⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Gateways / Data Loggers

ABB (E-mobility; NA distribution via InCharge Energy) QA/S 4.16.1

Official manufacturer GLOBAL перевірено 23 вересня 2026 р.

Identity

category gateways
manufacturer ABB суперечливе
model QA/S 4.16.1
region GLOBAL
variant —

Electrical

ambient_humidity_pct max 93 (no condensation)
data_retention Minimum 3 years with up to 64 Modbus slaves/devices
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
device_role DIN-rail Modbus RTU meter gateway and data logger with web server; forwards metering data over Modbus TCP, REST API and WebSockets
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
ethernet_ports 1
ethernet_speed 10/100BaseT (IEEE 802.3), autosensing
input_current_a < 0.05
input_voltage_v 100-240 V AC, 50/60 Hz
installation_width_modules 4 modules at 18 mm
local_modbus_available True
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
max_connected_devices 16
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
max_modbus_slaves 16
modbus_serial_baud_rates [1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200]
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
overvoltage_category III (EN 60664-1)
physical_interfaces ['1 x Ethernet RJ45 10/100BaseT', '1 x RS-485 Modbus RTU']
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
pollution_degree 2 (EN 60664-1)
power_consumption_w < 10 W at 230 V AC суперечливе
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
power_loss_w < 3
serial_baud_rates 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
serial_ports 1 x RS-485 (Modbus RTU), screw terminal
supply_voltage_v 100 - 240 V AC, 50/60 Hz суперечливе
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
supported_protocols Modbus RTU (master, RS-485); Modbus TCP; REST API; web sockets
web_server Max. 10 simultaneous users
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)

Physical / mechanical

depth_mm 64
TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)
dimensions_mm 90 x 72 x 64 (H x W x D)
enclosure_material Plastic, light grey, halogen-free; UL94 V-0
height_mm 90
TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)
weight_kg 0.15
width_mm 72
TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)

Installation

mounting 35 mm DIN rail, 4 modules at 18 mm width, 68 mm depth суперечливе
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)

Environment

ip_rating IP 20
TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)
operating_temperature_max_c 45
TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)
operating_temperature_min_c -5
TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)
operating_temperature_range_c -5 to +45
storage_temperature_range_c -25 to +55

Interfaces & connectors

cloud_required False
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
documented_ports [{'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'RJ45 10/100BaseT IEEE 802.3', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical data', 'quote': '"RJ45 connector for 10/100BaseT IEEE 802.3 networks, autosensing"'}, {'port_role': 'RS485', 'port_label_from_manual': 'Modbus RTU (RS-485)', 'port_type': 'RS-485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical data', 'quote': 'Modbus RTU Interface (RS-485): Available baud rates include "1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200"'}]
protocols ['Modbus RTU (RS-485) downstream', 'Modbus TCP', 'REST API', 'WebSockets', 'HTTP (web server)'] суперечливе
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)

Protection

degree_of_protection IP 20 according to EN 60529
PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)
protection_class II (EN 61140)
protection_degree_ip IP20

Certifications

certifications CE (EMC Directive, Low Voltage Directive)

Документи

datasheet TECHNICAL DATA EQmatic Energy Analyzer, Modbus QA/S 4.16.1 QA/S 4.64.1 (2CDC512102D0211)
manual PRODUCT MANUAL EQmatic Energy Analyzer, M-Bus / Modbus QA/S x.yy.1 (2CDC512090D0202)

Зафіксовані конфлікти

installation.mounting Review required
35 mm DIN rail, 4 modules at 18 mm width, 68 mm depth — stored value
35 mm DIN rail (DIN EN 60715); modular DIN rail component (MDRC), Pro M design — incoming package
Detected during import deep-enrich-pass2-2026-09-batch09
electrical.power_consumption_w Review required
< 10 W at 230 V AC — stored value
< 10 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch09
identity.manufacturer Review required
ABB — stored value
ABB (E-mobility; NA distribution via InCharge Energy) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch09
interfaces.protocols Review required
['Modbus RTU (RS-485) downstream', 'Modbus TCP', 'REST API', 'WebSockets', 'HTTP (web server)'] — stored value
['Modbus RTU', 'Modbus TCP', 'REST API', 'web sockets'] — Protocols Modbus-TCP, REST API, web sockets
Detected during import wave4-2026-09-batch05
electrical.supply_voltage_v Review required
100 - 240 V AC, 50/60 Hz — stored value
100-240 V AC, 50/60 Hz — Supply voltage 100-240 V AC, 50/60 Hz
Detected during import wave4-2026-09-batch05
identity.manufacturer Review required
ABB — stored value
ABB (E-mobility; NA distribution via InCharge Energy) — incoming package
Detected during import wave4-2026-09-batch05

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesOne worldwide specification; 100-240 V AC mains supply, DIN-rail.
withheld:ethernet_port_count1
withheld:meter_type"not applicable - gateway"
withheld:phase_count"not applicable - gateway, not a meter"
withheld:rs485_port_count1