⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Carlo Gavazzi
model ET340
oem_ordering_code ET340-DIN.AV23.X.S1.X
product_family Carlo Gavazzi ET340 (Victron-distributed)
product_status active
region global
sku REL300300000

Electrical

accuracy_class_active_energy Class 1 (kWh) according to EN62053-21
accuracy_class_reactive_energy Class 2 according to EN62053-23
accuracy_current_voltage ±0.5% RDG (current/voltage)
base_current 5 A
ct_ratio_options Not applicable - direct connection
current_connection Direct / Shunt (no CT)
display No display - only an LED which blinks in case of active communication
energy_totalisation In the ET340, the energy imported and exported is counted at each individual phase and then the Total is provided from the sum of those values.
frequency 45 to 65Hz
insulation —
max_continuous_current 65A, @ 50Hz
max_current_victron_spec max. 65A per phase
measuring_category Overvoltage category Cat. III
minimum_current —
nominal_voltage 208 to 400 VLL AC
phases 3-phase, 3- or 4-wire; 2-phase 3-wire
power_consumption <= 1W, <= 10VA
rated_current 5(65)A (direct connection)
refresh_rate 2000 ms (Victron selection guide)
self_power_supply_range 208 to 400VAC VLL
temperature_drift —
voltage_range 113 to 265VLN (196 to 460VLL)

Physical / mechanical

dimensions_mm 54 x 90 x 63 mm
din_modules 3-DIN module
material Noryl, self-extinguishing: UL 94 V-0
screw_torque_measuring —
screw_torque_other —
terminals_measuring_inputs max. 16 mm2, min. 2.5 mm2
terminals_other —
weight Approx. 240 g (packing included)

Installation

max_cable_length The RS485 to USB interface cable between the GX device and the Energy Meter can be extended up to 100 meters; make sure that the extensions of the Data+ (orange) and Data- (yellow) wires form a twisted pair.
mounting DIN rail
multiple_meters To connect multiple Energy Meters, wire each meter to a separate RS485 to USB interface, which are then each plugged into a separate USB socket on the GX device.
rs485_wiring UNKNOWN - the ET340 installation page was not fetched; the ET112/EM540 wiring colour scheme should not be assumed identical

Environment

operating_temperature -20 to +65 °C
relative_humidity R.H. from 0 to 90% noncondensing @ 40°C
storage_temperature -30°C to +80°C

Interfaces & connectors

bluetooth No
ethernet No
modbus_rtu Yes - RS485 Modbus port; baud rate 9.6, 19.2, 38.4, 57.6, 115.2 kbaud; address 1 to 247 (default: 01); maximum 247 devices on the same bus
modbus_tcp No
rs485 Yes - RS485 Modbus port
ve_direct No
zigbee Optional via Victron Zigbee to USB converter (ASS300420200) and Zigbee to RS485 converter (ASS300420100)

Protection

ip_rating Protection degree (front): IP20

Certifications

standards ['CE', 'EN62052-11 (Safety)', 'EN62053-21 (Metrology)', 'EMC according to EN62052-11']

Warranty & service

summary —

Документи

manual-html Victron Energy Meter ET340 manual - FAQ
manual-html {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Victron Energy Meter ET340 manual - Installation and Configuration — знайдено, не отримано
manual-html Victron Energy Meter ET340 manual - Introduction
manual-pdf {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Victron Energy Meters manual (shared, 113406) — знайдено, не отримано
oem-datasheet Carlo Gavazzi ET340 Datasheet (ET340 DS ENG)
pricelist Pricelist Victron 2026 Q1 USD C
product-page Energy Meters product page
selection-guide Victron Energy Meter Selection Guide

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

Isolated USB-RS485 interfaceYes. The interfaces we sell are non isolated; suitable for most use cases.
Ordering code ET340-DIN AV2 3 X S1 XRange AV2: 208-400V; System 3-phase; Power supply X: self; Output S1: RS485; Option X: none
Other brand metersCan I use other meters, for example from other brands? No.
Single-phase PV on a 3-phase meterMeasuring energy from single-phase PV Inverter on the second phase of a 3-phase meter actually works.
Victron EM24 RS485 FAQThe ET meters have no display
Victron Energy Meter Selection GuideET340 (3-phase, Direct, 65A, RS485)
builder_completenesspartial
documented_relationship:gateway_device{"to_manufacturer": "Victron Energy", "to_model": "GX device (Cerbo GX / Venus OS family)", "relationship_type": "gateway_device", "source": "Victron Energy Meter ET340 manual, Introduction", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_ET340/en/introduction.html", "confidence": "officially-verified", "notes": "\"The Victron ET340 is a standard device to measure the power and energy of a 3-phase application.\" Data displays on a GX device and the VRM portal."}
documented_relationship:inverter_meter{"to_manufacturer": "Victron Energy", "to_model": "ESS (MultiPlus / Quattro inverter/charger system)", "relationship_type": "inverter_meter", "source": "Victron Energy Meter ET340 manual, Introduction", "source_url": "https://www.victronenergy.com/media/pg/Energy_Meter_ET340/en/introduction.html", "confidence": "officially-verified", "notes": "Role: \"a Grid meter and used as control input for an ESS System\""}