SAJ H2-6K-T2
Official manufacturer AU перевірено 23 вересня 2026 р.
Identity
| category | inverters |
| manufacturer | SAJ |
| model | H2-6K-T2 |
| region | AU |
Electrical
| backup_output |
True
H2-(5-10K)-T2_Datasheet_en_AU
|
| battery_chemistry_supported |
LiFePO4
H2-(5-10K)-T2_Datasheet_en_AU
|
| battery_supported |
True
H2-(5-10K)-T2_Datasheet_en_AU
|
| battery_voltage_class |
HV
H2-(5-10K)-T2_Datasheet_en_AU
|
| battery_voltage_max_v |
600
H2-(5-10K)-T2_Datasheet_en_AU
|
| battery_voltage_min_v |
180
H2-(5-10K)-T2_Datasheet_en_AU
|
| cooling |
Natural convection
H2-(5-10K)-T2_Datasheet_en_AU
|
| dimensions_h_w_d_mm |
[433, 549, 207]
H2-(5-10K)-T2_Datasheet_en_AU
|
| display |
LED+APP
H2-(5-10K)-T2_Datasheet_en_AU
|
| euro_efficiency_percent |
97.6
H2-(5-10K)-T2_Datasheet_en_AU
|
| grid_frequency_hz |
[50, 60]
H2-(5-10K)-T2_Datasheet_en_AU
|
| has_internal_pv_input |
True
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_ac_output_current_a |
8.7
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_ac_power_w |
6600
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_charge_current_a |
30
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_discharge_current_a |
30
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_efficiency_percent |
98.0
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_input_current_per_mppt_a |
[15, 15]
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_operating_altitude_m |
3000
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_pv_power_w |
9000
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_pv_voltage_v |
1000
H2-(5-10K)-T2_Datasheet_en_AU
|
| max_short_circuit_current_per_mppt_a |
[19, 19]
H2-(5-10K)-T2_Datasheet_en_AU
|
| mppt_voltage_max_v |
900
H2-(5-10K)-T2_Datasheet_en_AU
|
| mppt_voltage_min_v |
180
H2-(5-10K)-T2_Datasheet_en_AU
|
| noise_dba |
<30
H2-(5-10K)-T2_Datasheet_en_AU
|
| nominal_ac_output_current_a |
8.7
H2-(5-10K)-T2_Datasheet_en_AU
|
| nominal_grid_voltage_v |
400
H2-(5-10K)-T2_Datasheet_en_AU
|
| nominal_pv_voltage_v |
600
H2-(5-10K)-T2_Datasheet_en_AU
|
| number_of_mppt |
2
H2-(5-10K)-T2_Datasheet_en_AU
|
| phase_count |
3
H2-(5-10K)-T2_Datasheet_en_AU
|
| power_factor_range |
0.8 leading ~ 0.8 lagging
H2-(5-10K)-T2_Datasheet_en_AU
|
| rated_ac_power_w |
6000
H2-(5-10K)-T2_Datasheet_en_AU
|
| rated_apparent_power_va |
6000
H2-(5-10K)-T2_Datasheet_en_AU
|
| startup_voltage_v |
180
H2-(5-10K)-T2_Datasheet_en_AU
|
| thdi_percent |
<3
H2-(5-10K)-T2_Datasheet_en_AU
|
| topology |
Non-isolated
H2-(5-10K)-T2_Datasheet_en_AU
|
Physical / mechanical
| weight_kg |
25
H2-(5-10K)-T2_Datasheet_en_AU
|
Environment
| operating_temperature_c |
-25 to +60 (45 to 60 with derating)
H2-(5-10K)-T2_Datasheet_en_AU
|
Interfaces & connectors
| communications |
['Wi-Fi', 'Ethernet', '4G (optional)']
H2-(5-10K)-T2_Datasheet_en_AU
|
| documented_ports | [{'port_role': 'PV_IN', 'port_label_from_manual': 'PV Connection', 'port_type': 'MC4/D4', 'direction': 'input', 'electrical_domain': 'DC', 'document': 0, 'page': 'H2 Three Phase Hybrid Inverter specification table, columns H2-5K-T2 | H2-6K-T2 | H2-8K-T2 | H2-10K-T2', 'quote': 'PV Connection :: MC4/D4'}, {'port_role': 'BATTERY', 'port_label_from_manual': 'Battery Connection', 'port_type': 'Quick connector', 'direction': 'bidirectional', 'electrical_domain': 'DC', 'document': 0, 'page': 'H2 Three Phase Hybrid Inverter specification table, columns H2-5K-T2 | H2-6K-T2 | H2-8K-T2 | H2-10K-T2', 'quote': 'Battery Connection :: Quick connector'}, {'port_role': 'AC_OUT', 'port_label_from_manual': 'AC Connection', 'port_type': 'Plug-in connector', 'direction': 'output', 'electrical_domain': 'AC', 'document': 0, 'page': 'H2 Three Phase Hybrid Inverter specification table, columns H2-5K-T2 | H2-6K-T2 | H2-8K-T2 | H2-10K-T2', 'quote': 'AC Connection :: Plug-in connector'}] |
Protection
| ac_surge_protection |
Integrated
H2-(5-10K)-T2_Datasheet_en_AU
|
| afci_protection |
Optional
H2-(5-10K)-T2_Datasheet_en_AU
|
| dc_surge_protection |
Integrated
H2-(5-10K)-T2_Datasheet_en_AU
|
| ingress_protection |
IP65
H2-(5-10K)-T2_Datasheet_en_AU
|
| protection_class |
I
H2-(5-10K)-T2_Datasheet_en_AU
|
Документи
datasheet
H2-(5-10K)-T2_Datasheet_en_AU
product_page
H2 Series - SAJ Hybrid Inverter
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | Read from SAJ's Australian edition datasheet (file name H2-(5-10K)-T2_Datasheet_en_AU). SAJ publishes the same designations in EU editions (H2-(5-10K)-T2-datasheet-EN-BEU), but the EU PDF's table could not be parsed reliably - its row labels and value rows came back offset from one another in three separate reads - so no EU values were carried into this record. |