Janitza UMG 604-PRO
Official manufacturer GLOBAL перевірено 25 вересня 2026 р.
Identity
| category | smart_meters |
| manufacturer | Janitza |
| model | UMG 604-PRO |
| region | GLOBAL |
Electrical
| accuracy_class_active_energy |
0.5S (.../5 A)
UMG 604-PRO | Technical data
|
| accuracy_current_percent |
0.25
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| accuracy_power_percent |
0.4
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| accuracy_voltage_percent |
0.2
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| ct_secondary_current_a |
5
UMG 604-PRO | Technical data
|
| current_measuring_range_a |
0.005 to 7 A
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| current_overload_1s_a |
100
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| current_resolution_ma |
10
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| digital_input_count |
2
UMG 604-PRO | Technical data
|
| digital_output_count |
2
UMG 604-PRO | Technical data
|
| direct_current_max_a |
Not applicable - the device is connected through external current transformers
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| harmonics_order |
1st - 40th
UMG 604-PRO | Technical data
|
| local_modbus_available |
True
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| measurement_category |
300 V CAT III
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| measuring_range_l_l_vrms |
0 to 1000 Vrms
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| measuring_range_l_n_vrms |
0 to 600 Vrms
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| memory_mb |
128
UMG 604-PRO | Technical data
|
| meter_type |
DIN-rail power quality analyser (PMD), current-transformer connected
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| network_types |
Three-phase 4-conductor
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| nominal_voltage_l_l_max_v |
480
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| nominal_voltage_l_n_max_v |
277
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| phase_count |
3
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| physical_interfaces |
['RS232', 'RS485', 'Ethernet RJ45']
UMG 604-PRO | Technical data
|
| power_consumption |
max. 3.2 W / 9 VA (230 V and 90 V options); max. 5 W / 8 VA (24 V option)
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| rated_current_a |
5
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| sampling_rate_khz_per_phase |
20
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| supply_voltage |
230 V option: AC 95 V to 240 V (50/60 Hz) / DC 135 V to 340 V; 90 V option: AC 50 V to 110 V / DC 50 V to 155 V; 24 V option: AC 20 V to 50 V / DC 20 V to 70 V
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| voltage_resolution_v |
0.01
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
| weight_g |
350
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
Physical / mechanical
| dimensions_mm |
107.5 x 90 x 82
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
Installation
| mounting |
35 mm DIN rail
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
Interfaces & connectors
| cloud_required |
False
UMG 604-PRO product page
|
| documented_ports | [{'port_role': 'RS232', 'port_label_from_manual': 'RS232', 'port_type': '5-pin screw-type terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Interfaces', 'quote': 'RS232 | "5-pin screw-type terminals" | "Modbus RTU/slave"'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': '2-pin screw-type terminals', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Interfaces', 'quote': 'RS485 | "2-pin screw-type terminals" | "Modbus RTU/slave, Modbus RTU/master"'}, {'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'RJ45', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Interfaces', 'quote': 'Ethernet | "RJ45" | "TCP/IP, Modbus/TCP(port 502)"'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Digital / Pulse output', 'port_type': 'semiconductor relay', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': 'Digital I/O', 'quote': 'Outputs: "2 digital outputs; semiconductor relays, not short-circuit proof"'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Digital inputs', 'port_type': 'S0 pulse input', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 2, 'document': 1, 'page': 'Technical data', 'quote': 'Digital inputs: "2"'}] |
| protocols |
['Modbus RTU (slave)', 'Modbus RTU (master)', 'Modbus TCP/IP', 'Modbus Gateway', 'BACnet', 'TCP/IP']
UMG 604-PRO | Technical data
|
Protection
| ingress_protection |
IP20
Power Quality Analyser UMG 604-PRO - data sheet (EN)
|
Документи
product_page
UMG 604-PRO product page
product_page
UMG 604-PRO | Technical data
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | One worldwide specification: the datasheet prints 300 V CAT III measurement category with a 600 Vrms L-N / 1000 Vrms L-L metering range and the product page lists UL certification and ANSI, so the same device is sold in IEC and UL markets. Supply-voltage build options (230 V / 90 V / 24 V) are separate order variants, not regional specifications. |
| withheld:ethernet_port_count | 1 |
| withheld:rs232_port_count | 1 |
| withheld:rs485_port_count | 1 |