⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Manufacturer documented GLOBAL перевірено 23 вересня 2026 р.

Identity

category smart_meters
manufacturer Siemens
model 7KM PAC2200
region GLOBAL
variant —

Electrical

accuracy_class Class 1
SENTRON 7KM measuring device PAC2200 Product Manual
accuracy_class_active_energy Class 1
SENTRON 7KM measuring device PAC2200 Product Manual
accuracy_class_reactive Class 2
SENTRON 7KM measuring device PAC2200 Product Manual
ct_secondary_current_a [1, 5]
SENTRON 7KM measuring device PAC2200 Product Manual
digital_input_type optically isolated, passive
SENTRON 7KM measuring device PAC2200 Product Manual
digital_inputs 1
SENTRON 7KM measuring device PAC2200 Product Manual
digital_outputs 1
SENTRON 7KM measuring device PAC2200 Product Manual
direct_current_max_a 65
SENTRON 7KM measuring device PAC2200 Product Manual
display LC display with four control keys with variable function assignment
SENTRON 7KM measuring device PAC2200 Product Manual
frequency_hz 50/60
SENTRON 7KM measuring device PAC2200 Product Manual
grid_frequency_hz [50, 60]
SENTRON 7KM measuring device PAC2200 Product Manual
local_modbus_available True
SENTRON 7KM measuring device PAC2200 Product Manual
max_measuring_voltage_ll_v 480
SENTRON 7KM measuring device PAC2200 Product Manual
max_measuring_voltage_ln_v 277
SENTRON 7KM measuring device PAC2200 Product Manual
meter_type Panel-mount power monitoring device; ordered either CT-connected (x/1 A or x/5 A) or direct-connected up to 65 A
SENTRON 7KM measuring device PAC2200 Product Manual
modbus_tcp_port 502
SENTRON 7KM measuring device PAC2200 Product Manual
nominal_voltage_ln_v 230
SENTRON 7KM measuring device PAC2200 Product Manual
nominal_voltage_v 400
SENTRON 7KM measuring device PAC2200 Product Manual
phase_count 3 (three-wire / four-wire networks) суперечливе
PAC2200 SENTRON 7KM Power Monitoring Device Equipment Manual (L1V30415167B-06)
physical_interfaces ['Ethernet (RJ45)', 'RS485', 'M-Bus (optional)', '1 digital input', '1 digital output']
PAC2200 SENTRON 7KM Power Monitoring Device Equipment Manual (L1V30415167B-06)
pulse_output pulse function corresponds to the IEC 62053-31 standard
SENTRON 7KM measuring device PAC2200 Product Manual
rated_voltage_v 220/230 V AC rated; up to 277 V L-N and 480 V L-L
SENTRON 7KM measuring device PAC2200 Product Manual
supported_ct_ratios Primary 1 A to 99999 A freely adjustable; secondary 1 A or 5 A
SENTRON 7KM measuring device PAC2200 Product Manual
system_type three-wire or four-wire TN and TT networks
SENTRON 7KM measuring device PAC2200 Product Manual

Physical / mechanical

dimensions_mm 108 mm x 97 mm x 71 mm
SENTRON 7KM measuring device PAC2200 Product Manual

Installation

mounting TH35 rail (complying with EN 60715)
SENTRON 7KM measuring device PAC2200 Product Manual

Environment

ip_rating IP 40 (front), IP 20 (termination)
SENTRON 7KM measuring device PAC2200 Product Manual
operating_temperature_max_c 55
SENTRON 7KM measuring device PAC2200 Product Manual
operating_temperature_min_c -25
SENTRON 7KM measuring device PAC2200 Product Manual

Interfaces & connectors

cloud_required False
SENTRON 7KM measuring device PAC2200 Product Manual
documented_ports [{'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'Ethernet, Modbus TCP', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus TCP via Ethernet'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS-485, Modbus RTU', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus RTU via RS485'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Digital Input', 'port_type': 'Optically isolated passive input', 'direction': 'INPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital Input: 1, optically isolated, passive type'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Digital output', 'port_type': 'Passive pulse output (IEC 62053-31)', 'direction': 'OUTPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital output: 1, passive'}]
ethernet True
SENTRON 7KM measuring device PAC2200 Product Manual
modbus_rtu True
SENTRON 7KM measuring device PAC2200 Product Manual
modbus_tcp True
SENTRON 7KM measuring device PAC2200 Product Manual
protocols ['Modbus TCP', 'Modbus RTU', 'HTTP (web server)', 'SNTP', 'DHCP', 'M-Bus (EN 13757)']
SENTRON 7KM measuring device PAC2200 Product Manual
rs485 True
SENTRON 7KM measuring device PAC2200 Product Manual

Документи

manual PAC2200 SENTRON 7KM Power Monitoring Device Equipment Manual (L1V30415167B-06)
manual SENTRON 7KM measuring device PAC2200 Product Manual
product_page SENTRON measuring devices for energy transparency

Зафіксовані конфлікти

interfaces.documented_ports Resolved — accepted incoming value
[{'port_role': 'ETHERNET', 'port_label_from_manual': 'LAN', 'port_type': 'RJ45', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Technical specifications', 'quote': 'Ethernet Interface - Protocol: "Modbus TCP; web server (HTTP); SNTP; DHCP"; Port: 502 (Modbus TCP, configurable)'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': None, 'document': 0, 'page': 'Technical specifications', 'quote': 'RS485 Interface: "MODBUS RTU"'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'DI', 'port_type': 'digital input', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical specifications', 'quote': 'Digital Inputs/Outputs: "1 digital input" / "1 digital output"'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'DO', 'port_type': 'digital output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical specifications', 'quote': 'Digital Inputs/Outputs: "1 digital input" / "1 digital output"'}] — stored value
[{'port_role': 'ETHERNET', 'port_label_from_manual': 'Ethernet', 'port_type': 'Ethernet, Modbus TCP', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus TCP via Ethernet'}, {'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS-485, Modbus RTU', 'direction': 'BIDIRECTIONAL', 'electrical_domain': 'COMMUNICATION', 'document': 0, 'page': 'Communication', 'quote': 'Modbus RTU via RS485'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'Digital Input', 'port_type': 'Optically isolated passive input', 'direction': 'INPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital Input: 1, optically isolated, passive type'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'Digital output', 'port_type': 'Passive pulse output (IEC 62053-31)', 'direction': 'OUTPUT', 'electrical_domain': 'SIGNAL', 'document': 0, 'page': 'Digital I/O', 'quote': 'Digital output: 1, passive'}] — incoming package
Detected during import deep-enrich-2026-09-batch25
electrical.phase_count Review required
3 (three-wire / four-wire networks) — stored value
3 — single-phase, two-phase, or three-phase measurement
Detected during import deep-enrich-2026-09-batch25

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesIEC product family; Siemens publishes one 50/60 Hz specification. MID approval is limited to 50 Hz per the product manual.
withheld:max_connected_devices"not applicable - measuring device, not a concentrator"