⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Inverters

Growatt WIT 10K-HU

Побудувати систему з цим продуктом

Verified distributor GLOBAL перевірено 25 вересня 2026 р.

Identity

category inverters
manufacturer Growatt
model WIT 10K-HU
region GLOBAL

Electrical

ac_grid_connection_type 3P3W+PE / 3P4W+PE
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
afci Optional
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_apparent_power_va 20000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_frequency_hz 50/60 Hz
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_load_unbalance 100% three-phase unbalanced
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_nominal_voltage_v 220/380 V, 230/400 V
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_output True
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_rated_power_w 10000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
backup_transfer_time_ms 10
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
battery_nominal_voltage_v 51.2
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
battery_supported True
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
battery_type Lead-acid or Lithium-ion
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
battery_voltage_class LV
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
battery_voltage_max_v 60
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
battery_voltage_min_v 40
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
bms_communication RS485/CAN
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
display OLED/LED+APP
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
generator_input True
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
grid_frequency_hz 50/60 Hz (45~55 Hz / 55-65 Hz)
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
has_internal_pv_input True
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_ac_apparent_power_va 11000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_ac_output_current_a [16.7, 15.9]
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_ac_power_w 11000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_charge_current_a 220
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_discharge_current_a 220
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_input_current_per_mppt_a [50, 50]
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_parallel_units 6
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_pv_voltage_v 1000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_recommended_pv_power_w 16000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
max_short_circuit_current_per_mppt_a [50, 50]
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
mppt_voltage_max_v 850
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
mppt_voltage_min_v 150
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
nominal_dc_voltage_v 600
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
nominal_grid_voltage_v 220/380 V, 230/400 V (-15%~+10%)
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
number_of_mppt 2
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
parallel_supported True
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
phase_count 3
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
rated_ac_power_w 10000
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
smart_load True
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
startup_voltage_v 180
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
strings_per_mppt_distribution [2, 2]
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")

Environment

ip_rating IP66
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")

Interfaces & connectors

communications ['RS485', 'USB', 'WIFI', 'LAN']
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
documented_ports [{'port_role': 'PV_IN', 'port_label_from_manual': 'PV input (MC4)', 'port_type': 'PV DC connector', 'direction': 'input', 'electrical_domain': 'DC', 'quantity': None, 'document': 0, 'page': 'Input data (PV)', 'quote': 'rows "No. of MPP trackers" and "No. of PV strings per MPP tracker: 2"; the printed input count conflicts between document 0 and document 1, so quantity is left undocumented'}, {'port_role': 'BATTERY', 'port_label_from_manual': 'Battery', 'port_type': 'DC terminal', 'direction': 'bidirectional', 'electrical_domain': 'DC', 'quantity': 1, 'document': 0, 'page': 'Battery data (DC)', 'quote': 'rows "Battery voltage range: 40-60V", "Max charging and discharging current", "BMS communication: RS485/CAN"'}, {'port_role': 'GRID', 'port_label_from_manual': 'AC grid (3P3W+PE / 3P4W+PE)', 'port_type': 'screw terminal', 'direction': 'bidirectional', 'electrical_domain': 'AC', 'quantity': 1, 'document': 0, 'page': 'Input data (AC grid)', 'quote': 'row "AC grid connection type: 3P3W+PE/3P4W+PE"'}, {'port_role': 'BACKUP_LOAD', 'port_label_from_manual': 'Backup Power (AC)', 'port_type': 'screw terminal', 'direction': 'output', 'electrical_domain': 'AC', 'quantity': 1, 'document': 0, 'page': 'Backup power (AC)', 'quote': 'section "Backup Power (AC)", row "On/off grid transfer time: 10ms"'}, {'port_role': 'GENERATOR', 'port_label_from_manual': 'generator input', 'port_type': 'AC input', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': None, 'document': 0, 'page': 'headline feature line', 'quote': '"Integrated with generator input and smart load control"'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'communication interface', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'General', 'quote': 'row "Interfaces: RS485/USB: Yes"'}, {'port_role': 'CAN', 'port_label_from_manual': 'BMS communication CAN', 'port_type': 'communication interface', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Battery data (DC)', 'quote': 'row "BMS communication: RS485/CAN"'}, {'port_role': 'USB', 'port_label_from_manual': 'USB', 'port_type': 'USB', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'General', 'quote': 'row "Interfaces: RS485/USB: Yes"'}, {'port_role': 'ETHERNET', 'port_label_from_manual': 'LAN', 'port_type': 'Ethernet', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'General', 'quote': 'row "Interfaces: WIFI/LAN: Yes"'}]

Protection

pid_protection Optional
Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")

Документи

datasheet Growatt WIT 4-15K-HU Datasheet (marked "Preliminary Version")
datasheet Growatt | WIT 4-15K-HU | Solar Inverter Datasheet (ENF mirror of the manufacturer datasheet)
datasheet WIT 4-15K-HU Datasheet EN 202605
product_page Growatt WIT 4-15K-HU - product page (de.growatt.com)
product_page Growatt WIT 4-25K-HU - product page
product_page WIT 4-25K-XHU | Three Phase Hybrid | Growatt (family page listing the WIT XHU/HU documents)

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesThe datasheet prints one specification covering 220/380 V and 230/400 V at 50/60 Hz and cites EN 50549 and VDE 4105 alongside the IEC standards; no market-specific electrical edition was found, so GLOBAL.