⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer GLOBAL перевірено 25 вересня 2026 р.

Identity

category smart_meters
manufacturer Socomec
model DIRIS B-10
region GLOBAL

Electrical

accuracy_class Class 0.2 for the PMD alone; Class 0.5 for the overall measurement chain from 2 % to 120 % of nominal current
DIRIS B range page
accuracy_class_active_energy Class 0.5 in accordance with standard IEC 61557-12
DIRIS B-10 - Reference 48290010
accuracy_class_active_energy_by_sensor Class 0.2 (DIRIS B alone); Class 0.5 with TE, iTR or TF sensors; Class 1 with TR sensors
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
accuracy_class_reactive_energy Class 2 with all sensor types
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
accuracy_class_voltage Class 0.2
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
circuit_configurations 4 single-phase loads, or 1 three-phase plus 1 single-phase load
DIRIS B range page
compatible_current_sensors Solid-core TE, split-core TR/iTR, flexible TF sensors
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
ct_required True
DIRIS B range page
ct_secondary_current_a Not applicable - Socomec TE/TR/iTR/TF sensors connect over a proprietary RJ12 link, not a 1 A or 5 A secondary
DIRIS B-10 - Reference 48290010
current_input_connector RJ12
DIRIS B range page
current_input_count 4
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
current_input_type 4 RJ12 independent current measurement inputs
DIRIS B-10 - Reference 48290010
digital_input_count 2
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
digital_input_type Optocoupler with internal (12VDC +/-10%) or external (10-30VDC +/-10%) bias
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
direct_connect False
DIRIS B range page
direct_current_max_a Not applicable - the device is connected through external Socomec current sensors
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
display None (B-10 model)
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
frequency_accuracy Class 0.02
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
frequency_hz 45 ... 65 Hz
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
local_modbus_available True
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
manufacturer_part_number 4829 0010
DIRIS B-10 - Reference 48290010
manufacturer_reference 48290010
DIRIS B range page
measurement_directions Import and export (+/-kWh, +/-kVArh, kVAh)
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
meter_type Modular DIN-rail power monitoring device (PMD), metering; connected through external current sensors on RJ12 inputs
DIRIS B range page
network_types Single-phase / Two-phase / Two-phase with neutral / Three-phase / Three-phase with neutral
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
phase_count 3
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
physical_interfaces ['RS485']
DIRIS B-10 - Reference 48290010
power_consumption < 2 VA without display, < 6 VA with display
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
rated_voltage_v 110-230 VAC +/-15% (Ph/N or Ph/Ph) Cat III
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
rs485_baud_rates 1200 ... 115200 bauds
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
rs485_link_type 2 ... 3 wire half duplex
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
sampling_frequency_hz 10000
DIRIS B-10 - Reference 48290010
supported_ct_ratios Set by the chosen TE / TR / iTR / TF sensor; no ratio table is printed on the device data
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
voltage_input_count 4
DIRIS B-10 - Reference 48290010
voltage_measuring_range_ph_n_v 50-300 VAC
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
voltage_measuring_range_ph_ph_v 87-520 VAC
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)

Physical / mechanical

dimensions_mm 90 x 54 x 65 (H x W x D)
DIRIS B-10 - Reference 48290010

Installation

mounting modular / DIN rail
DIRIS B range page

Environment

operating_temperature_c -10 ... +70
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)

Interfaces & connectors

cloud_required False
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical characteristics', 'quote': 'Communication protocol | Modbus RTU; Communication link type | "2 ... 3 fils half duplex"'}, {'port_role': 'CT', 'port_label_from_manual': 'current measurement inputs (RJ12)', 'port_type': 'RJ12', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': 4, 'document': 1, 'page': 'Technical characteristics', 'quote': 'Current Inputs | 4 RJ12 independent current measurement inputs'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'inputs (status/pulse)', 'port_type': 'optocoupler', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': 'Technical characteristics', 'quote': 'Digital inputs | 2; Digital input type | "Optocoupler with internal (12VDC +-10%) or external (10-30VDC +-10%) bias"'}] суперечливе
protocols ['Modbus RTU']
DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
rs485 True
DIRIS B range page

Protection

ingress_protection IP20 (front side)
DIRIS B-10 - Reference 48290010

Certifications

standards ['IEC 61557-12', 'UL 61010', 'ANSI C12.20', 'EN 50160']
DIRIS B range page

Документи

datasheet DIRIS B Power Monitoring Device - PMD, catalogue pages (PCG057 EN V01)
installation_manual DIRIS B-10 / B-30 Multifunction meters - Installation and operating manual (546770C)
installation_manual DIRIS B-10 / B-30 multifunction meters installation and operating manual 546770C (EN)
product_page DIRIS B range page
product_page DIRIS B-10 - Reference 48290010
quick_start_guide DIRIS B Power metering and monitoring device - Quick start guide (542520G)

Зафіксовані конфлікти

interfaces.documented_ports Review required
[{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical characteristics', 'quote': 'Communication protocol | Modbus RTU; Communication link type | "2 ... 3 fils half duplex"'}, {'port_role': 'CT', 'port_label_from_manual': 'current measurement inputs (RJ12)', 'port_type': 'RJ12', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': 4, 'document': 1, 'page': 'Technical characteristics', 'quote': 'Current Inputs | 4 RJ12 independent current measurement inputs'}, {'port_role': 'DIGITAL_IN', 'port_label_from_manual': 'inputs (status/pulse)', 'port_type': 'optocoupler', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': 'Technical characteristics', 'quote': 'Digital inputs | 2; Digital input type | "Optocoupler with internal (12VDC +-10%) or external (10-30VDC +-10%) bias"'}] — stored value
[{'port_role': 'RS485', 'port_label_from_manual': 'RS485', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'document': 3, 'page': 'product page', 'quote': 'a power monitoring device in a modular format that communicates via RS485'}, {'port_role': 'CT', 'port_label_from_manual': 'RJ12 current inputs', 'port_type': 'RJ12', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 4, 'document': 3, 'page': 'product page', 'quote': 'It features 4 independent RJ12 current inputs supporting multi-circuit configurations.'}] — incoming package
Detected during import wave4-2026-09-batch09

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notesIEC device built to IEC 61557-12 with a 110-230 VAC auxiliary supply at 50/60 Hz; Socomec publishes the same DIRIS B range on its EMEA, APAC and US sites, and the catalogue pages also cite UL 61010 and ANSI C12.20, so one specification covers all markets. The reference numbers recorded are the EMEA ones.