⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Gateways / Data Loggers

Manufacturer documented GLOBAL

Identity

category gateways
manufacturer Weidmüller
manufacturer_part_number 1504460000
model IE-GW-MB-2TX-1RS232/485
mpn 1504460000
product_family Weidmueller Modbus gateways
product_status active
region GLOBAL
series IE-GW-MB
variant —

Electrical

input_voltage_v 24 V DC, 2 redundant inputs; range 12 to 48 V DC V DC
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Power supply rows
order_number 1504460000
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — General ordering data, row 'Order No.'
version_description Modbus TCP/Modbus Seriell Gateway, 2x RJ45, 1x DB9 for RS-232, 1x terminal block for RS-422/485, IP30, 0 C...60 C
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — General ordering data, row 'Version'

Physical / mechanical

dimensions_mm 29 x 124.5 x 89.2 (W x H x D) mm
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Dimensions rows

Environment

ip_rating IP30
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Protection degree row
operating_temperature_range_c 0 to +60 C
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Temperatures, row 'Operating'
storage_temperature_range_c -40 to +85 C
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Temperatures, row 'Storage'

Interfaces & connectors

device_type Modbus TCP to Modbus serial gateway
ethernet_ports 2 x RJ45 10/100BaseT(X), auto MDI/MDI-X
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Ethernet row
home_assistant_modbus_tcp_suitable True
home_assistant_suitability_basis The data sheet's Version row names the product 'Modbus TCP/Modbus Seriell Gateway' and the Operating modes row prints 'RTU Slave, RTU Master, ASCII Slave, ASCII Master' for the serial side. With the serial side set to RTU Master the Ethernet side serves Modbus TCP clients, so a standard Modbus TCP client (Home Assistant) reaches serial Modbus RTU slaves. Recorded limitation: the data sheet does not print the Modbus TCP server connection count, the default IP address or the Modbus TCP port number, so the mode name is the whole documented basis.
modbus_serial_modes RTU Slave, RTU Master, ASCII Slave, ASCII Master
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — row 'Operating modes'
rs232 true (on the DB9 male connector)
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Serial interface, rows 'Interface standards' / 'Connection type'
rs422 true (on the 5-pole removable terminal block)
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Serial interface, rows 'Interface standards' / 'Connection type'
rs485 true (on the 5-pole removable terminal block)
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Serial interface, rows 'Interface standards' / 'Connection type'
serial_baud_rates 50 bit/s to 921.6 kbit/s
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Serial interface, row 'Baud rate'
serial_port_count 1 serial channel presented on two connectors (1 x DB9 male for RS-232, 1 x removable 5-pole terminal block for RS-422/485)
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Serial interface, rows 'Interface standards' and 'Connection type'

Certifications

certifications cULus (E230683); cULusEX (E223527); RoHS compliant
Weidmueller data sheet IE-GW-MB-2TX-1RS232/485 — Approvals row

Документи

datasheet Weidmueller data sheet IE-GW-MB-2TX-1RS232/485
product-page IE-GW-MB-2TX-1RS232/485 — official product page