Identity
| category | batteries |
| ean | UNKNOWN |
| generation | G2 |
| hardware_revision | UNKNOWN |
| legacy_name | Likely successor to the PowerDepot H5B - the ITS Technologies UK product code is 'DY-POWERDEPOTH5B-G2', and the Dyness LV-Link A compatibility list names 'PowerDepot H5B'. Not confirmed by a Dyness-published statement. |
| manufacturer | Dyness |
| market_version | EN/global; separate datasheet revisions exist for RO, ES, MEA and DE/AT/CH markets |
| model | PowerDepot G2 |
| mpn | DY-POWERDEPOTH5B-G2 (ITS Technologies UK product code; not confirmed against a Dyness-published part list) |
| product_family | Dyness PowerDepot |
| product_status | active |
| product_status_evidence | Listed on the dyness.com residential Low Voltage ESS index with a live official product page (fetched 2026-09-02); current user manual revision EN 251029 dated 2025-10-29. |
| region | Global |
| release_year | UNKNOWN (earliest located official datasheet revision is dated 2025-03-31; page image assets dated 2025-04-25; no release year printed) |
| sku | UNKNOWN |
| subcategory | low-voltage 48V-class wall/floor mounted battery module |
| variant_note | One variant published: 'PowerDepot G2 51.2V/100Ah' (5.12 kWh). |
Electrical
| cell_chemistry | lithium iron phosphate (LiFePO4) |
| cell_type | UNKNOWN |
| continuous_charge_current_a | 75 (the manual publishes a single 'Max Charging Current' with no separate continuous rating) |
| continuous_discharge_current_a | 100 (the manual publishes a single 'Max Discharging Current' with no separate continuous rating) |
| continuous_power_kw | 5.12 |
| cycle_life | >=8000 cycles / 10 years |
| depth_of_discharge_pct | UNKNOWN (not printed) |
| max_charge_current_a | 75 |
| max_charge_power_kw | 3.84 (inferred: 75 A max charging current x 51.2 V nominal; NOT printed. Do not use the 5.12 kW 'Nominal Power' figure for charging - that corresponds to the 100 A DISCHARGE rating) |
| max_discharge_current_a | 100 |
| max_discharge_power_kw | 5.12 |
| max_parallel_units | 50 |
| max_series_units | N/A (LV parallel stack) |
| nominal_capacity_ah | 100 |
| nominal_energy_kwh | 5.12 |
| nominal_voltage_v | 51.2 |
| note | SAFETY-CRITICAL ASYMMETRY: the charge and discharge current limits are NOT equal. 'Max Charging Current' = 75 A but 'Max Discharging Current' = 100 A. Sizing a charger to the 100 A discharge figure would over-current the battery by 33%. Additionally the 200 A figure is a 2-minute peak DISCHARGE current only and must never be applied to charging. |
| operating_voltage_max_v | 57.6 |
| operating_voltage_min_v | 44.8 |
| parallel_supported | yes |
| peak_charge_current_a | UNKNOWN (only a peak DISCHARGING current is published) |
| peak_discharge_current_a | 200 (2 min) |
| peak_power_kw | 5.12 (the manual prints 'Peak Power' = '5.12 kW', i.e. EQUAL to nominal power, even though it separately allows a 200 A / 2 min peak DISCHARGING CURRENT which would be ~10.24 kW. Recorded verbatim; see raw_discovered.) |
| round_trip_efficiency_pct | UNKNOWN |
| series_supported | no (low-voltage parallel-only architecture) |
| system_energy_max_kwh | CONFLICT - see data_conflicts (50 modules x 5.12 kWh = 256 kWh per the official page and manual; ITS Technologies UK states expandable to 25.6 kWh = 5 modules) |
| system_energy_min_kwh | 5.12 |
| usable_energy_kwh | UNKNOWN (no usable-energy figure and no DoD percentage are printed in the user manual or on the official page) |
Physical / mechanical
| cooling_method | UNKNOWN as a documented label. ITS Technologies UK describes 'heating and cooling functions', implying active thermal management, but no cooling method is named in the manual. |
| depth_mm | 165 |
| height_mm | CONFLICT - see data_conflicts (user manual 640 mm, official product page 660 mm) |
| installation_notes | Wall-mounted or floor-standing per the ITS Technologies UK distributor page. |
| ip_rating | CONFLICT - see data_conflicts (official page and manual IP66, ITS Technologies UK IP65) |
| mounting_type | ['wall', 'floor'] |
| rack_units | N/A (wall/floor enclosure) |
| weight_kg | 54.4 |
| width_mm | 450 |
Installation
| indoor_outdoor | indoor and outdoor (IP66) |
| installation_notes | UNKNOWN |
| mounting_orientation | wall-mounted or floor-standing |
Environment
| charge_temperature_range_c | 0C to +55C (or -20C to +55C with the heating function) |
| discharge_temperature_range_c | -20C to +65C |
| indoor_outdoor | indoor and outdoor (IP66) |
| max_altitude_m | 4000 |
| note | The charge and discharge windows DIFFER substantially: charging 0..+55C (extended to -20C only with the heating function active), discharging -20..+65C. The +65C discharge ceiling is 10C higher than the charge ceiling. |
| operating_humidity | 5% ~ 85%RH |
| operating_temperature_max_c | 65 |
| operating_temperature_min_c | -20 |
| storage_temperature_max_c | 35 |
| storage_temperature_min_c | -10 |
Interfaces & connectors
| bluetooth | UNKNOWN |
