База знань › Current Transformers (CT)
DENT Instruments CT-SCM-0600-U
Official manufacturer GLOBAL перевірено 23 вересня 2026 р.
Identity
| category | current_transformers |
| manufacturer | DENT Instruments |
| model | CT-SCM-0600-U |
| region | GLOBAL |
| variant | — |
Electrical
| accuracy_class |
No IEC class printed; ratio error <1% at rated current (typical)
100/200/600A Medium Split-Core CT Data Sheet
|
| aperture_cm |
3.2
100/200/600A Medium Split-Core CT Data Sheet
|
| aperture_in |
1.25
100/200/600A Medium Split-Core CT Data Sheet
|
| aperture_mm |
32.0
100/200/600A Medium Split-Core CT Data Sheet
|
| cable_length_m |
3
100/200/600A Medium Split-Core CT Data Sheet
|
| ct_type |
split_core
суперечливе
100/200/600A Medium Split-Core CT Data Sheet
|
| dielectric_strength |
5000 VAC around case
100/200/600A Medium Split-Core CT Data Sheet
|
| dielectric_withstand_v |
5000
100/200/600A Medium Split-Core CT Data Sheet
|
| dimensions_cm |
8.26 x 8.51 x 2.54
100/200/600A Medium Split-Core CT Data Sheet
|
| frequency_hz |
50-400
суперечливе
100/200/600A Medium Split-Core CT Data Sheet
|
| housing_material |
Epoxy encapsulated housing
100/200/600A Medium Split-Core CT Data Sheet
|
| lead_description |
3 M (9.8'), twisted pair, 20 AWG
100/200/600A Medium Split-Core CT Data Sheet
|
| measurement_category |
CAT III
суперечливе
100/200/600A Medium Split-Core CT Data Sheet
|
| measuring_range |
12 to 780A AC
100/200/600A Medium Split-Core CT Data Sheet
|
| phase_error |
<2° at rated current (typical)
100/200/600A Medium Split-Core CT Data Sheet
|
| phase_error_deg |
<2° at rated current (typical)
100/200/600A Medium Split-Core CT Data Sheet
|
| primary_current_a |
600
100/200/600A Medium Split-Core CT Data Sheet
|
| rated_insulation_voltage_v |
600
100/200/600A Medium Split-Core CT Data Sheet
|
| ratio |
600 A : 333 mV
100/200/600A Medium Split-Core CT Data Sheet
|
| ratio_error |
<1% at rated current (typical)
100/200/600A Medium Split-Core CT Data Sheet
|
| secondary_voltage_mv |
333
100/200/600A Medium Split-Core CT Data Sheet
|
| window_size |
1.25" (3.20 cm)
100/200/600A Medium Split-Core CT Data Sheet
|
Environment
| operating_temperature_max_c |
55
100/200/600A Medium Split-Core CT Data Sheet
|
| operating_temperature_min_c |
-20
100/200/600A Medium Split-Core CT Data Sheet
|
Certifications
| standards |
UL STD 61010-1, EN 60044-1, CAN/CSA STD C22.2 No. 61010-1
суперечливе
100/200/600A Medium Split-Core CT Data Sheet
|
Документи
Зафіксовані конфлікти
certifications.standards Review required
UL STD 61010-1, EN 60044-1, CAN/CSA STD C22.2 No. 61010-1 — stored value
['UL STD 61010-1', 'EN 60044-1', 'CAN/CSA STD C22.2 No. 61010-1'] — Conforms to UL STD 61010-1, EN 60044-1, and CAN/CSA STD C22.2 No. 61010-1
Detected during import deep-enrich-2026-09-batch10
electrical.frequency_hz Review required
50-400 — stored value
50 to 400 Hz — 50 to 400 Hz
Detected during import deep-enrich-2026-09-batch10
electrical.measurement_category Review required
CAT III — stored value
Category III — 600 VAC, Category III
Detected during import deep-enrich-2026-09-batch10
electrical.ct_type Review required
split_core — stored value
Split-core — Split-core current transformers provide linear output voltage
Detected during import deep-enrich-2026-09-batch10
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | complete |
| region_notes | One specification; the datasheet cites UL, CAN/CSA and EN conformity together and prints no market variant. |