Identity
| battery_module_model | LX F3.2-20 (64 V, 3.2 kWh per module) |
| category | batteries |
| ean | UNKNOWN |
| generation | G2 |
| manufacturer | GoodWe |
| market_version | UNKNOWN |
| model | Lynx Home F G2 Series |
| mpn | UNKNOWN |
| product_family | Lynx Home F Series G2 (HV) |
| product_revision | UNKNOWN |
| product_status | active |
| region | EU / global EN documentation |
| release_year | UNKNOWN |
| sku | LX F6.4-H-20, LX F9.6-H-20, LX F12.8-H-20, LX F16.0-H-20, LX F19.2-H-20, LX F22.4-H-20, LX F25.6-H-20, LX F28.8-H-20 (manual p.01 'Applicable Models') |
Electrical
| chemistry | LFP (LiFePO4) |
| communication_can | True |
| communication_rs485 | True |
| firmware_requirements | Inverter-side per GoodWe Battery Compatibility Overview V029.1: ET/BT 'ARM25 and DSP09 versions and above'; EH/BH 'ARM25 and DSP version 07 and above'; EHB 'ARM25 and DSP version 03 and above' |
| max_continuous_charge_current_a | 35 |
| max_continuous_discharge_current_a | 35 |
| max_continuous_power_kw | 4.48-20.16 (scales with capacity) |
| max_parallel_units |
8
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.8 / p.20, 'A max of eight battery systems can be parallel connected in one energy storage system'
|
| max_series_units | 9 |
| min_series_units_hv | 2 |
| nominal_energy_kwh | 6.4-28.8 (modular family) |
| nominal_voltage_v | 128-576 (varies with 2-9 modules) |
| officially_supported_inverter_brands | ['GoodWe'] |
| officially_supported_inverter_models |
['GoodWe BH series', 'GoodWe EH series', 'GoodWe BT series', 'GoodWe ET series (smallest 6.4kWh tower has insufficient start-up voltage for 15-30kW ET inverters)']
GoodWe Battery Compatibility Overview — Battery Compatibility Overview V029.1, Lynx Home F G2 rows + note 'Lynx Home F G2 Series LX F6.4-H-20 only supports GW12KL-ET and GW18KL-ET models in the ET (15-30kW) series'
|
| peak_current_a | UNKNOWN |
| supported_inverter_protocols | ['CAN'] |
| usable_energy_kwh | 6.4-28.8 (family range) |
| voltage_class | HV |
| voltage_range_v | 114.8-649.8 |
Physical / mechanical
| bracket_dimensions_mm | UNKNOWN |
| cable_entry_positions | UNKNOWN |
| depth_mm |
380
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.35-36 technical data table
|
| enclosure_material | UNKNOWN |
| height_mm | 559 (LX F6.4-H-20) / 715 (F9.6) / 871 (F12.8) / 1027 (F16.0) / 1183 (F19.2) / 1339 (F22.4) / 1495 (F25.6) / 1651 (F28.8) — per-model, manual p.35-36 |
| housing_color | UNKNOWN |
| mounting_bolt_size | expansion bolts ×8 supplied (manual p.11 packing list) |
| mounting_hole_diameter_mm | UNKNOWN |
| mounting_hole_spacing_mm | UNKNOWN (manual p.17 gives locking-bracket spacing dimension 'D: 80mm' only) |
| mounting_type | ['floor'] |
| rack_units | UNKNOWN |
| screw_sizes | M5×12 screws ×8-13 and M6 screws ×0-2 depending on configuration (manual p.11 packing list) |
| shipping_weight_kg | UNKNOWN |
| terminal_locations | UNKNOWN |
| torque_specs | locking bracket screws M5×12: 4 N·m (manual p.17); DC power terminal M6: 6 N·m (manual p.22) |
| weight_kg | 86 (LX F6.4-H-20) / 120 (F9.6) / 154 (F12.8) / 188 (F16.0) / 222 (F19.2) / 256 (F22.4) / 290 (F25.6) / 324 (F28.8) — per-model, manual p.35-36 |
| width_mm |
600
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.35-36 technical data table, '600×559×380' ... '600×1651×380'
|
Installation
| cable_routing_note | 'Place the cables at least 30mm away from the heating components'; 'place cables of different types at least 30mm apart' (manual p.3) |
| clearance_bottom_mm | UNKNOWN |
| clearance_front_mm | UNKNOWN |
| clearance_left_mm | UNKNOWN |
| clearance_right_mm | UNKNOWN |
| clearance_top_mm | UNKNOWN |
