WAGO 879-3040
Manufacturer documented EU перевірено 23 вересня 2026 р.
Identity
| category | smart_meters |
| manufacturer | WAGO |
| model | 879-3040 |
| region | EU |
Electrical
| accuracy_class_active_energy |
Class B (= 1 % error); active energy per EN 50470-3
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| ct_secondary_current_a |
[1, 5]
Energy meter (MID26) (879-3040)
|
| direct_current_max_a |
Not applicable - transformer-connected meter
Energy meter (MID26) (879-3040)
|
| frequency_hz |
45 ... 60
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| full_designation |
Energy meter (MID26); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz; Modbus and M-Bus; 2 x S0 interface; 2PU CT
Energy meter (MID26) (879-3040)
|
| local_modbus_available |
True
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| manufacturer_part_number |
879-3040
Energy meter (MID26) (879-3040)
|
| max_current_a |
5
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| measurement_directions |
Supply and reference direction (import and export)
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| meter_type |
DIN-rail three-phase energy meter for current-transformer connection (MID)
Energy meter (MID26) (879-3040)
|
| mid_conformity |
True
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| phase_count |
3
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| physical_interfaces |
['RS-485 (2-wire)', 'M-Bus', 'Bluetooth', '2 x S0']
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| rated_current_a |
1
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| rated_voltage_v |
3 x AC 230 ... 400 V
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| s0_output_count |
2
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| supported_ct_ratios |
1:1 ... 9999:1 / 5:5 ... 9995:5
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| tariffs |
4
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
Physical / mechanical
| module_width_mm |
36
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
Environment
| operating_temperature_c |
-40 ... +70
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
Interfaces & connectors
| cloud_required |
False
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| documented_ports | [{'port_role': 'RS485', 'port_label_from_manual': 'RS-485 (2-wire)', 'port_type': 'RS-485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Technical data', 'quote': 'Interface/Protocol | "Modbus, M-Bus, Bluetooth, RS-485 (2-wire)"'}, {'port_role': 'DIGITAL_OUT', 'port_label_from_manual': 'S0 interface', 'port_type': 'S0 pulse output', 'direction': 'output', 'electrical_domain': 'communication', 'quantity': 2, 'document': 0, 'page': 'Technical data', 'quote': 'S0 Outputs | "2 x S0 interfaces (configurable)"'}, {'port_role': 'CT', 'port_label_from_manual': 'transformer connection 1 A / 5 A', 'port_type': 'current transformer secondary terminals', 'direction': 'input', 'electrical_domain': 'AC', 'quantity': 3, 'document': 0, 'page': 'Technical data', 'quote': 'Current Transformer Ratio | "1:1 ... 9999 : 1 / 5:5 ... 9995 : 5"'}] |
| protocols |
['Modbus', 'M-Bus', 'Bluetooth']
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
Protection
| ingress_protection |
IP51 (front side) / IP20 (connection)
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
| protection_class |
II
WAGO data sheet 879-3040 - Energy meter (MID); for transformer connection; 1 A / 5 A; 3x230/400V; 50Hz
|
Документи
product_page
Energy meter (MID26) (879-3040)
Додаткові задокументовані параметри
Записано дослівно з джерела; поля схеми для них поки немає.
| builder_completeness | partial |
| region_notes | European product: 3 x 230/400 V, 50 Hz, MID conformity assessed to EN 50470-3. WAGO publishes no 60 Hz edition of this item number. |