⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Current Transformers (CT)

Official manufacturer GLOBAL перевірено 23 вересня 2026 р.

Identity

category current_transformers
manufacturer Siemens
model 4NC5438-2DL21
region GLOBAL
variant —

Electrical

accuracy_class 0.5 суперечливе
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
aperture_mm 41
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
burden_va 20
busbar_dimensions 64 mm (1 bus bar) / 51 mm (2 bus bars); opening height 36 mm
conductor_size_mm max push-through conductor diameter 41 mm; opening height 36 mm
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
ct_type solid_core
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
frequency_hz 50/60
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
insulation_voltage_v 3000 (3 kV); highest operating voltage 0.72 kV
max_operational_current_a 2400
overcurrent_limiting_factor FS 5
primary_current_a 2000
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
rated_burden_va 20
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
rated_insulation_voltage_v 3000
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
rated_operational_voltage_v 720
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
ratio 2000/5 A
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
secondary_current_a 5
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
secondary_output 5
security_factor FS 5
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
short_time_thermal_current Ith 60 x Ipr for 1 s; Idyn 2.5 x Ith or 150 x Ipr суперечливе
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
terminal_type Screw-type terminals
transformer_size 4
window_diameter_mm 41

Physical / mechanical

depth_mm 77
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
dimensions_mm 112 x 127.5 x 77 (W x H x D)
height_mm 127.5
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
weight_kg 1.241
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
width_mm 112
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5

Installation

mounting Screw fixing; bushing-type (push-through) current transformer

Environment

ip_rating IP20
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
operating_temperature_max_c 55
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
operating_temperature_min_c -30
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5
operating_temperature_range_c -30 to 55
storage_temperature_range_c -30 to 70

Protection

protection_degree_ip IP20 (indoor use only, touch-protected)

Certifications

standards ['IEC 61869-2']
Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5

Документи

datasheet Data sheet 4NC5438-2DL21 - Current transformer 2000/5 A, 20 VA, Cl. 0.5

Зафіксовані конфлікти

electrical.short_time_thermal_current Review required
Ith 60 x Ipr for 1 s; Idyn 2.5 x Ith or 150 x Ipr — stored value
Ith (1 s) = 60 x Ipr; Idyn = 2.5 x Ith or 150 x Ipr (IEC 61869-2) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch10
electrical.accuracy_class Review required
0.5 — stored value
class 0.5 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch10

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesscomplete
region_notesSiemens SENTRON 4NC bushing-type CT; the TED per-article data sheet is the worldwide English edition.