⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 23 вересня 2026 р.

Identity

category smart_meters
manufacturer Crompton Instruments
model Integra 1222
region GLOBAL
variant —

Electrical

accuracy_class Active energy +/- 0.5 % of reading to IEC 62053-21; reactive energy +/- 0.5 % of reading to IEC 62053-24 суперечливе
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
burden_va Voltage < 0.2 VA per phase; current < 0.1 VA
current_accuracy +/- 0.5 % of range maximum
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
current_range_a Nominal input current 1 A AC or 5 A AC
display Backlit LCD HD Display
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
display_type Backlit LCD HD display with programmable backlight
frequency_hz 44 - 66 Hz суперечливе
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
measured_phases Single phase 2-wire, three phase 3-wire (auxiliary powered only), three phase 4-wire
nominal_input_current_a 1 A AC or 5 A AC
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
nominal_voltage_v Self-powered 100-277 V L-N / 173-480 V L-L; auxiliary-powered 57.7-276 V L-N / 100-480 V L-L
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
panel_cutout_mm 92 x 92
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
pulse_output Two pulsed outputs (self powered) / one pulsed output (auxiliary powered); 2400 imp/kWh, non-configurable
pulse_output_count 2
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
rs485_baud_rate 2400, 4800, 9600, 19200, 38400
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
rs485_wiring 2-wire half duplex
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
voltage_accuracy +/- 0.5 % of range maximum
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
voltage_range_v Self powered 100-277 V AC L-N (173-480 V L-L); auxiliary powered 57.7-276 V L-N (100-480 V L-L) AC/DC

Physical / mechanical

depth_mm 62.0
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
dimensions_mm 96 x 96 x 62
height_mm 96.0
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
weight_kg 0.34
width_mm 96.0
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)

Installation

mounting 96 mm square panel mount суперечливе
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)

Environment

ip_rating Front IP54, Rear IP30, IP64 with additional kit
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
operating_temperature_max_c 70
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
operating_temperature_min_c -25
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
operating_temperature_range_c -25 to +70
storage_temperature_range_c -40 to +80

Interfaces & connectors

communication_protocol Modbus RTU over RS485, 2-wire half duplex
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS485 2-wire half duplex', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Communications', 'quote': 'Modbus RTU (RS485)'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Pulsed output', 'port_type': 'Opto-coupled potential-free SPST-NO contact', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': 'Pulse outputs', 'quote': 'Opto-coupled, potential-free SPST-NO contact'}]
protocols ['Modbus RTU']
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
rs485 True
Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)

Protection

protection_degree_ip Front IP54, rear IP30; IP64 front with additional kit

Certifications

certifications BS EN 61010-1:2010; BS EN 61326-1:2013; IEC 62053-21; IEC 62053-24

Документи

compatibility_list TE Energy Integra Catalogue Update 2026
datasheet Integra 1222 Digital Metering System data sheet (EPP-2881-DDS-0919)
product_page Integra Digital Metering Systems

Зафіксовані конфлікти

installation.mounting Review required
96 mm square panel mount — stored value
DIN 96 panel mount — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16
electrical.frequency_hz Review required
44 - 66 Hz — stored value
44 to 66 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16
electrical.accuracy_class Review required
Active energy +/- 0.5 % of reading to IEC 62053-21; reactive energy +/- 0.5 % of reading to IEC 62053-24 — stored value
Class 0.5 (IEC 62053-21) active; Class 0.5 (IEC 62053-24) reactive — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesIEC-referenced instrument (IEC 62053-21 / IEC 62053-24) with a 100-277 V L-N input window covering 50 Hz and 60 Hz markets; Crompton Instruments is the TE Connectivity Energy brand. Crompton's own catalogue marks the Integra 1422 as 'Asia / Pac Only' - the 1221 and 1222 carry no such restriction.