| can | yes - CAN IN / CAN OUT ports; EXT CANH/CANL and INT CANH/CANL pins |
| communication_ports | CAN IN / CAN OUT (RJ45-style, pin definitions in Tables 3-2 and 3-3), RS485, Wi-Fi |
| dry_contact | UNKNOWN |
| ethernet | UNKNOWN |
| modbus_rtu | UNKNOWN |
| modbus_tcp | UNKNOWN |
| protocol_notes | A 4-position DIP switch on the master module selects the inverter protocol group. Factory default is '0000'. CAN baud rate 500K (switch OFF) or 250K (switch ON); RS485 9600 or 115200 bps. Full DIP mapping is in Table 3-4 and is reproduced in documented_relationships. |
| rs232 | UNKNOWN |
| rs485 | yes - 485B / 485A pins (marked 'reserve' on the CAN IN connector) |
| usb | UNKNOWN |
| wifi | yes ('Wifi' listed among communication ports) |
Protection
| fire_suppression | aerosol fire suppression system reported by ITS Technologies UK (distributor-verified); a fire-extinguisher component appears among the official product-page image assets |
| heating | yes - heating function extends the charge window down to -20C (manual) |
| ip_rating | IP66 (per Dyness); IP65 per ITS Technologies UK - see data_conflicts |
| over_current | UNKNOWN |
| over_temperature | charge window 0..+55C (-20C with heating); discharge window -20..+65C |
| over_voltage | UNKNOWN |
| short_circuit | UNKNOWN |
| under_voltage | UNKNOWN |
Certifications
| note | No UN38.3 / IEC 62619 identifier is printed in the fetched manual. The dyness.com download centre advertises certification documents by category (CE, CEI-021, EN/IEC 62619, UL 1973, MSDS, UN38.3, TUV) across its LV range, but those documents are robots-blocked and were not fetched, so nothing is asserted for this model. |
| safety_certifications | UNKNOWN |
| standards | UNKNOWN as a specific standards list. The manual prints only 'European ROHS, certified SGS'. |
| transport_certifications | UNKNOWN |
Warranty & service
| conditions | UNKNOWN |
| confidence | distributor-verified |
| note | Warranty length is distributor-sourced only. Note the shelf/design life '10 years' and the warranty '10 years' are different claims that happen to share a number. |
| summary | '10 Year Product Warranty' per Solar Proof (AU); the official page prints 'Cycle Life' = '>=8000 cycles/10 years' but no warranty row. |
| years | 10 |
Documents
datasheet
{# Located but never retrieved: listed, but deliberately not linked, and it
backs no stored value. #}
PowerDepot G2 Datasheet EN 2025-06-24 — located, not retrieved
rev UNKNOWN
distributor-page
Dyness PowerDepot G2 - distributor product page (Solar Proof, Australia)
rev UNKNOWN
distributor-page
Dyness PowerDepot G2 5.12kWh IP65 LV LFP battery - distributor product page (ITS Technologies, UK)
rev UNKNOWN
product-page
PowerDepot G2 - Low voltage residential energy storage batteries (official product page)
rev UNKNOWN
Recorded conflicts
electrical.system_energy_max_kwh / max_parallel_units Review required
50 modules (256 kWh) — Dyness official product page 'Maximum Parallel Modules' = '50' and user manual 'up to 50 PowerDepot G2'
5 modules (25.6 kWh) — ITS Technologies UK distributor page, 'Scalability: Expandable up to 25.6 kWh'
physical.ip_rating Review required
IP66 — Dyness official product page 'Protection Level' = 'IP66' AND user manual Table 2-1 'IP Level' = 'IP66'
IP65 — ITS Technologies UK distributor page, 'IP Rating: IP65'
physical.height_mm Review required
640 mm — Dyness PowerDepot G2 User Manual EN 251029, Table 2-1, 'Dimensions' = '450x640x165' mm
660 mm — Dyness official product page, 'Dimension [WxDxH]' = '450x165x660mm'
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| CAN baud rate | 500K (OFF) or 250K (ON) |
| Compliance (manual) | European ROHS, certified SGS |
| Factory default DIP mode | 0000 |
| Peak Power (Table 2-2) | 5.12 kW |
| Product Code (ITS Technologies UK) | DY-POWERDEPOTH5B-G2 |
| RS485 rate | 9600 or 115200 |
| Shelf Life (Solar Proof AU) | 10 years |
| Temperature Features (ITS Technologies UK) | Heating and cooling functions |
| documented_relationship:inverter_battery | {"to_manufacturer": "Voltronic/INFINI", "to_model": "Axpert-king / VMIII / MAX, Infinisolar", "relationship_type": "inverter_battery", "match_level": "series", "communication_protocol": "CAN or RS485 (not disambiguated per brand in Table 3-4)", "required_settings": "DIP switch setting 3 = #2 ON (0100) on the master module. CAN baud 500K (switch OFF) or 250K (switch ON); RS485 9600 or 115200 bps.", "source": "Dyness PowerDepot G2 User Manual EN 251029, Table 3-4 'DIP switch description'", "source_url": "https://samonolithportalprodcdn.blob.core.windows.net/assets/general_product_documents/97577a49c976c6ea8981a86cbd74718ed3c1d447_PowerDepot_G2_User_Manual_EN_251029.pdf", "source_page": "Table 3-4", "confidence": "manufacturer-documented", "notes": "Read from a mirror of the genuine Dyness manual on the Samonolith installer-portal CDN, not from dyness.com (whose PDFs are robots-blocked). Se |