ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseBatteries

Sungrow SBR096

Official manufacturer EU / APAC / AU / global (IEC datasheet) verified Sept. 3, 2026

Identity

category batteries
generation SBR (first-generation stacked HV residential battery; superseded in EU SHT pairings by the SBH series)
hardware_revision V114 / V12 / V13 module versions are referenced in Compatibility List V4.3; the datasheet itself carries no revision suffix
legacy_name UNKNOWN
manufacturer Sungrow
market_version IEC / EN datasheet V5 (2024-09-07)
model SBR096
product_family SBR
product_status active
product_status_evidence Listed with full specifications in Sungrow Compatibility List PUBLIC 2026 V4.3 dated 01.06.2026 and in datasheet V5 (2024-09-07)
region EU / APAC / AU / global (IEC datasheet)
release_year UNKNOWN
sku UNKNOWN
subcategory residential high-voltage stacked battery system
variant_note One of seven fixed stack configurations of the same 3.2 kWh module; differs from siblings only by module count.

Electrical

architecture HV (high-voltage DC series stack)
cell_chemistry LiFePO4 Prismatic Cell
cycle_life UNKNOWN
expansion_rules User manual Ver22: '2 to 8 individual battery modules connected in series' and 'Up to 4 units in parallel (need extra Combiner box)'. Compatibility List V4.3 instead caps towers per inverter: 'max. 1 battery tower' for SH3.0-6.0RS and SH5.0-10RT, 'max. 2 battery towers (used with Y-connector)' for SH5.0-25T. See data_conflicts.
firmware_requirements UNKNOWN
max_charge_current_a 30
max_charge_power_kw UNKNOWN
max_discharge_current_a 30
max_discharge_power_kw UNKNOWN
max_parallel_stacks UNKNOWN
mixed_generation_restrictions Compatibility List V4.3 SBR module cross-version matrix: V114+V114 Yes, V114+V12 No, V114+V13 Yes, V12+V12 Yes, V12+V13 Yes, V13+V13 Yes. Also 'Not compatible with SMR032 battery modules' for the SMR025-based item.
module_energy_kwh 3.2
modules_installed 3
modules_max 8
modules_min 2
nominal_energy_kwh 9.6
nominal_voltage_v 192
operating_voltage_max_v 219
operating_voltage_min_v 162
power_note Datasheet prints only a continuous current; no kW figure is printed. Not derived.
rated_power_kw UNKNOWN
round_trip_efficiency_pct UNKNOWN
short_circuit_current_a 3500
usable_dod_note 'Max. 100% DOD (settable)'
usable_dod_pct 100
usable_energy_kwh 9.6
usable_energy_note Datasheet row label is 'Energy (useable)'; DOD row is 'Max. 100% DOD (settable)', so nominal and usable coincide at 100% DOD.

Physical / mechanical

cooling Natural convection
depth_mm 330
dimensions_note Datasheet row 'Dimensions (W*H*D)'
display SOC & Status indicators
height_mm 545
ip_rating IP55
module_weight_kg 33
mounting Floor stand
weight_kg 114
width_mm 625

Installation

indoor_outdoor Indoor/Outdoor
mounting_method Floor stand
supported_installation_topology UNKNOWN

Environment

charge_temperature_c 0 to 50
discharge_temperature_c -20 to 50
humidity 0%-95% non-condensing
max_altitude_m 4000
noise UNKNOWN
storage_note User manual Ver22: 'Recharge the battery to 30% SOC every 6 months of storage'; preferred storage <=6 months, 'maximum storage time...12 months'.
storage_temperature_c -10 to 35
temperature_note Charge and discharge windows DIFFER; datasheet rows read 'Charge: 0 C - 50 C' and 'Discharge: -20 C - 50 C'.

Interfaces & connectors

can True
communication_protocol CAN (to Sungrow hybrid inverter)
ethernet UNKNOWN
ports 'COMM' terminal; two connector styles documented in user manual Ver22: 'Circular Communication Connector' and 'Square-shaped Communication Connector'; RJ45 plugs, CAN1_H/CAN1_L signal cable
rs485 UNKNOWN

Protection

dc_breaker True
over_current_protection True
over_under_temperature_protection True
over_under_voltage_protection True

Certifications

listed ['CE', 'CEC', 'IEC 62619', 'IEC 62040', 'UN38.3', 'VDE 2510-50', 'IEC 62477', 'IEC 63056', 'IEC 61000', 'UKCA']

Warranty & service

note User manual Ver22: 'Please consult the local SUNGROW service team'. No warranty term printed on datasheet V5.
years UNKNOWN

Documents

compatibility-list Compatibility List PUBLIC 2026 | Version 4.3 rev V4.3
datasheet SBR064/096/128/160/192/224/256 High Voltage LFP Battery Datasheet rev V5
user-manual SBR064/096/128/160/192/224/256 High Voltage LFP Battery User Manual rev Ver22

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

compatibility.match_level_policyPairings below are transcribed from Sungrow's own Compatibility List V4.3 and the SBR user manual. Anything not named there is NOT_LISTED, never INCOMPATIBLE. No pairing was inferred from voltage.
manufacturer_legal_entity_as_printedSungrow Power Supply Co., Ltd.
observation:electrical.max_parallel_stacks{"values": [], "note": "NOT RESOLVED - recorded as UNKNOWN in electrical.max_parallel_stacks. The two figures may be scoped differently (battery-side electrical maximum vs per-inverter approved maximum), but Sungrow does not say so, so no silent pick was made."}

Build a system with this product