База знань › Current Transformers (CT)
Continental Control Systems ACTL-1250-600
Official manufacturer US перевірено 25 вересня 2026 р.
Identity
| category | current_transformers |
| manufacturer | Continental Control Systems |
| model | ACTL-1250-600 |
| region | US |
| variant | — |
Electrical
| accuracy_class |
Standard (1.2)
Accu-CT ACTL-1250 Split-Core CT
|
| accuracy_option_c06_percent |
0.5
Accu-CT ACTL-1250 Split-Core CT
|
| accuracy_percent |
0.75
Accu-CT ACTL-1250 Split-Core CT
|
| aperture_size |
1.25 x 1.77 in
Accu-CT ACTL-1250 Split-Core CT
|
| cable_gauge_awg |
20
Accu-CT ACTL-1250 Split-Core CT
|
| cable_length_m |
2.4
Accu-CT ACTL-1250 Split-Core CT
|
| ct_type |
split_core
Accu-CT ACTL-1250 Split-Core CT
|
| frequency_hz |
50-60
Accu-CT ACTL-1250 Split-Core CT
|
| internal_burden_resistance_ohm |
3.3
ACTL-1250 Internal Burden Resistance
|
| measurement_category |
600 Vac CAT IV
Accu-CT ACTL-1250 Split-Core CT
|
| operating_humidity_percent_rh |
[5, 95]
Accu-CT ACTL-1250 Split-Core CT
|
| output_voltage_vac |
0.333
Accu-CT ACTL-1250 Split-Core CT
|
| phase_angle_deg |
0.5
Accu-CT ACTL-1250 Split-Core CT
|
| primary_current_a |
600
Accu-CT ACTL-1250 Split-Core CT
|
| rated_insulation_voltage_v |
600
Accu-CT ACTL-1250 Split-Core CT
|
| secondary_voltage_mv |
333
Accu-CT ACTL-1250 Split-Core CT
|
| split_core |
True
Accu-CT ACTL-1250 Split-Core CT
|
| weight_g |
395
Accu-CT ACTL-1250 Split-Core CT
|
Physical / mechanical
| dimensions_mm |
{'width': 114.0, 'height': 83.4, 'thickness': 40.2}
Accu-CT ACTL-1250 Split-Core CT
|
Environment
| operating_temperature_max_c |
75
Accu-CT ACTL-1250 Split-Core CT
|
| operating_temperature_min_c |
-30
Accu-CT ACTL-1250 Split-Core CT
|
Certifications
| certifications |
['UL 2808 listed, file E363660 (XOBA)']
Accu-CT ACTL-1250 Split-Core CT
|
Документи
application_note
ACTL-1250 Internal Burden Resistance
datasheet
ACTL-0750 / ACTL-1250 brochure
datasheet
ACTL-1250 Data Sheet
datasheet
Accu-CT Series Sales Brochure
installation_manual
ACTL-1250 CT Manual
product_page
Accu-CT ACTL-1250 Split-Core CT
Зафіксовані конфлікти
electrical.measurement_category Resolved — kept current value
600 Vac CAT IV — stored value
CAT IV — 600 Vac, CAT IV (service entrance) for pollution degree 2
Detected during import deep-enrich-2026-09-batch09
electrical.frequency_hz Resolved — kept current value
50-60 — stored value
[50, 60] — Line frequency: 50 to 60 Hz nominal (available for up to 400 Hz)
Detected during import deep-enrich-2026-09-batch09
electrical.accuracy_class Resolved — kept current value
Standard (1.2) — stored value
IEEE C57.13 class 1.2 — IEEE C57.13 accuracy: class 1.2 from 1% to 120% of rated current
Detected during import deep-enrich-2026-09-batch09
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | US manufacturer (Boulder, Colorado); the model table prints one 50-60 Hz, 600 Vac CAT IV rating, so no regional split was created. |