⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer EU перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Frer
model C18QSL045MD3AI
region EU
variant —

Electrical

accuracy_class Class B (EN 50470-3) active energy суперечливе
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
accuracy_class_reactive 2 (kVArh) EN 62053-23
C18 data sheet
baud_rates_kbps 2,4/4,8/9,6/19,2/38,4
C18 data sheet
bidirectional True
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
connection_type direct
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
din_modules 1
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
direct_current_rating_a 45
C18 data sheet
frequency_hz 50/60
C18 data sheet
installation Indoor use
C18 data sheet
max_current_a 45
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
minimum_current_a 0.25
C18 data sheet
modbus_addresses 1...247
C18 data sheet
nominal_voltage_v 230
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
operating_humidity_percent <95
C18 data sheet
parity NONE/EVEN/ODD
C18 data sheet
phase_count 1
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
pulse_output Voltage: 5...27Vdc - 27mA max; S01: programmable; S02: fixed to 1000 imp/kWh
C18 data sheet
pulse_output_count 2
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
reference_current_a 5
C18 data sheet
rs485_unit_load 1/2
C18 data sheet
s0_pulse_outputs 2
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
starting_current_a 0.02
C18 data sheet
stop_bits 1, 2
C18 data sheet
system_type Single-phase network
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
voltage_range 230 V ±20%
C18 data sheet

Installation

mounting 1-DIN-module format
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU

Environment

ip_rating IP51 (front), IP20 (terminals)
C18 data sheet
operating_temperature_max_c 70
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
operating_temperature_min_c -40
C18 data sheet
storage_temperature_max_c 75
C18 data sheet
storage_temperature_min_c -40
C18 data sheet

Interfaces & connectors

communications ['RS485']
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus RTU', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': "Product page 'C18QSL045MD3AI'", 'quote': 'Single-phase MID meter, 230V-45A direct, Modbus RTU'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'S0 pulse outputs', 'port_type': 'S0 pulse output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': "Product page 'C18QSL045MD3AI'", 'quote': 'two S0 pulse outputs'}] суперечливе
modbus_rtu True
C18 data sheet
protocols ['Modbus RTU']
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
rs485 True
C18 data sheet

Certifications

mid_certified True
C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU

Документи

communication_manual C18 communication protocols
datasheet C18 data sheet
product_page C18QSL045MD3AI - Single-phase MID meter, 230V-45A direct, Modbus RTU
user_manual C18 user manual

Зафіксовані конфлікти

interfaces.documented_ports Review required
[{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus RTU', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': "Product page 'C18QSL045MD3AI'", 'quote': 'Single-phase MID meter, 230V-45A direct, Modbus RTU'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'S0 pulse outputs', 'port_type': 'S0 pulse output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': "Product page 'C18QSL045MD3AI'", 'quote': 'two S0 pulse outputs'}] — stored value
[{'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS-485 Modbus RTU', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication options, C18-45M', 'quote': 'C18-45M (RS485): Modbus RTU'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'S01', 'port_type': 'S0 optoisolated passive pulse output', 'direction': 'OUTPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Pulse Outputs (S0)', 'quote': 'S01: programmable'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'S02', 'port_type': 'S0 optoisolated passive pulse output', 'direction': 'OUTPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Pulse Outputs (S0)', 'quote': 'S02: fixed to 1000 imp/kWh'}] — incoming package
Detected during import deep-enrich-2026-09-batch25
electrical.accuracy_class Review required
Class B (EN 50470-3) active energy — stored value
B (kWh) EN 50470-3 — Active Energy: B (kWh) EN 50470-3
Detected during import deep-enrich-2026-09-batch25

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesMID / EN 50470-3 European metering product; Italian manufacturer, EU market.