ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseBatteries

Dyness PowerDepot G2

Manufacturer documented Global verified Sept. 2, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category batteries
ean UNKNOWN
generation G2
hardware_revision UNKNOWN
legacy_name Likely successor to the PowerDepot H5B - the ITS Technologies UK product code is 'DY-POWERDEPOTH5B-G2', and the Dyness LV-Link A compatibility list names 'PowerDepot H5B'. Not confirmed by a Dyness-published statement.
manufacturer Dyness
market_version EN/global; separate datasheet revisions exist for RO, ES, MEA and DE/AT/CH markets
model PowerDepot G2
mpn DY-POWERDEPOTH5B-G2 (ITS Technologies UK product code; not confirmed against a Dyness-published part list)
product_family Dyness PowerDepot
product_status active
product_status_evidence Listed on the dyness.com residential Low Voltage ESS index with a live official product page (fetched 2026-09-02); current user manual revision EN 251029 dated 2025-10-29.
region Global
release_year UNKNOWN (earliest located official datasheet revision is dated 2025-03-31; page image assets dated 2025-04-25; no release year printed)
sku UNKNOWN
subcategory low-voltage 48V-class wall/floor mounted battery module
variant_note One variant published: 'PowerDepot G2 51.2V/100Ah' (5.12 kWh).

Electrical

cell_chemistry lithium iron phosphate (LiFePO4)
cell_type UNKNOWN
continuous_charge_current_a 75 (the manual publishes a single 'Max Charging Current' with no separate continuous rating)
continuous_discharge_current_a 100 (the manual publishes a single 'Max Discharging Current' with no separate continuous rating)
continuous_power_kw 5.12
cycle_life >=8000 cycles / 10 years
depth_of_discharge_pct UNKNOWN (not printed)
max_charge_current_a 75
max_charge_power_kw 3.84 (inferred: 75 A max charging current x 51.2 V nominal; NOT printed. Do not use the 5.12 kW 'Nominal Power' figure for charging - that corresponds to the 100 A DISCHARGE rating)
max_discharge_current_a 100
max_discharge_power_kw 5.12
max_parallel_units 50
max_series_units N/A (LV parallel stack)
nominal_capacity_ah 100
nominal_energy_kwh 5.12
nominal_voltage_v 51.2
note SAFETY-CRITICAL ASYMMETRY: the charge and discharge current limits are NOT equal. 'Max Charging Current' = 75 A but 'Max Discharging Current' = 100 A. Sizing a charger to the 100 A discharge figure would over-current the battery by 33%. Additionally the 200 A figure is a 2-minute peak DISCHARGE current only and must never be applied to charging.
operating_voltage_max_v 57.6
operating_voltage_min_v 44.8
parallel_supported yes
peak_charge_current_a UNKNOWN (only a peak DISCHARGING current is published)
peak_discharge_current_a 200 (2 min)
peak_power_kw 5.12 (the manual prints 'Peak Power' = '5.12 kW', i.e. EQUAL to nominal power, even though it separately allows a 200 A / 2 min peak DISCHARGING CURRENT which would be ~10.24 kW. Recorded verbatim; see raw_discovered.)
round_trip_efficiency_pct UNKNOWN
series_supported no (low-voltage parallel-only architecture)
system_energy_max_kwh CONFLICT - see data_conflicts (50 modules x 5.12 kWh = 256 kWh per the official page and manual; ITS Technologies UK states expandable to 25.6 kWh = 5 modules)
system_energy_min_kwh 5.12
usable_energy_kwh UNKNOWN (no usable-energy figure and no DoD percentage are printed in the user manual or on the official page)

Physical / mechanical

cooling_method UNKNOWN as a documented label. ITS Technologies UK describes 'heating and cooling functions', implying active thermal management, but no cooling method is named in the manual.
depth_mm 165
height_mm CONFLICT - see data_conflicts (user manual 640 mm, official product page 660 mm)
installation_notes Wall-mounted or floor-standing per the ITS Technologies UK distributor page.
ip_rating CONFLICT - see data_conflicts (official page and manual IP66, ITS Technologies UK IP65)
mounting_type ['wall', 'floor']
rack_units N/A (wall/floor enclosure)
weight_kg 54.4
width_mm 450

Installation

indoor_outdoor indoor and outdoor (IP66)
installation_notes UNKNOWN
mounting_orientation wall-mounted or floor-standing

Environment

charge_temperature_range_c 0C to +55C (or -20C to +55C with the heating function)
discharge_temperature_range_c -20C to +65C
indoor_outdoor indoor and outdoor (IP66)
max_altitude_m 4000
note The charge and discharge windows DIFFER substantially: charging 0..+55C (extended to -20C only with the heating function active), discharging -20..+65C. The +65C discharge ceiling is 10C higher than the charge ceiling.
operating_humidity 5% ~ 85%RH
operating_temperature_max_c 65
operating_temperature_min_c -20
storage_temperature_max_c 35
storage_temperature_min_c -10

