⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Accuenergy
model Acuvim IIR
region GLOBAL
variant —

Electrical

accuracy_class Class 0.1S active energy (IEC 62053-22) / Class 0.1 (ANSI C12.20); Class 0.5S reactive (IEC 62053-24)
accuracy_class_active_energy Class 0.1s (IEC 62053-22); Class 0.1 (ANSI C12.20)
Acuvim II Series Advanced Power and Energy Meter datasheet
control_power_supply_range 100-415 Vac 50/60 Hz; 100-300 Vdc (20-60 Vdc with P2V3 option)
ct_input_options 5A, 1A, 333mV, Rogowski Coil, 80mA/100mA/200mA
Acuvim II Series Advanced Power and Energy Meter datasheet
ct_secondary_current_a [5, 1]
Acuvim II Series Advanced Power and Energy Meter datasheet
current_accuracy_percent 0.1
Acuvim II Series Advanced Power and Energy Meter datasheet
current_range_a Nominal 5 A or 1 A (also 333 mV, Rogowski, 80/100/200 mA options); metering range 0-10 A on the 5 A input
direct_current_max_a Not applicable - the meter is ordered with a current-input option and connected through external CTs
Acuvim II Series Advanced Power and Energy Meter datasheet
display_type LCD
expansion_modules Up to three simultaneous modules: AXM-RS485, AXM-NET2, AXM-WEB2, AXM-WEB2-D, AXM-WEB2-FOLC, AXM-IO1, AXM-IO2, AXM-IO3, AXM-IO4
Acuvim II Series Advanced Power and Energy Meter datasheet
frequency_hz 45Hz~65Hz суперечливе
Acuvim II Series Advanced Power and Energy Meter datasheet
harmonics_measured up to 63rd harmonic
humidity_range_pct 5 to 95, non-condensing
input_impedance 2 MOhm per phase
installation_category III (Distribution)
local_modbus_available True
Acuvim II Series Advanced Power and Energy Meter datasheet
meter_type Panel- or DIN-rail-mounted advanced multifunction power and energy meter with data logging, current-transformer connected
Acuvim II Series Advanced Multifunction Power Meters
onboard_memory 8 MB (Acuvim IIR)
phase_count 3
Acuvim II Series Advanced Power and Energy Meter datasheet
physical_interfaces ['RS485', 'Optional Ethernet via AXM-NET2 / AXM-WEB2 / AXM-WEB2-D / AXM-WEB2-FOLC module', 'Optional Wi-Fi via AXM-WEB2']
Acuvim II Series Advanced Power and Energy Meter datasheet
power_consumption_w 5
pulse_output Digital output (Photo-MOS) 0-250 Vac/dc, 100 mA max load, 25 Hz 50% duty, 2500 Vac isolation
rated_voltage_v Nominal Full Scale 480Vac L-N, 828Vac L-L
Acuvim II Series Advanced Power and Energy Meter datasheet
supply_voltage P1V3: 100~415Vac, 50/60Hz, 100~300Vdc; P2V3: 20~60Vdc
Acuvim II Series Advanced Power and Energy Meter datasheet
supported_ct_ratios Set by the chosen current transformer; the datasheet prints input options, not a ratio table
Acuvim II Series Advanced Power and Energy Meter datasheet
voltage_range_v Nominal full scale 480 Vac L-N / 828 Vac L-L; pickup 10 Vac
voltage_withstand 1500Vac Continuous; 2500Vac, 50/60Hz for 1 Minute
Acuvim II Series Advanced Power and Energy Meter datasheet

Physical / mechanical

dimensions_mm 96 x 96 x 64.3 (panel mount) суперечливе
Acuvim II Series Advanced Power and Energy Meter datasheet

Installation

mounting Panel mount (92 x 92 mm opening) or DIN rail
mounting_options D (LCD display, panel) or M (DIN-rail without display)
Acuvim II Series Advanced Power and Energy Meter datasheet

Environment

operating_temperature_range_c -25 to 70
storage_temperature_range_c -40 to 85

Interfaces & connectors

cloud_required False
Acuvim II Series Advanced Power and Energy Meter datasheet
communication_protocol Modbus-RTU or BACnet MS/TP over RS-485 (2400-115200 bps); optional second RS-485 (4800-38400 bps); optional Ethernet 10M/100M BaseT; IEC 61850 2nd Ed., BTL listed B-SA
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical Specifications', 'quote': 'Communication Ports | RS485 (Modbus-RTU/BACnet MS/TP); Optional Ethernet'}, {'port_role': 'ETHERNET', 'port_label_from_manual': 'Optional Ethernet (AXM-NET2 / AXM-WEB2 module)', 'port_type': 'Ethernet', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Technical Specifications', 'quote': 'Communication Ports | RS485 (Modbus-RTU/BACnet MS/TP); Optional Ethernet'}, {'port_role': 'CT', 'port_label_from_manual': 'Current Input', 'port_type': '5A, 1A, 333mV, Rogowski Coil or 80/100/200mA per order option', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': 3, 'document': 0, 'page': 'Technical Specifications', 'quote': 'Current Input Options | 5A, 1A, 333mV, Rogowski Coil, 80mA/100mA/200mA'}]
protocols ['Modbus-RTU', 'BACnet MS/TP', 'DNP 3.0 V2 ready', 'Modbus-TCP (module)', 'BACnet-IP (module)', 'IEC 61850 2nd Edition (module)', 'EtherNet/IP (module)', 'MQTT (module)']
Acuvim II Series Advanced Power and Energy Meter datasheet

Certifications

certifications IEC 62053-22; ANSI C12.20; IEC 61557-12; IEC 60068-2; CE; RoHS; IEC 61010-1; UL 61010-1; CISPR 22; IEC 61000-3-2; IEC 61000-6-2/-6-4; EN 55011; DIN 43700; ANSI C39.1

Документи

communication_manual Acuvim II Power Meter DNP3 User Manual
datasheet Acuvim II Series Advanced Power and Energy Meter datasheet
product_page Acuvim II Series Advanced Multifunction Power Meters
user_manual Acuvim II Power Meter User Manual 1040E1303

Зафіксовані конфлікти

physical.dimensions_mm Review required
96 x 96 x 64.3 (panel mount) — stored value
96 x 96 x 64.3 (panel mount; 92 x 92 opening) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16
electrical.frequency_hz Review required
45Hz~65Hz — stored value
45 to 65 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesOne worldwide specification: the datasheet prints IEC 62053-22 Class 0.1s and ANSI C12.20 Class 0.1 for the same device, with a 45-65 Hz frequency range.