⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 23 вересня 2026 р.

Identity

category smart_meters
manufacturer Huawei
marketing_name Smart Power Sensor
model DTSU666-HW
note Distinguished from the DTSU666-H by direct current measurement without external CTs up to 80 A. Above 80 A, CT connection is required.
region GLOBAL
variant direct-measurement (no external CT) three-phase, up to 80 A

Electrical

ac_voltage_v 230 V AC / 400 V AC
DTSU666-HW Smart Power Sensor Quick Guide (ZTY0.464.1516)
accuracy_class Class 1 (error within ±1%) суперечливе
ct_ratio n/a for direct connection; UNKNOWN when CT-connected
direct_measurement_current_a 80
frequency_hz 50 / 60
grid_frequency_hz 50/60
DTSU666-HW Smart Power Sensor Quick Guide (ZTY0.464.1516)
measurement_method direct up to 80 A; external CT required above 80 A
measurement_voltage_range_v 90 - 1000 V line voltage; direct connection ≤500 V, potential transformers required above 500 V
nominal_voltage_v 230 V AC / 400 V AC
phase_configuration three-phase
power_consumption_w —
power_grid_type three-phase four-wire or three-phase three-wire

Physical / mechanical

dimensions_mm 72 x 80 x 62 mm (±1 mm tolerance)
din_modules —
mounting_type DIN35 mm rail
weight_kg —

Installation

connected_device SmartLogger or inverter via RS485
import_export_measurement Measures import/export at the point of connection; no explicit sign convention published in the fetched quick guide.
topology DIN-rail mounted; connects to a Huawei inverter or SmartLogger via RS485; measures at the point of connection.

Environment

ip_rating —
max_operating_altitude_m —
operating_humidity_pct_rh —
operating_temperature_c -25 to +60

Interfaces & connectors

baud_rate_bps 4800 / 9600 / 19200 / 115200 (default 9600)
communication_interface RS485
modbus_address_range 1-247 (default 011)
protocol Modbus-RTU
register_map_public —

Certifications

list —

Warranty & service

standard_warranty_years —

Документи

quick_guide DTSU666-HW Smart Power Sensor Quick Guide (ZTY0.464.1516) rev Issue 07 / ZTY0.464.1516

Зафіксовані конфлікти

electrical.accuracy_class Review required
Class 1 (error within ±1%) — stored value
Class 1 — Accuracy Class: Class 1 (error within ±1%)
Detected during import wave4-2026-09-batch09

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
manufacturer_legal_entity_as_printedUNKNOWN
region_notesDocument served from Huawei's APAC attachment path; the guide itself is not market-specific.