Carlo Gavazzi EM330
Official manufacturer GLOBAL перевірено 25 вересня 2026 р.
Identity
| category | smart_meters |
| manufacturer | Carlo Gavazzi |
| model | EM330 |
| region | GLOBAL |
| variant | — |
Electrical
| accuracy_class |
Class 1 (kWh) according to EN62053-21; Class B (kWh) according to EN50470-3
суперечливе
EM330 Three-phase energy meter - datasheet
|
| auxiliary_supply |
H order code: 100-240 V ac/dc auxiliary supply
EM330 Three-phase energy meter - datasheet
|
| ct_secondary_current_a |
5
EM330 Three-phase energy meter - datasheet
|
| ct_secondary_current_max_a |
6
EM330 Three-phase energy meter - datasheet
|
| current_range_a | Rated 5 A, Imax 6 A (5(6) A); Imin 0.25 A; start-up current 10 mA |
| display |
Backlit LCD, 3 rows by 8-digit each; energy 8-digit, variables 4-digit
EM330 Three-phase energy meter - datasheet
|
| display_type | Backlit LCD, 3 rows of 8 digits, 7 mm high, with integrated touch keypad (DOWN / ENTER / UP) |
| ethernet_port_count |
0
EM330 Three-phase energy meter - datasheet
|
| frequency_hz | 45 to 65 |
| humidity_pct | 0 to 90 non-condensing at 40 degC operating; <90 non-condensing at 40 degC storage |
| measured_phases | 3-phase 3- or 4-wire; 2-phase 3-wire; 1-phase 2-wire |
| measurement_accuracy |
current from 0.2In to Imax: ±(0.5%RDG); voltage ±(0.5% RDG) phase-neutral, ±(1% RDG) phase-phase
суперечливе
EM330 Three-phase energy meter - datasheet
|
| measurement_directions |
imported and exported energy, configurable to imported only
EM330 Three-phase energy meter - datasheet
|
| measurement_system |
3-phase (3 or 4-wire), 2-phase and 1-phase configurations supported
EM330 Three-phase energy meter - datasheet
|
| meter_type |
CT-operated three-phase energy meter with 5(6) A secondary current inputs
EM330 Three-phase energy meter - datasheet
|
| phase_count |
3
EM330 Three-phase energy meter - datasheet
|
| physical_interfaces |
['RS485 (option S1)', 'M-Bus (option M1)', 'pulse output (option O1)']
EM330 Three-phase energy meter - datasheet
|
| power_consumption | <= 1 W, <= 8 VA (auxiliary supply 100-240 V ac/dc +/-10%) |
| pulse_output | Open-collector PNP static output; pulse weight 1, 10, 100 or 1000 pulses/kWh set automatically from the CT x VT ratio; pulse rate 1-1500 (Ton 30 ms) or 1-500 (Ton 100 ms) |
| rated_voltage_v |
400-480 V L-L ac / 230-277 V L-N ac (AV5 range code)
EM330 Three-phase energy meter - datasheet
|
| rs485_port_count |
1 on the S1 order-code option
EM330 Three-phase energy meter - datasheet
|
| supported_ct_ratios |
CT x VT ratio max. 1000
EM330 Three-phase energy meter - datasheet
|
| voltage_range_v | 400 to 480 V L-L ac (230 to 277 V L-N) |
Physical / mechanical
| dimensions_mm | 54 x 90 x 63 |
| weight_kg | 0.240 (packing included) |
Installation
| mounting | DIN-rail, 3-DIN module (54 mm) |
Environment
| operating_temperature_c |
-25 to +65 (X option); -25 to +55 (PF option)
EM330 Three-phase energy meter - datasheet
|
| operating_temperature_range_c | -25 to +55 (PF/MID option); -25 to +65 (X option) |
| storage_temperature_range_c | -30 to +80 |
Interfaces & connectors
| communication_protocol | RS485 Modbus RTU (slave) at 9.6/19.2/38.4/57.6/115.2 kbaud; M-Bus per EN 13757-1 at 0.3/2.4/9.6 kbaud; data refresh time 1 s |
| documented_ports | [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus (order-code option S1)', 'port_type': 'screw terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Communication interfaces', 'quote': 'Communication Interfaces | RS485 Modbus (optional S1), M-Bus (optional M1), pulse output (optional O1)'}, {'port_role': 'CT', 'port_label_from_manual': 'Current inputs (CT connection)', 'port_type': 'screw terminals', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 3, 'document': 0, 'page': 'Inputs', 'quote': 'CT Connection | 5(6) A secondary current'}] |
| protocols |
['Modbus RTU (order-code option S1)', 'M-Bus (order-code option M1)']
EM330 Three-phase energy meter - datasheet
|
| wifi |
False
EM330 Three-phase energy meter - datasheet
|
Protection
| protection_degree_ip | IP51 front; IP20 screw terminals |
Certifications
| certifications | EN 62052-11 / EN 62053-21 (X option); EN 50470-1 / EN 50470-3 (PF option); IEC/EN 61557-12; CE; MID (PF option only); cULus (UL 61010-1) |
Документи
Зафіксовані конфлікти
electrical.measurement_accuracy Review required
current from 0.2In to Imax: ±(0.5%RDG); voltage ±(0.5% RDG) phase-neutral, ±(1% RDG) phase-phase — stored value
Voltage +/-(0.5% RDG) phase-neutral, +/-(1% RDG) phase-phase; current +/-(0.5% RDG) from 0.2 In to Imax; frequency +/-(0.2% RDG) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch11
electrical.accuracy_class Review required
Class 1 (kWh) according to EN62053-21; Class B (kWh) according to EN50470-3 — stored value
Active energy: class 1 per EN 62053-21 and class B per EN 50470-3; reactive energy: class 2 per EN 62053-23 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch11
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | complete |
| region_notes | One English datasheet; the AV5 range code covers 400-480 V L-L / 230-277 V L-N. MID certification is the PF order-code option. |
| withheld:direct_current_max_a | "not applicable - CT-operated meter" |
| withheld:internet_required_for_operation | "not applicable - standalone meter" |
| withheld:local_modbus_available | "yes on the S1 order-code option" |