Identity

brand Growatt
category inverters
ean UNKNOWN
generation XH
manufacturer Growatt (Shenzhen Growatt New Energy Technology Co., Ltd.)
model MOD 10KTL3-XH
mpn UNKNOWN
product_family MOD 3-10KTL3-XH (MOD 3000-10000TL3-XH); MOD 3000-10000TL3-XH(BP) is the backup-capable sibling
product_status active
region EU/global
sku UNKNOWN

Electrical

ac_coupling_support UNKNOWN
backup_eps_output_support UNKNOWN for standard XH (manual documents backup for BP series with APX HV battery)
battery_support True
battery_type Growatt ARK XH HV Battery System (7.68-25.6 kWh); BP variant: APX HV Battery (5-60 kWh)
battery_voltage_class HV
battery_voltage_max_v 950
battery_voltage_min_v 600
communication_can UNKNOWN
communication_ethernet optional (LAN module)
communication_rs485 True
communication_wifi optional (WiFi/GPRS/4G/RF modules)
ct_support true (TPM-CT-G 100A; SDM630MCT 40mA CT-type meter)
generator_input_support UNKNOWN
grid_certifications ['CE', 'VDE 0126', 'EN 50549', 'C10/C11', 'VFR 2019', 'G98/G99', 'AS 4777', '(Greece grid code; full list in datasheet)']
grid_export_control true (export limitation via documented meters/CT per manual)
grid_frequency_hz 50/60 (45-55Hz/55-65Hz)
grid_voltage_v 220/380, 230/400 (340-440V)
home_assistant_integration UNKNOWN
max_ac_power_kw 11
max_battery_charge_current_a 18.5 ('Max. operating current 18.5A' standard XH; 25A for BP series per manual)
max_battery_charge_power_kw 10
max_battery_discharge_current_a 18.5 (standard XH; 25A BP series)
max_dc_voltage_v 1100
max_input_current_per_mppt_a 16
max_parallel_units UNKNOWN
max_pv_input_power_w 20000
max_short_circuit_current_per_mppt_a 20
modbus_rtu true ('RS485 (Modbus-RTU protocol)' per manual)
modbus_tcp UNKNOWN
mppt_max_voltage_v 1000
mppt_min_voltage_v 140
num_mppt 2
officially_supported_battery_brands ['Growatt (ARK XH HV Battery System; APX HV Battery for BP variant)']
parallel_support UNKNOWN
phase_type three-phase
pv_inputs_per_mppt 1
rated_ac_power_kw 10
region_variant EU/Global
smart_meter_support true (manual names Growatt TPM-CT-G 100A, Eastron SDM630-Modbus V3, Eastron SDM630MCT 40mA, CHINT DTSU666 variants)
sources [{'url': 'https://www.pvo-int.com/wp-content/uploads/2022/01/MOD-3-10KTL3-XH-Datasheet.pdf', 'title': 'MOD 3-10KTL3-XH datasheet (distributor mirror)', 'doc_type': 'datasheet', 'publisher': 'Growatt via PVO International', 'doc_date': '2022-01 (upload path)', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'manufacturer-documented'}, {'url': 'https://donauer.s3.eu-west-1.amazonaws.com/files/growattmod3-10ktl3-xhusermanualen20240575df997daa.pdf', 'title': 'MOD 3-10KTL3-XH Installation & Operation Manual (Version 00, copyright 2023)', 'doc_type': 'manual', 'publisher': 'Growatt via Donauer', 'revision': 'V00, 2023/2024', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'manufacturer-documented'}, {'url': 'https://solarmagazine.nl/u/webshop/datasheetgrowattmod-3-10ktl3-xh.pdf', 'title': 'MOD 3-10KTL3-XH datasheet (distributor mirror, older revision)', 'doc_type': 'datasheet', 'publisher': 'Growatt via Solar Magazine NL', 'language': 'en', 'accessed': '2026-09-01', 'confidence': 'manufacturer-documented'}]
startup_voltage_v 160
sunspec_support UNKNOWN
topology grid-tie (battery-ready hybrid via XH battery port; standard XH pairs with ARK XH HV battery, XH-BP variant with APX HV battery adds backup)

Physical / mechanical

cable_gland_sizes UNKNOWN
depth_mm 178
height_mm 387
mounting_bolt_size M6 expansion bolts; drilled hole Φ=8 mm, depth 55 mm (manual p.22)
mounting_hole_diameter_mm 8
mounting_hole_spacing_mm 154 (bracket hole spacing, manual p.22)
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.22, bracket hole spacing '154 mm', drill 'Φ=8 mm', depth '55mm'
mounting_type ['wall']
screw_sizes M6 (bracket to wall), M4 (inverter to bracket)
shipping_weight_kg UNKNOWN
torque_specs wall bracket 5 N·m (M6, manual p.22); inverter-to-bracket securing screw 5 N·m (M4, manual p.23)
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.22 '5 N·m M6'; p.23 '5 N·m M4'
weight_kg 14
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.17, '14 kg'
width_mm 425
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.17, '425*387*178mm'

Installation

clearance_bottom_mm 300
clearance_front_mm UNKNOWN
clearance_left_mm 500
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.20, '≥500mm' sides/top and '≥300mm' bottom
clearance_right_mm 500
clearance_top_mm 500
direct_sunlight_restriction 'Do not expose ... to direct sunlight, rain, snow' (manual p.18)
indoor_outdoor indoor and outdoor (IP66)
max_installation_altitude_m 3000
mounting_orientation vertical wall mounting on the supplied bracket
orientation_allowed ['vertical', 'backward tilt ≤15°']
orientation_forbidden ['tilt greater than 15° from vertical']
surface_requirements fire-proof and high-temperature-resistant mounting surface (manual p.19)

