⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer EU перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Gossen Metrawatt
model SINEAX AM1000
region EU
variant —

Electrical

accuracy_class IEC 62053-22:2003 0.5S active; IEC 62053-24:2014 0.5S reactive суперечливе
SINEAX AM1000 product page
analog_outputs +/-20mA (2/4 optional) суперечливе
SINEAX AM1000 product page
condition_monitoring All voltages, currents, powers and power factors every 10/12 cycles
current_channels 3
SINEAX AM1000 product page
data_memory 16 GB (optional data logger) суперечливе
SINEAX AM1000 product page
digital_inputs 4 active/passive (optional) суперечливе
SINEAX AM1000 product page
digital_io 1 суперечливе
SINEAX AM1000 product page
digital_outputs 1
SINEAX AM1000 product page
display High-resolution color TFT display (320x240px)
SINEAX AM1000 product page
disturbance_recorder Optional, for PQ events (voltage dip, swell, interruption) acc. IEC 61000-4-30 Ed.3
harmonic_analysis_standard IEC 61000-4-7
harmonics_standard IEC 61000-4-7
SINEAX AM1000 product page
measurement_accuracy_percent 0.2
SINEAX AM1000 product page
measurement_category 600 V CAT III (voltage), 300 V CAT III (current)
measurement_category_current 300V, CAT III
SINEAX AM1000 product page
measurement_category_voltage 600V, CAT III
SINEAX AM1000 product page
measurement_channels 3 current channels and 3 voltage channels, 0.2% accuracy
panel_cutout_mm 96x96
SINEAX AM1000 product page
relay_outputs 2 (optional) суперечливе
SINEAX AM1000 product page
sampling_rate_khz 18
SINEAX AM1000 product page
voltage_channels 3
SINEAX AM1000 product page

Installation

mounting Panel mounting 96 x 96 mm

Interfaces & connectors

communications ['Ethernet', 'RS485']
SINEAX AM1000 product page
documented_ports [{'port_role': 'ETHERNET', 'port_label_from_manual': 'Communication Options', 'port_type': 'Ethernet', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 0, 'page': 'Technical characteristics table on the SINEAX AM1000 product page', 'quote': 'Communication Options | Ethernet (Modbus/TCP, http/https, NTP, SFTP, SYSLOG), IEC61850, Profinet I/O, Modbus/RTU (optional)'}, {'port_role': 'RS485', 'port_label_from_manual': 'Communication Options', 'port_type': 'RS485 (Modbus/RTU)', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 0, 'page': 'Technical characteristics table on the SINEAX AM1000 product page', 'quote': 'Communication Options | Ethernet (Modbus/TCP, http/https, NTP, SFTP, SYSLOG), IEC61850, Profinet I/O, Modbus/RTU (optional)'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Standard Digital Output', 'port_type': 'digital output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical characteristics table on the SINEAX AM1000 product page', 'quote': 'Standard Digital Output | 1'}]
protocols ['Modbus TCP', 'HTTP', 'HTTPS', 'NTP', 'SFTP', 'SYSLOG', 'IEC 61850', 'PROFINET IO', 'Modbus RTU']
SINEAX AM1000 product page

Документи

certificate SINEAX AM1000 CE certificate
communication_manual SINEAX AM1000/3000 MODBUS interface (EN)
datasheet SINEAX AM series pamphlet (EN) P1036
product_page SINEAX AM1000 product page
user_manual SINEAX AM series operating instructions (EN)

Зафіксовані конфлікти

electrical.data_memory Review required
16 GB (optional data logger) — stored value
16 GB data logger memory (optional) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.digital_io Review required
1 — stored value
Standard: 1 digital output, 1 digital input/output — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.digital_inputs Review required
4 active/passive (optional) — stored value
4, active / passive — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.relay_outputs Review required
2 (optional) — stored value
2 — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.analog_outputs Review required
+/-20mA (2/4 optional) — stored value
+/-20 mA (2 or 4) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15
electrical.accuracy_class Review required
IEC 62053-22:2003 0.5S active; IEC 62053-24:2014 0.5S reactive — stored value
Active/reactive energy class 0.5S (HT/LT, demand/delivery), configurable resolution — incoming package
Detected during import deep-enrich-pass2-2026-09-batch15

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesGerman manufacturer (GMC-I Messtechnik GmbH); IEC 62053 / EN power meter for the European market.