Fronius Fronius Smart Meter IP 5kA-3
Official manufacturer EU перевірено 23 вересня 2026 р.
Identity
| category | smart_meters |
| manufacturer | Fronius |
| model | Fronius Smart Meter IP 5kA-3 |
| region | EU |
Electrical
| accuracy_class |
Class 1 (EN 62053-21) / Class B (EN 50470-3) active energy; Class 2 (EN 62053-23) reactive energy
Fronius Smart Meter IP 5kA-3 - technical data
|
| ct_secondary_output |
333 mV
Fronius Smart Meter IP 5kA-3 - technical data
|
| ethernet_port_count |
1
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
| grid_frequency_hz |
[50, 60]
Fronius Smart Meter IP 5kA-3 - technical data
|
| local_modbus_available |
True
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
| measurement_directions |
bidirectional - meter position configurable as feed-in point or consumption point
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
| meter_type |
CT-operated three-phase DIN-rail energy meter with 333 mV current-transformer inputs
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
| overload_short_term |
3x Imax / 20 sec
Fronius Smart Meter IP 5kA-3 - technical data
|
| phase_count |
3
Fronius Smart Meter IP 5kA-3 - technical data
|
| physical_interfaces |
['RS485', 'Ethernet (LAN)', 'Wi-Fi']
Fronius Smart Meter IP 5kA-3 - technical data
|
| rated_voltage_v |
100-240 V (3x 208-480 V)
Fronius Smart Meter IP 5kA-3 - technical data
|
| self_consumption_w |
5
Fronius Smart Meter IP 5kA-3 - technical data
|
| starting_current_ma |
20
Fronius Smart Meter IP 5kA-3 - technical data
|
| supported_ct_ratios |
CT primary 1 - 5000 A, secondary 333 mV output only
Fronius Smart Meter IP 5kA-3 - technical data
|
| terminal_cross_section_mm2 |
1.5 - 4 mm2 phase and neutral; 0.25 - 2.5 mm2 CT and communication cables
Fronius Smart Meter IP 5kA-3 - technical data
|
Physical / mechanical
| dimensions_mm |
58 x 53 x 90 (length x width x height), depth 58
Fronius Smart Meter IP 5kA-3 - technical data
|
| weight_kg |
0.13
Fronius Smart Meter IP 5kA-3 - technical data
|
Installation
| mounting |
Indoors (DIN rail), 3 modules DIN 43880
Fronius Smart Meter IP 5kA-3 - technical data
|
Environment
| operating_temperature_c |
-25 to +55
Fronius Smart Meter IP 5kA-3 - technical data
|
Interfaces & connectors
| documented_ports | [{'port_role': 'RS485', 'port_label_from_manual': 'Modbus RTU connection area', 'port_type': 'screw terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 1, 'page': 'Commissioning / Connecting to the inverter', 'quote': 'Connect the data communication connections of the Fronius Smart Meter IP to the Modbus interface of the Fronius inverter using a CAT 5 STP (Shielded Twisted Pair) or higher data cable.'}, {'port_role': 'ETHERNET', 'port_label_from_manual': 'LAN port', 'port_type': 'RJ45', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 1, 'page': 'Commissioning / Connecting to the inverter', 'quote': 'One LAN port is present. Use a shielded data cable of type CAT 5 STP (Shielded Twisted Pair) or higher.'}, {'port_role': 'WIFI', 'port_label_from_manual': 'WiFi', 'port_type': 'integrated radio', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 1, 'page': 'Status LED description', 'quote': 'Flashing green: WiFi connection is being established / Illuminated green: WiFi connection is active'}, {'port_role': 'CT', 'port_label_from_manual': 'Current transformer connection', 'port_type': 'screw terminals', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 3, 'document': 1, 'page': 'Technical data / current transformers', 'quote': 'The current transformer must generate 333 mV at nominal current.'}] |
| local_web_ui |
True
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
| protocols |
['Modbus RTU', 'Modbus TCP', 'MQTT (secured)']
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
| wifi |
True
Fronius Smart Meter IP 5kA-3 Operating Instructions (digital eManual)
|
Protection
| ingress_protection |
IP20 (front frame), IP30 (terminals)
Fronius Smart Meter IP 5kA-3 - technical data
|
Документи
product_page
Fronius Smart Meter IP 5kA-3 - technical data
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | complete |
| region_notes | Documented from Fronius' English (EU) product page and the English digital operating instructions. Nominal voltage row reads '100 - 240 (3x 208-480)', so the hardware covers several grid configurations, but only the EU-language documentation was opened this session. |
| withheld:ct_secondary_current_a | "not applicable - 333 mV voltage-output CTs only" |
| withheld:rs485_port_count | 1 |