ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseInverters

Huawei SUN2000-8KTL-M1

Official manufacturer EU (datasheet 04-(20201006)); APAC datasheet 01-(20190716) additionally covers 5/8/10KTL-M1 verified Sept. 3, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category inverters
ean UNKNOWN
generation M1 (three-phase 1100 V DC platform)
hardware_revision UNKNOWN
legacy_name UNKNOWN
manufacturer Huawei
manufacturer_legal_entity UNKNOWN
market_version UNKNOWN
model SUN2000-8KTL-M1
mpn UNKNOWN
order_code UNKNOWN
product_family SUN2000-3/4/5/6/8/10KTL-M1
product_status UNKNOWN
product_status_evidence No live solar.huawei.com product page was fetched for the -M1 family this session; only datasheet PDFs. Status not asserted.
region EU (datasheet 04-(20201006)); APAC datasheet 01-(20190716) additionally covers 5/8/10KTL-M1
release_year UNKNOWN
sku UNKNOWN
subcategory three-phase residential hybrid inverter (battery-ready, DC-coupled)
variant_note The -M1 suffix denotes the battery-capable three-phase 1100 V DC platform. It is NOT the same product as the -M0 sibling in the shared APAC datasheet: -M0 has no battery interface and a different depth (166 mm vs 146.5 mm). ANMA's pre-existing SUN2000-10KTL-M1 record cites a user-manual 'High Current Version' at 13.5 A/19.5 A per MPPT; that user manual was NOT fetched in this session, so no high-current value is recorded here.

Electrical

dc_ac_ratio_guidance UNKNOWN
european_efficiency 98.0%
max_ac_apparent_power_va 8800
max_active_power_w UNKNOWN (no separate max active power row on either fetched datasheet)
max_dc_voltage_v 1100
max_efficiency 98.6%
max_input_current_per_mppt_a 11
max_output_current_a 13.5
max_recommended_pv_power_w 12000
max_short_circuit_current_per_mppt_a 15
mppt_voltage_max_v 980
mppt_voltage_min_v 140
nominal_frequency 50 Hz/60 Hz
nominal_voltage 220 Vac/380 Vac, 230 Vac/400 Vac, 3W/N+PE (three-phase)
num_mppt 2
num_pv_inputs 2
num_pv_inputs_note 'Number of MPP trackers 2' and 'Max. input number per MPP tracker 1' -> 2 DC inputs total on a single unit.
oversizing_limits Recommended max. PV power 12000 Wp against 8000 W rated AC.
power_factor_range 0.8 leading ... 0.8 lagging
rated_ac_power_w 8000
rated_input_voltage_v 600
rated_output_current_a UNKNOWN (no 'Rated output current' row on either fetched datasheet)
startup_voltage_v 200
string_rules UNKNOWN
thd <= 3 %
voltage_range UNKNOWN

Physical / mechanical

cooling Natural convection
depth_mm 146.5
dimensions_note 'Dimension (incl. mounting bracket) 525 x 470 x 146.5 mm'; 'Weight (incl. mounting bracket) 17 kg (37.5 lb)'.
enclosure_material UNKNOWN
height_mm 470
ip_rating IP65
mounting_type UNKNOWN
noise_db UNKNOWN
weight_kg 17.0
width_mm 525

Installation

ac_connector UNKNOWN
cable_entry UNKNOWN
dc_connector UNKNOWN
dc_switch UNKNOWN
mounting UNKNOWN

Environment

altitude_note 'Max. operating altitude 4,000 m (13,123 ft.)'; APAC sheet adds '(Derating above 2000 m)'.
max_altitude_m 4000
operating_temperature -25 ~ +60 C (-13 F ~ 140 F)
relative_humidity 0 %RH ~ 100 %RH

Interfaces & connectors

can UNKNOWN
display LED Indicators
dongle_support Smart Dongle-WLAN-FE (WLAN/Ethernet); Smart Dongle-4G (4G/3G/2G, optional)
ethernet Optional, via Smart Dongle-WLAN-FE
fe Optional, via Smart Dongle-WLAN-FE
fusionsolar_monitoring Yes - 'LED Indicators; Integrated WLAN + FusionSolar App'
local_api_availability UNKNOWN
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
register_doc_availability UNKNOWN
rs485 True
smartlogger_compatibility UNKNOWN
usb UNKNOWN
wlan Yes, integrated WLAN

Protection

afci Yes ('Arc fault protection')
anti_islanding Yes
dc_reverse_polarity_protection Yes
dc_switch UNKNOWN
insulation_monitoring Yes
pid_recovery Yes - 'Integrated PID recovery'
rcmu Yes ('Residual current monitoring')
surge_protection DC surge protection: Yes; AC surge protection: Yes (protection-feature list; class not stated on the fetched M1 sheet)

Certifications

grid_standards ['G98', 'G99', 'EN 50438', 'CEI 0-21', 'VDE-AR-N-4105', 'AS 4777', 'C10/11', 'ABNT', 'NRS 097-2-1']
note Grid-code list merged from the two fetched datasheets; the EU sheet's list is followed by 'others' and is not exhaustive.
regional_certifications UNKNOWN
safety_standards ['EN/IEC 62109-1', 'EN/IEC 62109-2', 'IEC 62116']

Warranty & service

extension_options UNKNOWN
note No warranty row on either fetched datasheet.
standard_warranty UNKNOWN

Documents

datasheet SUN2000-3/4/5/6/8/10KTL-M1 datasheet rev Version No.:04-(20201006)
datasheet SUN2000-5/8/10KTL-M0 & SUN2000-5/8/10KTL-M1 datasheet (APAC) rev Version No.:01-(20190716)

Recorded conflicts

electrical.max_recommended_pv_power_w Review required
12000 Wp — EU datasheet 04-(20201006) 'Recommended max PV power'
12000 Wp — APAC datasheet 01-(20190716) 'Recommended max. PV power'
battery.max_operating_current_a Review required
16.7 A — SUN2000-3/4/5/6/8/10KTL-M1 datasheet, Version No.:04-(20201006), row 'Max operating current'
16 A — SUN2000-5/8/10KTL-M0-M1 datasheet (APAC), Version No.:01-(20190716), row 'Max operating current'

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Battery reverse charging from gridYes
European weighted efficiency98.0%
Integrated PID recoveryYes
Max. efficiency98.6%
Nighttime Power Consumption< 5.5 W; < 10 W when PID recovery function is activated