Environment

cooling_method natural heat dissipation (fanless)
fan_replaceable not applicable (fanless)
ip_rating IP66
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.72 spec table, 'IP66'
max_altitude_m 3000
noise_level_db ≤29 dB(A) (typical)
MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) — manual p.72, '≤29dB(A)'
operating_temperature_c -25 to +60 (>45 °C derating)
relative_humidity 0~100% operating; 5% RH to 95% RH storage
storage_temperature_c -25 to +60

Interfaces & connectors

ac_terminal_type quick-connector terminal
digital_inputs DRMS port on the 30-pin connector, pins 11-14 relay inputs (manual p.32)
dry_contacts COM port pins 1 and 2 provide a 12 V signal output (manual p.13)
ethernet optional (Shine LAN module)
modbus_rtu yes ('RS485 (Modbus-RTU protocol)')
protocol_notes Battery communication is carried on an RJ45 socket (manual p.34). Documented meters: Growatt TPM-CT-G 100A, Eastron SDM630-Modbus V3, Eastron SDM630MCT 40mA, CHINT DTSU666/3*220/5(80)A and /1.5(6)A.
pv_connector_type H4 / MC4 (optional) - spec table 'H4/MC4 (OPT)'
rs485 yes - on the 30-pin COM connector: pins 3-4 parallel bus, pins 5-6 meter, pins 7-8 battery (manual p.32)
usb yes
wifi optional (Shine WiFi / GPRS / 4G / RF modules)

Controls & display

buttons single touch button - single / double / triple tap and long press (manual p.46)
display_type OLED+LED
leds leaf-shaped LED indicator; 'Green Solid' for normal operation (manual p.11)
local_display True
mobile_app ShinePhone (Growatt)
touchscreen False

Protection

afci AFCI protection - configurable (manual p.77); product page lists 'AFCI function optional'
anti_islanding anti-islanding protection
ground_fault_protection UNKNOWN (grid monitoring and RCMU documented; no separate GFDI entry)
insulation_monitoring insulation resistance monitoring
integrated_dc_switch True
residual_current_monitoring residual-current monitoring unit
reverse_polarity DC reverse-polarity protection
short_circuit AC short-circuit protection
string_monitoring string monitoring documented
surge_protection DC surge protection and AC surge protection (product page: 'Type II SPD on AC&DC side')

Certifications

other ['CE-EMC and CE-LVD certificates, VDE-AR-N 4105:2018 (I and II), VDE 0126-1-1, Austria, and N4105:2021 (CN-PV-210283R2 / CN-PV-210284R2) certificates are published on the official DE product page - located, not fetched']
regional ['CE']

Documents

compatibility-list {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} MOD 3000-10000TL3-XH + ARK XH Battery (system document, EN 202307) — located, not retrieved rev 202307
datasheet {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} MOD 3-10KTL3-XH Datenblatt DE 202306 — located, not retrieved rev 202306
installation-manual MOD 3-10KTL3-XH Installation & Operation Manual (Version 00) rev V00 (2023/2024)
installation-manual {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} MOD_3-10KTL3-XH_User_Manual_EN_202405 (current official revision) — located, not retrieved rev 202405
product-page MOD 3-10KTL3-XH product page (German)
product-page MOD 3000-10000TL3-XH official product page
quick-start {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} MOD_3-10KTL3-XH_Quick_Guide_EN_202510 — located, not retrieved rev 202510

Documented compatibility

Documented pairings only. A product absent here has no fetched document naming the pairing — that is not a statement that it fails.

inverter_meter

Eastron SDM630MCT COMPATIBLEmanufacturer-documented
Growatt MOD 3-10KTL3-XH Installation & Operation Manual (2023, Version 00), Donauer-hosted PDF
CHINT DTSU666 (and DTSU666-CT variant) COMPATIBLEmanufacturer-documented
Growatt MOD 3-10KTL3-XH Installation & Operation Manual (2023, Version 00), Donauer-hosted PDF

Recorded conflicts

max_pv_input_power_w Review required
15000 — solarmagazine.nl datasheet mirror: 'Max recommended PV power 15000W' (extraction showed column-mixing artifacts)
20000 — pvo-int.com datasheet mirror (2022-01): 'Max. recommended PV power: 20000W'
doc revision between datasheet versions, and possible table-parsing artifact in one mirror
max_battery_discharge_power_kw Review required
10 — both datasheet mirrors: 'Max discharging power: 10000W'
11 — manual 2023 V00: 'Max. discharge power: 11kW'
doc revision / manual covers BP-capable hardware
max_battery_discharge_power_kw Review required
10 — both datasheet mirrors: 'Max discharging power: 10000W'
11 — manual 2023 V00: 'Max. discharge power: 11kW'
doc revision / manual covers BP-capable hardware
max_pv_input_power_w Review required
15000 — solarmagazine.nl datasheet mirror: 'Max recommended PV power 15000W' (extraction showed column-mixing artifacts)
20000 — pvo-int.com datasheet mirror (2022-01): 'Max. recommended PV power: 20000W'
doc revision between datasheet versions, and possible table-parsing artifact in one mirror

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

COM port pin map30-pin COM: pins 1-2 12V dry-contact output; pins 3-4 RS485 parallel; pins 5-6 RS485 meter; pins 7-8 RS485 battery; pins 11-14 DRMS relay inputs
Max. tilt from vertical≤15°
Product-page highlights (DE)'Max. Wirkungsgrad 98,6%'; 'DC/AC bis zu 2,0'; 'Typ II SPD auf der AC&DC-Seite'; 'AFCI-Funktion optional'; 'Berührungstaste und OLED-Display'