Knowledge Base ›
Batteries
Victron Energy Lithium NG battery 25,6V/100Ah (LFP25.6/100)
Official manufacturer
global
verified Sept. 2, 2026
Identity
| category |
batteries
|
| manufacturer |
Victron Energy B.V.
|
| model |
Lithium NG battery 25,6V/100Ah (LFP25.6/100)
|
| product_family |
Lithium NG Batteries
|
| product_status |
active
|
| region |
global
|
| sku |
UNKNOWN
|
Electrical
| charge_c_rate |
1C
|
| charge_voltage_v |
Between 28 V and 28,8 V
|
| chemistry |
LiFePO4 (Lithium Iron Phosphate)
|
| cycle_life |
{'at_80_pct_dod': 2500, 'at_70_pct_dod': 3000, 'at_50_pct_dod': 5000}
|
| discharge_c_rate |
1C
|
| end_of_discharge_voltage_v |
22.4
|
| float_voltage_v |
27.0
|
| max_continuous_charge_current_a |
100
|
| max_continuous_discharge_current_a |
100
|
| max_pulse_discharge_current_a |
200
|
| nominal_capacity_ah |
100
|
| nominal_energy_kwh |
2.56
|
| nominal_energy_wh |
2560
|
| nominal_voltage_v |
25.6
|
| pulse_condition |
2C, 10 s pulse
|
Physical / mechanical
| bms_connection |
Male + female cable with M8 circular connector
|
| depth_mm |
160
|
| dimensions_h_w_d_mm |
235 x 341 x 160
|
| height_mm |
235
|
| mounting |
Bracket and strap mounting options
|
| power_connection_terminals |
M8 (threaded inserts and bolts)
|
| terminal_torque |
UNKNOWN
|
| weight_kg |
19
|
| width_mm |
341
|
Installation
| bms_requirement_note |
'Lynx Smart BMS NG 500 A / 1000 A, must be purchased separately'
|
| external_bms_required |
True
|
| max_batteries_12v_24v_systems |
50
|
| max_batteries_48v_systems |
25
|
| max_single_bank_kwh |
385
|
| series_parallel |
Series, parallel or series/parallel; max 50 batteries in 12 V/24 V systems, 25 in 48 V systems
|
Environment
| humidity_non_condensing |
Max. 95 %
|
| operating_temperature |
Discharge: -20 °C to +50 °C | Charge: +5 °C to +50 °C
|
| protection_class_ip |
IP65
|
| storage_temperature |
-45 °C to +70 °C
|
Interfaces & connectors
| bms_port |
M8 circular connector (male + female, daisy-chainable)
|
| cell_data_readout |
Added read-out of cell voltages and temperatures
|
Protection
| protection_delegated_to |
Lynx Smart BMS NG (external)
|
Certifications
| standards |
['IEC62619', 'UL1973', 'UL9540A', 'EN 61000-6-2', 'EN 61000-6-3', 'ECE R10-6']
|
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| Max Pulse Discharge | 200 A (2C, 10s pulse) |