⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Carlo Gavazzi
model EM511
region GLOBAL
variant —

Electrical

accuracy_class Class 1 (EN IEC 62053-21); Class B (EN 50470-3) for the MID versions суперечливе
EM511 Energy analyzer for 1-phase systems - datasheet
current_range_a Base current Ib 5 A; minimum current Imin 0.25 A; maximum current Imax 45 A; start-up current Ist 0.02 A
direct_current_max_a 45
EM511 Energy analyzer for 1-phase systems - datasheet
display_type Backlit LCD, segment type
ethernet_port_count 0
EM511 Energy analyzer for 1-phase systems - datasheet
frequency_hz 50 (MID models); 50/60 (non-MID models)
measured_phases Single-phase
measurement_directions imported and exported energy (kWh+ and kWh-); the PFB order-code option is MID-certified bidirectional, while PFA/SFA use 'easy connection' with power always positive
EM511 Energy analyzer for 1-phase systems - datasheet
meter_type direct-connected single-phase DIN-rail energy analyzer, 45 A max
EM511 Energy analyzer for 1-phase systems - datasheet
nominal_current_a 5
EM511 Energy analyzer for 1-phase systems - datasheet
phase_count 1
EM511 Energy analyzer for 1-phase systems - datasheet
physical_interfaces ['RS485 (option S1)', 'M-Bus 2-wire (option M1)', 'digital/pulse output (option O1)']
EM511 Energy analyzer for 1-phase systems - datasheet
power_consumption <0.6 W / 1.8 VA суперечливе
EM511 Energy analyzer for 1-phase systems - datasheet
pulse_output 0.001 kWh per pulse, red LED, proportional to consumption суперечливе
EM511 Energy analyzer for 1-phase systems - datasheet
rated_voltage_v 230 V L-N (MID versions); 120-240 V L-N (non-MID versions)
EM511 Energy analyzer for 1-phase systems - datasheet
refresh_time ≤100 ms
EM511 Energy analyzer for 1-phase systems - datasheet
rs485_port_count 1 on the S1 order-code option (0 on O1/M1 versions)
EM511 Energy analyzer for 1-phase systems - datasheet
starting_current_a 0.02
EM511 Energy analyzer for 1-phase systems - datasheet
voltage_range_v 230 V L-N (MID models); 120 to 240 V L-N (non-MID models); tolerance 0.8 to 1.15 Un

Physical / mechanical

dimensions_mm 90 x 58 x 44
EM511 Energy analyzer for 1-phase systems - datasheet
weight_kg 0.155 (packaging included)

Installation

mounting DIN rail

Environment

operating_temperature_c up to +55 standard; -25 to +70 on the extended-temperature option
EM511 Energy analyzer for 1-phase systems - datasheet
operating_temperature_range_c -25 to +55 (standard models); -25 to +70 (S1PFx70 models)
storage_temperature_range_c -25 to +70

Interfaces & connectors

communication_protocol RS485 Modbus RTU at 9.6/19.2/38.4/115.2 kbps; M-Bus at 0.3/2.4/9.6 kbps; refresh time <= 100 ms
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 (order-code option S1)', 'port_type': 'screw terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Communication', 'quote': 'Communication - Modbus RTU | RS485, multidrop bidirectional, ≤100 ms refresh'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'S0 pulse output (order-code option O1)', 'port_type': 'screw terminals', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Outputs', 'quote': 'Communication - S0 Pulse | Red LED; 0.001 kWh per pulse (proportional to consumption)'}]
protocols ['Modbus RTU (order-code option S1)', 'M-Bus EN IEC 13757-3:2013 (order-code option M1)']
EM511 Energy analyzer for 1-phase systems - datasheet
wifi False
EM511 Energy analyzer for 1-phase systems - datasheet

Protection

protection_degree_ip IP40 front; IP20 terminals

Certifications

certifications EN IEC 62053-21, EN 50470-3, EN IEC 61557-12, EN IEC 62052-11, EN IEC 61010-1, EN IEC 62053-23, EN IEC 62053-31; directives 2014/32/EU (MID), 2014/35/EU (LVD), 2014/30/EU (EMC), 2011/65/EU; cULus approved (UL 61010); CTEP approved (US market)

Документи

datasheet EM511 Energy analyzer for 1-phase systems - datasheet
manual EM511 Energy analyzer for single-phase systems - user manual

Зафіксовані конфлікти

electrical.power_consumption Review required
<0.6 W / 1.8 VA — stored value
< 0.6 W / 1.8 VA — incoming package
Detected during import deep-enrich-pass2-2026-09-batch11
electrical.pulse_output Review required
0.001 kWh per pulse, red LED, proportional to consumption — stored value
Front red LED / S0 pulse output, Opto-MOSFET, pulse weight 0.001 kWh per pulse — incoming package
Detected during import deep-enrich-pass2-2026-09-batch11
electrical.accuracy_class Review required
Class 1 (EN IEC 62053-21); Class B (EN 50470-3) for the MID versions — stored value
Active energy: class 1 (EN IEC 62053-21) and class B (EN 50470-3, MID); reactive energy: class 2 (EN IEC 62053-23) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch11

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesscomplete
region_notesCarlo Gavazzi publishes one English datasheet for the EM511 family; the order code selects the MID certification (SFA/PFA/PFB for EU legal metrology) and the communication option. ANMA's existing Carlo Gavazzi records use the family name, and the same convention is used here.
withheld:ct_secondary_current_a"not applicable - direct-connected meter"
withheld:internet_required_for_operation"not applicable - standalone meter"
withheld:local_modbus_available"yes on the S1 (RS485 Modbus RTU) order-code option"
withheld:max_connected_devices"not applicable - end device"
withheld:supported_ct_ratios"not applicable - direct-connected meter"