜 product page
|
| height_mm |
2400
HyperCube II — 交直流一体户外柜 product page
|
| length_mm |
1030
HyperCube II — 交直流一体户外柜 product page
|
| weight_kg |
2600
HyperCube II — 交直流一体户外柜 product page
|
| width_mm |
1350
HyperCube II — 交直流一体户外柜 product page
|
Environment
| ip_rating |
IP55
HyperCube II — 交直流一体户外柜 product page
|
| max_altitude_m |
4000
HyperCube II — 交直流一体户外柜 product page
|
| operating_temperature_max_c |
55
HyperCube II — 交直流一体户外柜 product page
|
| operating_temperature_min_c |
-25
HyperCube II — 交直流一体户外柜 product page
|
Interfaces & connectors
| communications |
['CAN', 'Ethernet', 'RS485']
суперечливе
HyperCube II — 交直流一体户外柜 product page
|
| documented_ports | [{'port_role': 'CAN', 'port_label_from_manual': 'CAN', 'port_type': 'CAN', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'spec table row 通信接口', 'quote': '通信接口 | CAN、以太网、RS485'}, {'port_role': 'ETHERNET', 'port_label_from_manual': '以太网', 'port_type': 'ETHERNET', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'spec table row 通信接口', 'quote': '通信接口 | CAN、以太网、RS485'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS485', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'spec table row 通信接口', 'quote': '通信接口 | CAN、以太网、RS485'}] |
Certifications
| certifications |
['UL1973', 'UL9540', 'UL9540A', 'NFPA69', 'NFPA855', 'UN38.3', 'UL1741']
HyperCube II — 交直流一体户外柜 product page
|
Документи
product_page
HyperCube II — 交直流一体户外柜 product page
Зафіксовані конфлікти
interfaces.communications Review required
['CAN', 'Ethernet', 'RS485'] — stored value
['CAN', '以太网', 'RS485'] — 通信接口 | CAN、以太网、RS485
Detected during import deep-enrich-2026-09-batch07
electrical.cooling Resolved — kept current value
liquid — stored value
全智能液冷(电池+PCS) — 冷却方式 | 全智能液冷(电池+PCS)
Detected during import deep-enrich-2026-09-batch07
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | North-American edition: 480 Vac / 60 Hz, UL1973/UL9540/UL9540A/NFPA69/NFPA855/UL1741. |