Interfaces & connectors

bluetooth UNKNOWN
can yes - CAN IN / CAN OUT ports; EXT CANH/CANL and INT CANH/CANL pins
communication_ports CAN IN / CAN OUT (RJ45-style, pin definitions in Tables 3-2 and 3-3), RS485, Wi-Fi
dry_contact UNKNOWN
ethernet UNKNOWN
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
protocol_notes A 4-position DIP switch on the master module selects the inverter protocol group. Factory default is '0000'. CAN baud rate 500K (switch OFF) or 250K (switch ON); RS485 9600 or 115200 bps. Full DIP mapping is in Table 3-4 and is reproduced in documented_relationships.
rs232 UNKNOWN
rs485 yes - 485B / 485A pins (marked 'reserve' on the CAN IN connector)
usb UNKNOWN
wifi yes ('Wifi' listed among communication ports)

Protection

fire_suppression aerosol fire suppression system reported by ITS Technologies UK (distributor-verified); a fire-extinguisher component appears among the official product-page image assets
heating yes - heating function extends the charge window down to -20C (manual)
ip_rating IP66 (per Dyness); IP65 per ITS Technologies UK - see data_conflicts
over_current UNKNOWN
over_temperature charge window 0..+55C (-20C with heating); discharge window -20..+65C
over_voltage UNKNOWN
short_circuit UNKNOWN
under_voltage UNKNOWN

Certifications

note No UN38.3 / IEC 62619 identifier is printed in the fetched manual. The dyness.com download centre advertises certification documents by category (CE, CEI-021, EN/IEC 62619, UL 1973, MSDS, UN38.3, TUV) across its LV range, but those documents are robots-blocked and were not fetched, so nothing is asserted for this model.
safety_certifications UNKNOWN
standards UNKNOWN as a specific standards list. The manual prints only 'European ROHS, certified SGS'.
transport_certifications UNKNOWN

Warranty & service

conditions UNKNOWN
confidence distributor-verified
note Warranty length is distributor-sourced only. Note the shelf/design life '10 years' and the warranty '10 years' are different claims that happen to share a number.
summary '10 Year Product Warranty' per Solar Proof (AU); the official page prints 'Cycle Life' = '>=8000 cycles/10 years' but no warranty row.
years 10

Documents

datasheet {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} PowerDepot G2 Datasheet EN 2025-06-24 — located, not retrieved rev UNKNOWN
distributor-page Dyness PowerDepot G2 - distributor product page (Solar Proof, Australia) rev UNKNOWN
distributor-page Dyness PowerDepot G2 5.12kWh IP65 LV LFP battery - distributor product page (ITS Technologies, UK) rev UNKNOWN
product-page PowerDepot G2 - Low voltage residential energy storage batteries (official product page) rev UNKNOWN
user-manual USER MANUAL PowerDepot G2 - 51.2V/100Ah Battery Module (genuine Dyness manual, mirrored on the Samonolith installer portal CDN) rev EN 251029

Recorded conflicts

electrical.system_energy_max_kwh / max_parallel_units Review required
50 modules (256 kWh) — Dyness official product page 'Maximum Parallel Modules' = '50' and user manual 'up to 50 PowerDepot G2'
5 modules (25.6 kWh) — ITS Technologies UK distributor page, 'Scalability: Expandable up to 25.6 kWh'
physical.ip_rating Review required
IP66 — Dyness official product page 'Protection Level' = 'IP66' AND user manual Table 2-1 'IP Level' = 'IP66'
IP65 — ITS Technologies UK distributor page, 'IP Rating: IP65'
physical.height_mm Review required
640 mm — Dyness PowerDepot G2 User Manual EN 251029, Table 2-1, 'Dimensions' = '450x640x165' mm
660 mm — Dyness official product page, 'Dimension [WxDxH]' = '450x165x660mm'

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

CAN baud rate500K (OFF) or 250K (ON)
Compliance (manual)European ROHS, certified SGS
Factory default DIP mode0000
Peak Power (Table 2-2)5.12 kW
Product Code (ITS Technologies UK)DY-POWERDEPOTH5B-G2
RS485 rate9600 or 115200
Shelf Life (Solar Proof AU)10 years
Temperature Features (ITS Technologies UK)Heating and cooling functions
documented_relationship:inverter_battery{"to_manufacturer": "Voltronic/INFINI", "to_model": "Axpert-king / VMIII / MAX, Infinisolar", "relationship_type": "inverter_battery", "match_level": "series", "communication_protocol": "CAN or RS485 (not disambiguated per brand in Table 3-4)", "required_settings": "DIP switch setting 3 = #2 ON (0100) on the master module. CAN baud 500K (switch OFF) or 250K (switch ON); RS485 9600 or 115200 bps.", "source": "Dyness PowerDepot G2 User Manual EN 251029, Table 3-4 'DIP switch description'", "source_url": "https://samonolithportalprodcdn.blob.core.windows.net/assets/general_product_documents/97577a49c976c6ea8981a86cbd74718ed3c1d447_PowerDepot_G2_User_Manual_EN_251029.pdf", "source_page": "Table 3-4", "confidence": "manufacturer-documented", "notes": "Read from a mirror of the genuine Dyness manual on the Samonolith installer-portal CDN, not from dyness.com (whose PDFs are robots-blocked). Se