⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer EU перевірено 23 вересня 2026 р.

Identity

category smart_meters
manufacturer Fronius
model Fronius Smart Meter TS 5kA-3
region EU

Electrical

accuracy_class 1
Fronius Smart Meter TS 5kA-3 - technical data
baud_rate 9600, 19,200, 38,400 bit/s
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
ct_secondary_current_a [1, 5]
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
ethernet_port_count 0
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
local_modbus_available True
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
max_current_a 6
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
measurement_directions bidirectional - can be installed at the feed-in point or the consumption point, and can be configured to measure imported and exported energy separately or all energy without regard to direction
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
meter_type CT-operated three-phase DIN-rail energy meter with 1 A / 5 A current-transformer inputs
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
modbus_address_range 1-255
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
nominal_current_a 1 A + 5 A
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
overload_short_term 30A@500ms
Fronius Smart Meter TS 5kA-3 - technical data
physical_interfaces ['RS485']
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
rated_voltage_v 400-480 V (L-L) / 230-277 V (L-N)
Fronius Smart Meter TS 5kA-3 - technical data
rs485_port_count 1
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
self_consumption_w 1 W (product page); 0.3 W per phase current path (manual)
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
starting_current_ma 10
Fronius Smart Meter TS 5kA-3 - technical data
supported_ct_ratios current transformer ratio kCT 1 - 1000 (kCT = 1 for direct connection)
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
terminal_cross_section_mm2 1-4 mm2 phase and neutral; 0.05 mm2 current transformers and communication cables
Fronius Smart Meter TS 5kA-3 - technical data

Physical / mechanical

dimensions_mm 53.8 (W) x 91.5 (H) x 63 (D)
Fronius Smart Meter TS 5kA-3 - technical data
weight_kg 0.24
Fronius Smart Meter TS 5kA-3 - technical data

Environment

operating_temperature_c -25 to +65
Fronius Smart Meter TS 5kA-3 - technical data

Interfaces & connectors

documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 - 3 conductors', 'port_type': 'screw terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 1, 'page': 'Technical data / data communication', 'quote': 'RS485 - 3 conductors, Serial, asynchronous transmission; Modbus RTU addressing scheme (1-255)'}, {'port_role': 'CT', 'port_label_from_manual': 'Current transformer inputs', 'port_type': 'screw terminals', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 3, 'document': 1, 'page': 'Installation / current transformers', 'quote': 'Current transformers must supply alternating current at a nominal current of 1 or 5 A.'}]
protocols ['Modbus RTU']
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
wifi False
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)

Документи

manual Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
product_page Fronius Smart Meter TS 5kA-3 - technical data

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesscomplete
region_notes400-480 V (L-L) / 230-277 V (L-N) three-phase CT-operated meter; documented from the English (EU) product page and English operating instructions.
withheld:direct_current_max_a"not applicable - CT-operated meter"
withheld:phase_count3