⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Gateways / Data Loggers

HMS Networks Anybus Communicator - Modbus RTU Server to Modbus TCP Client

Manufacturer documented GLOBAL

Identity

category gateways
manufacturer HMS Networks
manufacturer_part_number ABC3210-A
model Anybus Communicator - Modbus RTU Server to Modbus TCP Client
mpn ABC3210-A
product_family Anybus Communicator (gen 2)
product_status active
region GLOBAL
series Anybus Communicator
variant —

Electrical

current_consumption_max 125 mA @ 24 V DC (3 W)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Current Consumption Max value at Vcc nom (mA)'
current_consumption_typical 90 mA @ 24 V DC (2.2 W)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Current Consumption Type Value at Vcc Nom (mA)'
galvanic_isolation Yes (boolean only; no test voltage printed)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Isolation'
input_voltage_v 12-30 V DC
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Input Voltage (V)'
model_code 40-SER-ETH-B
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Identification and Status, row 'Model Code'
predecessor_models AB9005-B
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Identification and Status, row 'Predecessor'
product_id ABC3210-A
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Identification and Status, row 'Product ID'
security_features Security lock switch
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features, row 'DIP & Rotary Switches'
warranty_years 5 years
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Warranty (years)'

Physical / mechanical

dimensions_mm 27 x 144 x 98 (W x H x D) mm
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, rows 'Net Width/Height/Depth (mm)'
housing_material PC ABS, UL 94 V0
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Housing Materials'
weight_g 150 g
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Net Weight (g)'

Installation

mounting DIN-rail (EN 50022 standard)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, row 'Mounting'

Environment

ip_rating IP20
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Certifications and Standards, row 'Protection Class IP'
operating_temperature_range_c -25 to +70 C
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, rows 'Operating Temperature C Min/Max'
storage_temperature_range_c -40 to +85 C
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — General, rows 'Storage Temperature C Min/Max'

Interfaces & connectors

device_type Modbus RTU slave to Modbus TCP master protocol gateway
ethernet_ports 2 x RJ45 plus a separate RJ45 configuration port
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features, row 'Connectors / Input / Output'
ethernet_speed 10/100 Mbit/s, down to 10 ms
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Bandwidth'
home_assistant_modbus_tcp_suitable False
home_assistant_suitability_basis NOT suitable as a Home Assistant Modbus TCP target. The datasheet prints 'Modbus-TCP Mode: Master / Client' and 'Modbus-RTU Mode: Slave mode' - the gateway is itself the Modbus TCP client and the Modbus RTU server, i.e. the opposite direction to ABC3028-A. A Home Assistant Modbus TCP client has nothing to connect to.
modbus_rtu_functions 1, 2, 3, 4, 5, 6, 8, 15, 16, 22, 23, 43/14
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Modbus-RTU Functions Supported'
modbus_rtu_role Slave mode (the gateway is a Modbus RTU server on the serial side)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Modbus-RTU Mode'
modbus_tcp_capacity 152 transactions / 64 connections
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP No. Of Servers'
modbus_tcp_functions 1, 2, 3, 4, 5, 6, 15, 16, 23
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Functions Supported'
modbus_tcp_role Master / Client (the gateway is the Modbus TCP client on the Ethernet side)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Mode'
modbus_tcp_spec Modbus specification V1.1B
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-TCP Features, row 'Modbus-TCP Supported Functionality'
rs232 true
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality' (literal 'RS-232')
rs422 not stated
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality'
rs485 true
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality' (literal 'RS-485')
serial_baud_rates 1200; 1800; 2400; 4800; 7200; 9600; 14400; 19200; 35700; 38400; 57600; 115200; 128000 bit/s
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Modbus-RTU Baud Rate'
serial_data_format 8 data bits; parity none/odd/even; 1 or 2 stop bits
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Modbus-RTU Features, row 'Supported Functionality'
serial_port_count 1
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features, row 'Connectors / Input / Output'
serial_ports 1 x serial port on a 7-pin 5.08 mm pluggable screw connector; RS-232 and RS-485 named. RS-422 is NOT named.
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Physical Features 'Connectors / Input / Output' + Modbus-RTU 'Supported Functionality'

Certifications

certifications CE, UL, KC, WEEE, EMC; UL file E214107 (UL 61010-1, CSA C22.2 No. 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-2-201)
HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client — Certifications and Standards

Документи

datasheet HMS generated datasheet (EN) - Anybus Communicator - Modbus RTU Server to Modbus TCP Client