⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Janitza
model UMG 96-PA
region GLOBAL

Electrical

accuracy_class_active_energy 0.2S (IEC 62053-22); 0.2 (IEC 61557-12); 0.2 (ANSI C12.20)
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
ct_secondary_current_a 5
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
current_measuring_range_a 0.005 .. 6 Arms
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
current_overload_1s_a 60
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
digital_input_count 3
UMG 96-PA | Technical data
digital_output_count 3
UMG 96-PA | Technical data
direct_current_max_a Not applicable - the device is connected through external current transformers
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
frequency_hz 45 Hz .. 65 Hz
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
harmonics_order 1st - 40th
UMG 96-PA | Technical data
local_modbus_available True
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
manufacturer_part_numbers ['52.32.001', '52.32.002', '52.32.004', '52.32.010']
UMG 96-PA leaflet (EN)
measurement_category 600 V CAT III
UMG 96-PA | Technical data
memory_mb 8
UMG 96-PA | Technical data
meter_type Panel-mounted modular power analyser (PMD), current-transformer connected
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
network_types TT-Net, TN-Net
UMG 96-PA | Technical data
nominal_voltage_max_v up to 417 V / 720 V (three-phase 4-conductor)
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
panel_cutout_mm 92+0.8 x 92+0.8
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
phase_count 3
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
physical_interfaces ['RS485', 'Ethernet']
UMG 96-PA | Technical data
power_consumption max. 4.5 VA / 2 W
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
rated_current_a 5
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
rs485_baud_rates 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
supply_voltage 230 V option: AC 90 V - 277 V (50/60 Hz) or DC 90 V - 250 V, 300 V CATIII; 24 V option: AC 24 V - 90 V (50/60 Hz) or DC 24 V - 90 V, 150 V CATIII
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet

Physical / mechanical

depth_mm 87.2
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet

Interfaces & connectors

cloud_required False
UMG 96-PA | Technical data
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS-485', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Interfaces', 'quote': '"RS-485 - Modbus RTU/Slave 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps"'}, {'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'Ethernet', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 1, 'page': 'Technical data', 'quote': 'Interfaces: "RS485, Ethernet"; Protocols: "Modbus RTU, Modbus TCP/IP, Modbus Gateway"'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Digital inputs', 'port_type': 'digital input', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 3, 'document': 0, 'page': 'Digital inputs and outputs', 'quote': 'Digital inputs: 3 inputs'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Digital / Pulse output', 'port_type': 'digital output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 3, 'document': 0, 'page': 'Digital inputs and outputs', 'quote': 'Digital outputs: 3 outputs'}]
protocols ['Modbus RTU (slave)', 'Modbus TCP/IP', 'Modbus Gateway']
UMG 96-PA | Technical data

Protection

ingress_protection IP40 front (EN60529), IP54 front with seal, IP20 rear
Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet

Документи

datasheet Power Analyzer UMG 96-PA (from Firmware 3.41) / UMG 96-PA-MID+ (from Firmware 3.41) - Data sheet
product_page UMG 96-PA
product_page UMG 96-PA leaflet (EN)
product_page UMG 96-PA | Technical data

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesOne worldwide specification: the data sheet prints IEC 62053-22, IEC 61557-12 and ANSI C12.20 accuracy classes for the same device, and 600 V CAT III on the technical-data page.