⚡ANMAПобудова системAutomation, Network, Monitoring & Analytics

База знань › Smart Meters

Official manufacturer EU перевірено 23 вересня 2026 р.

Identity

category smart_meters
manufacturer SolarEdge
model SE-WND-3Y400-MB-K2
region EU
variant —

Electrical

accuracy_class ±1.0 % (1% - 100% of Rated CT Current, @25°C, PF 1) суперечливе
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
ethernet_port_count 0
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
frequency_hz 48 to 62
grid_frequency_hz 48-62
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
humidity_range_pct 5 to 90, non-condensing
local_modbus_available True
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
measured_phases Single phase (L/N/PE) and three phase (L1/L2/L3/N/PE)
meter_type CT-operated wide-range energy meter with Modbus RS485 connection
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
modbus_default_device_id 2
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
operating_voltage_v 320-460 Vac line-to-line / 184-264 Vac line-to-neutral
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
phase_count 1 or 3 (Single Phase L/N/PE; Three Phase L1/L2/L3/N/PE)
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
physical_interfaces ['RS485']
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
power_consumption_w 1.8 (typ.) суперечливе
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
rated_voltage_v 400 Vac line-to-line / 230 Vac line-to-neutral
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
response_time ≤1 sec
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
response_time_s <= 1
rs485_line_termination 120 Ω
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
supported_ct_ratios SECT-SPL-100A-A (100 A), SECT-SPL-250A-A (250 A), SECT-SPL-1000A-A (1000 A)
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
voltage_range_v Nominal 400 Vac L-L / 230 Vac L-N; operating 320-460 Vac L-L, 184-264 Vac L-N

Physical / mechanical

dimensions_mm 85 x 153 x 38 (H x W x D)
weight_kg 0.31

Installation

mounting DIN rail / wall mount

Environment

operating_temperature_range_c -40 to 75

Interfaces & connectors

communication_protocol Modbus over RS485; default Modbus device ID 2; 120 ohm line termination
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'Supported Communication Interfaces', 'port_type': 'terminal', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'COMMUNICATION', 'quote': 'Supported Communication Interfaces: RS485; RS485 line termination: 120 Ω'}, {'port_role': 'CT', 'port_label_from_manual': 'Current transformer inputs', 'port_type': 'terminal', 'direction': 'input', 'electrical_domain': 'communication', 'quantity': 3, 'document': 0, 'page': 'CURRENT TRANSFORMER MODELS', 'quote': 'SECT-SPL-100A-A (100 A), SECT-SPL-250A-A (250 A), SECT-SPL-1000A-A (1000 A)'}]
protocols ['Modbus RTU']
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition
wifi False
SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition

Protection

protection_degree_ip Indoor rated (outdoor only when installed in an outdoor enclosure); enclosure ABS / ABS-PC plastic UL 94V-0, IEC FV-0

Документи

datasheet SolarEdge Energy Meter with Modbus Connection (SE-WND-3Y400-MB-K2) datasheet, UK edition

Зафіксовані конфлікти

electrical.power_consumption_w Review required
1.8 (typ.) — stored value
1.8 typical — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16
electrical.accuracy_class Review required
±1.0 % (1% - 100% of Rated CT Current, @25°C, PF 1) — stored value
+/- 1.0 % from 1% to 100% of rated CT current (at 25 °C, PF 1) — incoming package
Detected during import deep-enrich-pass2-2026-09-batch16

Додаткові задокументовані параметри

Записано дослівно з джерела; поля схеми для них поки немає.

builder_completenesspartial
region_notes400 V L-L / 230 V L-N, 48-62 Hz; the datasheet opened was SolarEdge's UK edition of the Energy Meter with Modbus Connection. It supports both single-phase (L/N/PE) and three-phase (L1/L2/L3/N/PE) connection.
withheld:direct_current_max_a"not applicable - CT-operated meter"
withheld:rs485_port_count1