⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer EU перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Gossen Metrawatt
model CENTRAX CU3000
region EU
variant —

Electrical

accuracy_class 0.2S active energy; 0.5S reactive energy суперечливе
CENTRAX CU3000 product page
analog_outputs +/-20 mA (2 or 4), optional module
current_channels 4
CENTRAX CU3000 product page
data_memory 16 GB (optional) суперечливе
CENTRAX CU3000 product page
digital_inputs 1
CENTRAX CU3000 product page
digital_io Standard: 1 digital input, 2 digital outputs; optional 4 digital inputs and 2 relay outputs
digital_outputs 2
CENTRAX CU3000 product page
harmonic_analysis_standard IEC 61000-4-7
harmonics_standard IEC 61000-4-7
CENTRAX CU3000 product page
measurement_accuracy_percent 0.1
CENTRAX CU3000 product page
measurement_category 600 V CAT III (voltage), 300 V CAT III (current)
measurement_category_current 300V CAT III
CENTRAX CU3000 product page
measurement_category_voltage 600V CAT III
CENTRAX CU3000 product page
measurement_channels 4 current and 4 voltage channels with 0.1% accuracy
panel_cutout_mm 144x144
CENTRAX CU3000 product page
plc Codesys Soft-PLC, 3 performance classes (BASIC, ADVANCED, PROFESSIONAL)
CENTRAX CU3000 product page
plc_functionality Codesys-based, 3 performance classes (BASIC / ADVANCED / PROFESSIONAL)
power_quality_events Optional disturbance recorder per IEC 61000-4-30 Ed.3
CENTRAX CU3000 product page
sampling_rate_khz 18
CENTRAX CU3000 product page
security_features Role-based access control, HTTPS, audit log with SYSLOG, client whitelist, digital firmware signature
ups_option 5x3 minutes суперечливе
CENTRAX CU3000 product page
voltage_channels 4
CENTRAX CU3000 product page

Installation

mounting Panel mounting 144 x 144 mm

Interfaces & connectors

communication_protocol Ethernet: Modbus/TCP, HTTP/HTTPS, NTP, SFTP, SYSLOG; Modbus/RTU master or slave; optional IEC 61850
communications ['Ethernet', 'RS485']
CENTRAX CU3000 product page
documented_ports [{'port_role': 'ETHERNET', 'port_label_from_manual': 'Communication', 'port_type': 'Ethernet', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 0, 'page': 'Technical characteristics table on the CENTRAX CU3000 product page', 'quote': 'Communication | Ethernet (Modbus/TCP, http/https), Modbus/RTU, optional IEC61850'}, {'port_role': 'RS485', 'port_label_from_manual': 'Communication', 'port_type': 'RS485 (Modbus/RTU)', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 0, 'page': 'Technical characteristics table on the CENTRAX CU3000 product page', 'quote': 'Communication | Ethernet (Modbus/TCP, http/https), Modbus/RTU, optional IEC61850'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Standard Digital Outputs', 'port_type': 'digital output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': 'Technical characteristics table on the CENTRAX CU3000 product page', 'quote': 'Standard Digital Outputs | 2'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Standard Digital Input', 'port_type': 'digital input', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical characteristics table on the CENTRAX CU3000 product page', 'quote': 'Standard Digital Input | 1'}]
protocols ['Modbus TCP', 'HTTP', 'HTTPS', 'Modbus RTU', 'IEC 61850']
CENTRAX CU3000 product page

Документи

certificate CENTRAX CU3000 CE certificate
communication_manual CENTRAX CU series Modbus interface (EN)
datasheet CENTRAX CU series pamphlet (EN) P1043
product_page CENTRAX CU3000 product page
user_manual CENTRAX CU series operating instructions (EN)

Зафіксовані конфлікти

electrical.ups_option Review required
5x3 minutes — stored value
Optional UPS (5 x 3 minutes) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.data_memory Review required
16 GB (optional) — stored value
16 GB (option) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.accuracy_class Review required
0.2S active energy; 0.5S reactive energy — stored value
Active energy class 0.2S; reactive energy class 0.5S — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesGerman manufacturer (GMC-I Messtechnik GmbH); IEC 62053 / EN power meter for the European market.