База знань › Gateways / Data Loggers
HMS Networks Anybus Communicator - Modbus RTU Server to Modbus TCP Client
Manufacturer documented GLOBAL
Identity
| category | gateways |
| manufacturer | HMS Networks |
| manufacturer_part_number | ABC3210-A |
| model | Anybus Communicator - Modbus RTU Server to Modbus TCP Client |
| mpn | ABC3210-A |
| product_family | Anybus Communicator (gen 2) |
| product_status | active |
| region | GLOBAL |
| series | Anybus Communicator |
| variant | — |
Electrical
| current_consumption_max |
125 mA @ 24 V DC (3 W)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Current Consumption Max value at Vcc nom (mA)'
|
| current_consumption_typical |
90 mA @ 24 V DC (2.2 W)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Current Consumption Type Value at Vcc Nom (mA)'
|
| galvanic_isolation |
Yes (boolean only; no test voltage printed)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Isolation'
|
| input_voltage_v |
12-30 V DC
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Input Voltage (V)'
|
| model_code |
40-SER-ETH-B
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Identification and Status, row 'Model Code'
|
| predecessor_models |
AB9005-B
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Identification and Status, row 'Predecessor'
|
| product_id |
ABC3210-A
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Identification and Status, row 'Product ID'
|
| security_features |
Security lock switch
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features, row 'DIP & Rotary Switches'
|
| warranty_years |
5 years
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Warranty (years)'
|
Physical / mechanical
| dimensions_mm |
27 x 144 x 98 (W x H x D) mm
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, rows 'Net Width/Height/Depth (mm)'
|
| housing_material |
PC ABS, UL 94 V0
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Housing Materials'
|
| weight_g |
150 g
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Net Weight (g)'
|
Installation
| mounting |
DIN-rail (EN 50022 standard)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Mounting'
|
Environment
| ip_rating |
IP20
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Certifications and Standards, row 'Protection Class IP'
|
| operating_temperature_range_c |
-25 to +70 C
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, rows 'Operating Temperature C Min/Max'
|
| storage_temperature_range_c |
-40 to +85 C
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, rows 'Storage Temperature C Min/Max'
|
Interfaces & connectors
| device_type | Modbus RTU slave to Modbus TCP master protocol gateway |
| ethernet_ports |
2 x RJ45 plus a separate RJ45 configuration port
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features, row 'Connectors / Input / Output'
|
| ethernet_speed |
10/100 Mbit/s, down to 10 ms
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Bandwidth'
|
| home_assistant_modbus_tcp_suitable | False |
| home_assistant_suitability_basis | NOT suitable as a Home Assistant Modbus TCP target. The datasheet prints 'Modbus-TCP Mode: Master / Client' and 'Modbus-RTU Mode: Slave mode' - the gateway is itself the Modbus TCP client and the Modbus RTU server, i.e. the opposite direction to ABC3028-A. A Home Assistant Modbus TCP client has nothing to connect to. |
| modbus_rtu_functions |
1, 2, 3, 4, 5, 6, 8, 15, 16, 22, 23, 43/14
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Modbus-RTU Functions Supported'
|
| modbus_rtu_role |
Slave mode (the gateway is a Modbus RTU server on the serial side)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Modbus-RTU Mode'
|
| modbus_tcp_capacity |
152 transactions / 64 connections
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP No. Of Servers'
|
| modbus_tcp_functions |
1, 2, 3, 4, 5, 6, 15, 16, 23
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Functions Supported'
|
| modbus_tcp_role |
Master / Client (the gateway is the Modbus TCP client on the Ethernet side)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Mode'
|
| modbus_tcp_spec |
Modbus specification V1.1B
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Supported Functionality'
|
| rs232 |
true
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality' (literal 'RS-232')
|
| rs422 |
not stated
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality'
|
| rs485 |
true
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality' (literal 'RS-485')
|
| serial_baud_rates |
1200; 1800; 2400; 4800; 7200; 9600; 14400; 19200; 35700; 38400; 57600; 115200; 128000 bit/s
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Modbus-RTU Baud Rate'
|
| serial_data_format |
8 data bits; parity none/odd/even; 1 or 2 stop bits
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality'
|
| serial_port_count |
1
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features, row 'Connectors / Input / Output'
|
| serial_ports |
1 x serial port on a 7-pin 5.08 mm pluggable screw connector; RS-232 and RS-485 named. RS-422 is NOT named.
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features 'Connectors / Input / Output' + Modbus-RTU 'Supported Functionality'
|
Certifications
| certifications |
CE, UL, KC, WEEE, EMC; UL file E214107 (UL 61010-1, CSA C22.2 No. 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-2-201)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Certifications and Standards
|