| indoor_outdoor | indoor or outdoor ('The equipment with a high ingress protection rating can be installed indoors or outdoors', manual p.14) |
| max_installation_altitude_m | 3000 |
| mounting_orientation | vertical, floor-standing, secured to wall with locking brackets |
| orientation_allowed | ['vertical (upright, floor-standing)'] |
| orientation_forbidden | ['tilted', 'upside down'] |
| surface_requirements | 'Put the battery system near the wall and install the locking brackets to prevent the battery from falling down' (manual p.15) |
| ventilation_requirements | 'The place to install the equipment shall be well-ventilated for heat dissipation and large enough for operations' (manual p.14) |
Environment
| cooling_method | UNKNOWN (no active cooling documented; ventilation-dependent) |
| corrosion_class | UNKNOWN |
| ik_rating | UNKNOWN |
| ip_rating |
IP55 (Outdoor / Indoor)
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.35-36, 'IP55'
|
| max_altitude_m | 3000 |
| nema_rating | UNKNOWN |
| noise_level_db | UNKNOWN |
| operating_temperature_c |
Charge: 0 ~ +50; Discharge: -20 ~ +50
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.35-36 'Charge: 0~+50; Discharge: -20~+50'; also p.14 section 5.1
|
| pollution_degree | UNKNOWN |
| relative_humidity | 0 ~ 95% (datasheet); storage 0~95%RH no condensation (manual p.12) |
| salt_mist_resistance | UNKNOWN |
| storage_temperature_c |
-20~0 °C, <=1 month; 0~35 °C, <=6 months; 35~45 °C, <=1 month (manual p.13)
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.13 storage conditions
|
Interfaces & connectors
| bluetooth | UNKNOWN |
| can | CAN (COM1/COM2 pins 4-5 CAN_1H/CAN_1L — inverter and parallel communication, manual p.23) |
| digital_inputs | COM1/COM2 pins 6-7 DI7H- / DI7H+ cluster signal detection (manual p.23) |
| ethernet | UNKNOWN |
| modbus_rtu | UNKNOWN |
| modbus_tcp | UNKNOWN |
| protocol_notes | Communication with inverter: CAN (datasheet). COM2 of the PCU ships with terminal resistors installed (manual p.20). COM1/COM2 pin 8: PWM parallel signal on COM2. |
| rs485 | RS485 (COM1/COM2 pins 1-2 RS485A/RS485B — external communication, manual p.23) |
| usb | UNKNOWN |
| wifi | UNKNOWN |
Certifications
| emc | ['CE', 'RCM'] |
| eu_directives | Directive 2014/30/EU (EMC); Directive 2014/35/EU (LVD); Battery Directive 2006/66/EC and amending Directive 2013/56/EU; WEEE 2012/19/EU; REACH (EC) No 1907/2006 (manual p.4) |
| other | ['UN38.3'] |
| regional | ['CE', 'CEC'] |
| safety |
['IEC62619', 'IEC62040-1', 'IEC63056', 'VDE2510']
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.35-36 certification rows
|
Warranty & service
| cycle_life |
>4000 cycles at 80% end-of-life capacity, 0.7C/1C test conditions (datasheet/manual p.35-36)
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual — manual p.35-36 footnote, '>4000' cycles @ 80% EOL, 0.7C/1C
|
| design_life_years | UNKNOWN |
| field_replaceable_parts | UNKNOWN |
| standard_years | UNKNOWN (manual refers to https://en.goodwe.com/warranty) |
Packaging & logistics
| transport_restrictions | UN38.3 (transport test certification listed in manual p.35-36) |
Documents
compatibility-list
GoodWe Battery Compatibility Overview
rev GoodWe Battery Compatibility Overview-20260715-EN-V029.1
user-manual
Rechargeable Li-ion Battery System Lynx Home F Series G2 User Manual
rev V1.7-2025-05-14
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| Battery module | LX F3.2-20: 64V 3.2kWh |
| Cable spacing from heating components | at least 30mm |
| DOD (test condition) | 100% DOD |
| Locking bracket dimension D | 80mm |
| Round Trip Efficiency | 94% |
| Terminal resistor | COM2 of the PCU has installed terminal resistors when leaving factory |