Identity

category power_conversion_systems
manufacturer KACO new energy
model blueplanet gridsave 110 TL3-S
region GLOBAL

Electrical

ac_voltage_range 300 - 580 V
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
ac_voltage_v 480
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
bidirectional True
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
dc_voltage_max_v 1315
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
dc_voltage_min_v 801
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
grid_frequency_hz [50, 60]
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
max_ac_power_kva 110
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
max_dc_current_a 145
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
max_efficiency_charge_percent 98.6
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
max_efficiency_percent 98.8
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
max_parallel_units 2
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
number_of_dc_inputs 1
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
parallel_supported True
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
phase_count 3
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
rated_ac_current_a 132.3
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
rated_ac_power_kw 110
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
reactive_power_support True
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
thd_percent <3
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)

Physical / mechanical

weight_kg 80
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)

Environment

ip_rating IP66 / NEMA 4X
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
operating_temperature_max_c 60
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
operating_temperature_min_c -20
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)

Interfaces & connectors

communications ['Ethernet', 'USB']
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
documented_ports [{'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'Ethernet', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 1, 'page': 'Interfaces', 'quote': 'Ethernet, USB'}, {'port_role': 'USB', 'port_label_from_manual': 'USB', 'port_type': 'USB', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 1, 'page': 'Interfaces', 'quote': 'Ethernet, USB'}, {'port_role': 'BATTERY_DC', 'port_label_from_manual': 'DC inputs', 'port_type': 'DC terminal', 'direction': 'bidirectional', 'electrical_domain': 'DC', 'quantity': 1, 'document': 1, 'page': 'DC input', 'quote': 'Number of DC inputs 1'}]
protocols ['TCP/IP', 'Modbus TCP based on SunSpec']
blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)

Документи

datasheet blueplanet gridsave 92.0 - 137 TL3-S technical data (KACO doc EN 500xxxx-01-220307)
product_page Battery inverters for C&I energy storage systems - blueplanet gridsave

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesOne datasheet covers all three line voltages (400 V / 480 V / 600 V) at 50 Hz or 60 Hz, so the specification is not market-split; the individual model is selected by grid line voltage.