⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Current Transformers (CT)

Phoenix Contact PACT MCR-V2-3015-60-250-5A-1

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category current_transformers
manufacturer Phoenix Contact
model PACT MCR-V2-3015-60-250-5A-1
region GLOBAL
variant —

Electrical

accuracy_class 1
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
aperture_mm 28
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
approvals CE, UKCA, cULus (E323953)
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
article_number 2277080
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
burden_va 10
busbar_capacity_mm 30 x 15 mm; 20 x 20 mm
conductor_size_mm 30 mm width x 15 mm height
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
connection_method Screw connection, secondary conductor flexible 2 x 10 mm2, tightening torque 2 Nm
continuous_thermal_current_id 1.2 x In
ct_type solid_core
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080
dimensions_alternative_mounting_mm 60 x 82 x 31 (W x H x D)
dimensions_w_h_d_mm 31 mm x 82 mm x 60 mm
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
dynamic_current_idyn 2.5 x Ith
frequency_hz 50/60
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
housing_material PA 6.6, grey RAL 7042; UL 94 V0
humidity_conditions Indoor use only, non-condensing
instrument_security_factor 5
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
instrument_security_factor_fs 5
insulating_material_class H
insulation_voltage_v 1000
primary_current_a 250
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
rated_insulation_voltage_kv 1
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
rated_power_va 10
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
ratio 250:5 A
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
secondary_current_a 5
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
secondary_output 5 A AC
short_time_thermal_current_ith 60 x In
weight_g 285.7
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
window_diameter_mm 28

Physical / mechanical

dimensions_mm 31 x 82 x 60 (W x H x D)
weight_kg 0.2857

Environment

operating_temperature_max_c 40
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
operating_temperature_min_c -25
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
operating_temperature_range_c -25 to +40
storage_temperature_range_c -25 to +40

Certifications

certifications EN 61869; CE; UKCA; cULus Recognized (UL file E323953)
standards EN 61869
PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)

Документи

datasheet PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080 (technical data PDF export)
product_page PACT MCR-V2-3015-60-250-5A-1 - Current transformer - 2277080

Зафіксовані конфлікти

electrical.frequency_hz Resolved — kept current value
50/60 — stored value
50 / 60 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch09

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesscomplete
region_notesOne worldwide article; EN 61869 specification with CE, UKCA and cULus approvals printed on the same data sheet.