Continental Control Systems ACTL-1250-250

Official manufacturer US перевірено 25 вересня 2026 р.

Identity

category current_transformers
manufacturer Continental Control Systems
model ACTL-1250-250
region US
variant —

Electrical

accuracy_class Standard (1.2)
Accu-CT ACTL-1250 Split-Core CT
accuracy_option_c06_percent 0.5
Accu-CT ACTL-1250 Split-Core CT
accuracy_percent 0.75
Accu-CT ACTL-1250 Split-Core CT
aperture_size 1.25 x 1.77 in
Accu-CT ACTL-1250 Split-Core CT
cable_gauge_awg 20
Accu-CT ACTL-1250 Split-Core CT
cable_length_m 2.4
Accu-CT ACTL-1250 Split-Core CT
ct_type split_core
Accu-CT ACTL-1250 Split-Core CT
frequency_hz 50-60
Accu-CT ACTL-1250 Split-Core CT
internal_burden_resistance_ohm 8.0
ACTL-1250 Internal Burden Resistance
measurement_category 600 Vac CAT IV
Accu-CT ACTL-1250 Split-Core CT
operating_humidity_percent_rh [5, 95]
Accu-CT ACTL-1250 Split-Core CT
output_voltage_vac 0.333
Accu-CT ACTL-1250 Split-Core CT
phase_angle_deg 0.5
Accu-CT ACTL-1250 Split-Core CT
primary_current_a 250
Accu-CT ACTL-1250 Split-Core CT
rated_insulation_voltage_v 600
Accu-CT ACTL-1250 Split-Core CT
secondary_voltage_mv 333
Accu-CT ACTL-1250 Split-Core CT
split_core True
Accu-CT ACTL-1250 Split-Core CT
weight_g 395
Accu-CT ACTL-1250 Split-Core CT

Physical / mechanical

dimensions_mm {'width': 114.0, 'height': 83.4, 'thickness': 40.2}
Accu-CT ACTL-1250 Split-Core CT

Environment

operating_temperature_max_c 75
Accu-CT ACTL-1250 Split-Core CT
operating_temperature_min_c -30
Accu-CT ACTL-1250 Split-Core CT

Certifications

certifications ['UL 2808 listed, file E363660 (XOBA)']
Accu-CT ACTL-1250 Split-Core CT

Документи

application_note ACTL-1250 Internal Burden Resistance
datasheet ACTL-0750 / ACTL-1250 brochure
datasheet ACTL-1250 Data Sheet
datasheet Accu-CT Series Sales Brochure
installation_manual ACTL-1250 CT Manual
product_page Accu-CT ACTL-1250 Split-Core CT

Зафіксовані конфлікти

electrical.measurement_category Resolved — kept current value
600 Vac CAT IV — stored value
CAT IV — 600 Vac, CAT IV (service entrance) for pollution degree 2
Detected during import deep-enrich-2026-09-batch09
electrical.frequency_hz Resolved — kept current value
50-60 — stored value
[50, 60] — Line frequency: 50 to 60 Hz nominal (available for up to 400 Hz)
Detected during import deep-enrich-2026-09-batch09
electrical.accuracy_class Resolved — kept current value
Standard (1.2) — stored value
IEEE C57.13 class 1.2 — IEEE C57.13 accuracy: class 1.2 from 1% to 120% of rated current
Detected during import deep-enrich-2026-09-batch09

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesUS manufacturer (Boulder, Colorado); the model table prints one 50-60 Hz, 600 Vac CAT IV rating, so no regional split was created.