Fronius Fronius Smart Meter TS 5kA-3
Official manufacturer EU перевірено 23 вересня 2026 р.
Identity
| category | smart_meters |
| manufacturer | Fronius |
| model | Fronius Smart Meter TS 5kA-3 |
| region | EU |
Electrical
| accuracy_class |
1
Fronius Smart Meter TS 5kA-3 - technical data
|
| baud_rate |
9600, 19,200, 38,400 bit/s
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| ct_secondary_current_a |
[1, 5]
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| ethernet_port_count |
0
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| local_modbus_available |
True
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| max_current_a |
6
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| measurement_directions |
bidirectional - can be installed at the feed-in point or the consumption point, and can be configured to measure imported and exported energy separately or all energy without regard to direction
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| meter_type |
CT-operated three-phase DIN-rail energy meter with 1 A / 5 A current-transformer inputs
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| modbus_address_range |
1-255
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| nominal_current_a |
1 A + 5 A
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| overload_short_term |
30A@500ms
Fronius Smart Meter TS 5kA-3 - technical data
|
| physical_interfaces |
['RS485']
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| rated_voltage_v |
400-480 V (L-L) / 230-277 V (L-N)
Fronius Smart Meter TS 5kA-3 - technical data
|
| rs485_port_count |
1
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| self_consumption_w |
1 W (product page); 0.3 W per phase current path (manual)
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| starting_current_ma |
10
Fronius Smart Meter TS 5kA-3 - technical data
|
| supported_ct_ratios |
current transformer ratio kCT 1 - 1000 (kCT = 1 for direct connection)
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| terminal_cross_section_mm2 |
1-4 mm2 phase and neutral; 0.05 mm2 current transformers and communication cables
Fronius Smart Meter TS 5kA-3 - technical data
|
Physical / mechanical
| dimensions_mm |
53.8 (W) x 91.5 (H) x 63 (D)
Fronius Smart Meter TS 5kA-3 - technical data
|
| weight_kg |
0.24
Fronius Smart Meter TS 5kA-3 - technical data
|
Environment
| operating_temperature_c |
-25 to +65
Fronius Smart Meter TS 5kA-3 - technical data
|
Interfaces & connectors
| documented_ports | [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 - 3 conductors', 'port_type': 'screw terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 1, 'page': 'Technical data / data communication', 'quote': 'RS485 - 3 conductors, Serial, asynchronous transmission; Modbus RTU addressing scheme (1-255)'}, {'port_role': 'CT', 'port_label_from_manual': 'Current transformer inputs', 'port_type': 'screw terminals', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 3, 'document': 1, 'page': 'Installation / current transformers', 'quote': 'Current transformers must supply alternating current at a nominal current of 1 or 5 A.'}] |
| protocols |
['Modbus RTU']
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
| wifi |
False
Fronius Smart Meter TS 5kA-3 Operating Instructions (digital eManual 42,0426,0348)
|
Документи
product_page
Fronius Smart Meter TS 5kA-3 - technical data
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | complete |
| region_notes | 400-480 V (L-L) / 230-277 V (L-N) three-phase CT-operated meter; documented from the English (EU) product page and English operating instructions. |
| withheld:direct_current_max_a | "not applicable - CT-operated meter" |
| withheld:phase_count | 3 |