CHINT CPS SCH100KTL-DO/US-480
Official manufacturer US перевірено 25 вересня 2026 р.
Identity
| category | inverters |
| manufacturer | CHINT |
| model | CPS SCH100KTL-DO/US-480 |
| region | US |
| variant | 3-phase |
Electrical
| ac_voltage_range |
423-528 Vac
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| ac_voltage_v |
480
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| cec_efficiency_percent |
98.0
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| cooling_method |
Variable speed cooling fans
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| dc_disconnect |
Load-rated DC switch
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| dc_input_voltage_range |
750-1450 Vdc
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| grid_frequency_hz |
60
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| grid_frequency_range |
57-63 Hz
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_ac_apparent_power_kva |
105.3
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_ac_current_a |
126.7
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_dc_current_a |
136
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_efficiency_percent |
98.9
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_ocpd_rating_a |
200
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_pv_voltage_v |
1500
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_short_circuit_current_a |
220
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| mppt_voltage_max_v |
1300
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| mppt_voltage_min_v |
760
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| night_consumption_w |
2
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| number_of_mppt |
1
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| phase_count |
3
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| power_factor_range |
> 0.99 (+/-0.8 adjustable)
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| rated_ac_power_kw |
100
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| startup_voltage_v |
900
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| thd_percent |
3
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| topology |
Transformerless
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
Environment
| enclosure_rating |
NEMA Type 4X
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| max_altitude_m |
2500
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| operating_temperature_max_c |
60
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| operating_temperature_min_c |
-30
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
Protection
| ac_surge_protection |
Type II MOV (with indicator/remote signaling)
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
| dc_surge_protection |
Type II MOV (with indicator/remote signaling)
CPS SCH100KTL-DO/US-480 datasheet (8-21-2026)
|
Документи
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | North-American (CPS America) edition, 60 Hz, UL/IEEE grid codes. ANMA stores this brand as 'CHINT', which is carried here so the new rows sit with the six CPS products already in the catalog. |