Identity

category pv_optimizers
manufacturer SolarEdge
model P601
region EU

Electrical

dimensions_w_l_h_mm 129 x 153 x 52
SolarEdge Power Optimizer - Voor Europa - P370 / P401 / P404 / P485 / P500 / P505 / P601
input_connector MC4 (single/dual)
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
max_dc_voltage_label Absolute Maximum Input Voltage (Voc)
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
max_efficiency_pct 99.5
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
max_output_current_a 15
SolarEdge Power Optimizer - Voor Europa - P370 / P401 / P404 / P485 / P500 / P505 / P601
maximum_system_voltage_v 1000
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
number_of_mppt 1
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
number_of_mppt_note One per-module maximum power point tracker inside the optimizer. This is NOT an inverter MPPT channel count: the optimizer's MPPT operating range row is its own per-module tracking window.
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
number_of_pv_inputs 1
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
optimizer_topology_note SolarEdge power optimizers are per-module DC-DC converters, not inverter MPPT trackers. Each optimizer tracks the maximum power point of its own module and the string then runs at a fixed DC bus voltage set by the SolarEdge inverter. 'max_output_voltage_v' below is the per-optimizer output limit; the separate string-level rule is 'maximum_system_voltage_v'. These are different axes and are not interchangeable, and this architecture must not be assumed for other brands' optimizers.
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
output_connector MC4
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
overvoltage_category II
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
rated_input_dc_power_w 600
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
relative_humidity_pct 0-100
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
standby_safety_output_voltage_v 1 +/- 0.1
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
string_design_rules_by_inverter_type {'Home Wave (single-phase)': 'Minimum string length 8-9 power optimizers; maximum 25; maximum power per string 5700 W', 'Home short string (three-phase)': 'Minimum string length 8-9; maximum 20; maximum power per string 5625 W', '230/400 V grid (three-phase)': 'Minimum string length 14-16; maximum 50; maximum power per string 11,250 W', '277/480 V grid (three-phase)': 'Minimum string length 14-18; maximum 50; maximum power per string 12,750 W'}
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
string_mixing_restriction It is not allowed to mix P404/P485/P505/P601 with P370/P401/P500 in one string.
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
strings_per_mppt_distribution [1]
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)
weighted_efficiency_pct 98.8
SolarEdge Power Optimizer - Voor Europa - P370 / P401 / P404 / P485 / P500 / P505 / P601

Environment

operating_temperature_c -40 to +85
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)

Interfaces & connectors

documented_ports [{'port_role': 'DC_IN', 'port_label_from_manual': 'Input Connector', 'port_type': 'MC4 (single/dual)', 'direction': 'input', 'electrical_domain': 'DC', 'document': 0, 'page': 'INSTALLATION SPECIFICATIONS', 'quote': 'Input Connector: MC4 (single/dual)', 'quantity': 1}, {'port_role': 'DC_OUT', 'port_label_from_manual': 'Output Connector', 'port_type': 'MC4', 'direction': 'output', 'electrical_domain': 'DC', 'document': 0, 'page': 'INSTALLATION SPECIFICATIONS', 'quote': 'Output Connector: MC4; Maximum Output Current: 15 Adc', 'quantity': 1, 'max_current_a': 15}]

Protection

ingress_protection IP68
SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)

Документи

datasheet SolarEdge Optimizador de potencia P370 / P401 / P404 / P485 / P500 / P505 / P601
datasheet SolarEdge Power Optimizer - Voor Europa - P370 / P401 / P404 / P485 / P500 / P505 / P601
datasheet SolarEdge Power Optimizer P370 / P401 / P404 / P485 / P500 / P505 / P601 (module add-on)

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesSpecifications taken from the SolarEdge datasheet edition marked for Europe. SolarEdge publishes separate NA / AUS / ROW editions of the same models whose string-design rules differ; those were not merged in.
withheld:gateway_required"Not applicable - DC-DC module add-on used with SolarEdge inverters"