Siemens 7KM PAC2200
Manufacturer documented GLOBAL перевірено 23 вересня 2026 р.
Identity
| category | smart_meters |
| manufacturer | Siemens |
| model | 7KM PAC2200 |
| region | GLOBAL |
| variant | — |
Electrical
| accuracy_class |
Class 1
SENTRON 7KM measuring device PAC2200 Product Manual
|
| accuracy_class_active_energy |
Class 1
SENTRON 7KM measuring device PAC2200 Product Manual
|
| accuracy_class_reactive |
Class 2
SENTRON 7KM measuring device PAC2200 Product Manual
|
| ct_secondary_current_a |
[1, 5]
SENTRON 7KM measuring device PAC2200 Product Manual
|
| digital_input_type |
optically isolated, passive
SENTRON 7KM measuring device PAC2200 Product Manual
|
| digital_inputs |
1
SENTRON 7KM measuring device PAC2200 Product Manual
|
| digital_outputs |
1
SENTRON 7KM measuring device PAC2200 Product Manual
|
| direct_current_max_a |
65
SENTRON 7KM measuring device PAC2200 Product Manual
|
| display |
LC display with four control keys with variable function assignment
SENTRON 7KM measuring device PAC2200 Product Manual
|
| frequency_hz |
50/60
SENTRON 7KM measuring device PAC2200 Product Manual
|
| grid_frequency_hz |
[50, 60]
SENTRON 7KM measuring device PAC2200 Product Manual
|
| local_modbus_available |
True
SENTRON 7KM measuring device PAC2200 Product Manual
|
| max_measuring_voltage_ll_v |
480
SENTRON 7KM measuring device PAC2200 Product Manual
|
| max_measuring_voltage_ln_v |
277
SENTRON 7KM measuring device PAC2200 Product Manual
|
| meter_type |
Panel-mount power monitoring device; ordered either CT-connected (x/1 A or x/5 A) or direct-connected up to 65 A
SENTRON 7KM measuring device PAC2200 Product Manual
|
| modbus_tcp_port |
502
SENTRON 7KM measuring device PAC2200 Product Manual
|
| nominal_voltage_ln_v |
230
SENTRON 7KM measuring device PAC2200 Product Manual
|
| nominal_voltage_v |
400
SENTRON 7KM measuring device PAC2200 Product Manual
|
| phase_count |
3 (three-wire / four-wire networks)
суперечливе
PAC2200 SENTRON 7KM Power Monitoring Device Equipment Manual (L1V30415167B-06)
|
| physical_interfaces |
['Ethernet (RJ45)', 'RS485', 'M-Bus (optional)', '1 digital input', '1 digital output']
PAC2200 SENTRON 7KM Power Monitoring Device Equipment Manual (L1V30415167B-06)
|
| pulse_output |
pulse function corresponds to the IEC 62053-31 standard
SENTRON 7KM measuring device PAC2200 Product Manual
|
| rated_voltage_v |
220/230 V AC rated; up to 277 V L-N and 480 V L-L
SENTRON 7KM measuring device PAC2200 Product Manual
|
| supported_ct_ratios |
Primary 1 A to 99999 A freely adjustable; secondary 1 A or 5 A
SENTRON 7KM measuring device PAC2200 Product Manual
|
| system_type |
three-wire or four-wire TN and TT networks
SENTRON 7KM measuring device PAC2200 Product Manual
|
Physical / mechanical
| dimensions_mm |
108 mm x 97 mm x 71 mm
SENTRON 7KM measuring device PAC2200 Product Manual
|
Installation
| mounting |
TH35 rail (complying with EN 60715)
SENTRON 7KM measuring device PAC2200 Product Manual
|
Environment
| ip_rating |
IP 40 (front), IP 20 (termination)
SENTRON 7KM measuring device PAC2200 Product Manual
|
| operating_temperature_max_c |
55
SENTRON 7KM measuring device PAC2200 Product Manual
|
| operating_temperature_min_c |
-25
SENTRON 7KM measuring device PAC2200 Product Manual
|
Interfaces & connectors
| cloud_required |
False
SENTRON 7KM measuring device PAC2200 Product Manual
|
| documented_ports | [{'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'Ethernet, Modbus TCP', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus TCP via Ethernet'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS-485, Modbus RTU', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus RTU via RS485'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Digital Input', 'port_type': 'Optically isolated passive input', 'direction': 'INPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital Input: 1, optically isolated, passive type'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Digital output', 'port_type': 'Passive pulse output (IEC 62053-31)', 'direction': 'OUTPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital output: 1, passive'}] |
| ethernet |
True
SENTRON 7KM measuring device PAC2200 Product Manual
|
| modbus_rtu |
True
SENTRON 7KM measuring device PAC2200 Product Manual
|
| modbus_tcp |
True
SENTRON 7KM measuring device PAC2200 Product Manual
|
| protocols |
['Modbus TCP', 'Modbus RTU', 'HTTP (web server)', 'SNTP', 'DHCP', 'M-Bus (EN 13757)']
SENTRON 7KM measuring device PAC2200 Product Manual
|
| rs485 |
True
SENTRON 7KM measuring device PAC2200 Product Manual
|
Документи
product_page
SENTRON measuring devices for energy transparency
Зафіксовані конфлікти
interfaces.documented_ports Resolved — accepted incoming value
[{'port_role': 'ETHERNET', 'port_label_from_manual': 'LAN', 'port_type': 'RJ45', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Technical specifications', 'quote': 'Ethernet Interface - Protocol: "Modbus TCP; web server (HTTP); SNTP; DHCP"; Port: 502 (Modbus TCP, configurable)'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Technical specifications', 'quote': 'RS485 Interface: "MODBUS RTU"'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'DI', 'port_type': 'digital input', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical specifications', 'quote': 'Digital Inputs/Outputs: "1 digital input" / "1 digital output"'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'DO', 'port_type': 'digital output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical specifications', 'quote': 'Digital Inputs/Outputs: "1 digital input" / "1 digital output"'}] — stored value
[{'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'Ethernet, Modbus TCP', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus TCP via Ethernet'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS-485, Modbus RTU', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus RTU via RS485'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Digital Input', 'port_type': 'Optically isolated passive input', 'direction': 'INPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital Input: 1, optically isolated, passive type'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Digital output', 'port_type': 'Passive pulse output (IEC 62053-31)', 'direction': 'OUTPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital output: 1, passive'}] — incoming package
Detected during import deep-enrich-2026-09-batch25
electrical.phase_count Review required
3 (three-wire / four-wire networks) — stored value
3 — single-phase, two-phase, or three-phase measurement
Detected during import deep-enrich-2026-09-batch25
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | IEC product family; Siemens publishes one 50/60 Hz specification. MID approval is limited to 50 Hz per the product manual. |
| withheld:max_connected_devices | "not applicable - measuring device, not a concentrator" |