Identity

brand Sungrow
category inverters
ean UNKNOWN
generation CX disputed
grid_type TN / TT
hardware_revision UNKNOWN
legacy_name UNKNOWN
manufacturer Sungrow
manufacturer_legal_entity Sungrow Power Supply Co., Ltd.
market_version IEC + VDE-AR-N 4110/4120 + AS/NZS 4777.2 + CEI 0-21
model SG110CX
mpn UNKNOWN
order_code UNKNOWN
phase_configuration three-phase (3 / N / PE)
product_family SG110CX (and SG110CX Premium variant) disputed
product_status active disputed
product_status_detail superseded - the official 2026 sungrowpower.com string-inverter index no longer lists SG110CX; the 110 kW slot is now filled by SG110CX-P2 (datasheet Version 4, 2026)
product_status_evidence official product index fetched 2026-09-03; SG100/110CX-P2 datasheet Version 4 (2026) fetched 2026-09-03
region IEC / EU / AU / IN
release_year UNKNOWN
sku UNKNOWN
subcategory grid-tied PV string inverter (three-phase commercial, no battery interface)
topology transformerless (no galvanic isolation)
variant_note ENRICHMENT-ONLY RECORD. ANMA already holds a full SG110CX specification record built from datasheet V1.21. No SG110CX datasheet was re-fetched in this session, so NO electrical value is asserted here - every electrical field is UNKNOWN by design and the existing ANMA record remains the source of truth for specifications. What this record adds is (a) documented accessory compatibility from the official 2026 Compatibility List and (b) an evidenced product-status/succession statement.

Electrical

ac_coupling_support UNKNOWN
backup_eps_output_support false (INFERRED: commercial grid-tie inverter, no backup output in datasheet)
battery_support False
battery_type None (commercial grid-tie string inverter)
battery_voltage_class N/A (no battery interface)
battery_voltage_max_v N/A (no battery interface)
battery_voltage_min_v N/A (no battery interface)
communication_can UNKNOWN
communication_ethernet optional (label 'RS485 / Optional: Wi-Fi, Ethernet')
communication_rs485 True
communication_wifi optional (label 'RS485 / Optional: Wi-Fi, Ethernet')
ct_support UNKNOWN
dc_ac_ratio UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
generator_input_support N/A (grid-tie)
grid_certifications ['IEC 62109', 'IEC 61727', 'IEC 62116', 'IEC 60068', 'IEC 61683', 'VDE-AR-N 4110:2018', 'VDE-AR-N 4120:2018', 'IEC 61000-6-3', 'EN 50549', 'AS/NZS 4777.2:2015', 'CEI 0-21']
grid_export_control UNKNOWN
grid_frequency_hz 50 (45-55) / 60 (55-65)
grid_voltage_v 400, 3/N/PE (voltage range 320-460 V)
home_assistant_integration UNKNOWN
max_ac_power_kw 110 (kVA; temperature-derated to 100 kVA @ 50 C; separate max apparent figure not listed)
max_ac_power_w UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
max_apparent_power_va UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
max_battery_charge_current_a N/A (no battery interface)
max_battery_charge_power_kw N/A (no battery interface)
max_battery_discharge_current_a N/A (no battery interface)
max_dc_voltage_v 1100
max_input_current_per_input_a UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
max_input_current_per_mppt_a 26 (label 'Max. PV input current 26 A * 9')
max_output_current_a UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
max_pv_input_power_w UNKNOWN
max_short_circuit_current_per_mppt_a 40 (label 'Max. DC short-circuit current 40 A * 9')
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
mppt_max_voltage_v 1000
mppt_min_voltage_v 200 (operating range '200 - 1000 V'; MPPT range for nominal power '550 - 850 V')
mppt_voltage_max_v UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
mppt_voltage_min_v UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
nominal_dc_voltage_v UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
nominal_frequency UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
nominal_voltage UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
num_mppt 9
num_pv_inputs UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
officially_supported_battery_brands N/A (no battery support)
oversizing_guidance UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
phase_type three-phase
power_factor_range UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
pv_inputs_per_mppt 2
rated_ac_power_kw 110 (label 'Rated Power 110 kVA @ 45 C / 100 kVA @ 50 C')
rated_ac_power_w UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
recommended_pv_power_w UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
region_variant IEC/EU/AU (400 V grid; 'Premium' AU sub-variant exists with its own datasheets)
smart_meter_support UNKNOWN
sources [{'url': 'https://www.sungrowpowerservice.com/Files/KnowledgeBase/String/Manual/DS_201909_SG110CX%20Datasheet_V1.21.pdf', 'title': 'SG110CX datasheet', 'doc_type': 'datasheet', 'publisher': 'Sungrow (official service knowledge base)', 'revision': 'Version 1.21', 'doc_date': '2019-09', 'language': 'en', 'region': 'IEC', 'accessed': '2026-09-01', 'confidence': 'officially-verified'}, {'url': 'https://www.originenergy.com.au/wp-content/uploads/Datasheet-SG-SG110CX-B-DS024.pdf', 'title': 'SG110CX datasheet (Origin Energy mirror)', 'doc_type': 'datasheet', 'publisher': 'Sungrow (mirrored by Origin Energy)', 'revision': 'Version 1.1', 'doc_date': '2021', 'language': 'en', 'region': 'AU', 'accessed': '2026-09-01', 'confidence': 'distributor-verified'}]
startup_voltage_v 250
string_rules UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
sunspec_support UNKNOWN
thd UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)
topology grid-tie (commercial multi-MPPT string inverter, no battery interface)
voltage_range UNKNOWN (not re-fetched this session - see the existing ANMA SG110CX record, sourced from datasheet V1.21)

Physical / mechanical

bracket_dimensions_mm mounting bracket = 2 bracket components + 1 connecting bar (user manual package list)
cable_entry_positions UNKNOWN
cable_gland_sizes UNKNOWN
cooling UNKNOWN
depth_mm 362.5
dimensions_mm UNKNOWN
enclosure_material UNKNOWN
height_mm 660
mounting_bolt_size M10 x 95 expansion bolts recommended for wall mounting (user manual)
mounting_hole_diameter_mm UNKNOWN
mounting_hole_spacing_mm UNKNOWN
mounting_plate_dimensions_mm UNKNOWN
mounting_type ['wall', 'rack/bracket'] disputed
screw_sizes M4x10, M6x65 and M6x12 hex socket screws supplied (2 each)
shipping_weight_kg UNKNOWN
torque_specs cable gland tightening 2.5 N.m to 3 N.m (user manual)
weight_kg 89
SG110CX Datasheet (including Premium) — 'Weight 89 kg'
width_mm 1051
SG110CX Datasheet (including Premium) — 'Dimensions 1051*660*362.5 mm' (user manual gives '1051x660x362.5mm')

Installation

ac_connector UNKNOWN
altitude_derating_note derating above 3000 m
clearance_bottom_mm at least 300 mm above the ground surface
clearance_front_mm 300 (space in front of the DC/AC connectors for cable binding)
clearance_left_mm 200 (left side carries the fans and needs the larger space per the manual)
clearance_note manual prints '200 mm' minimum per condition, '300 mm' at the DC/AC connectors and 'at least 300 mm higher than ground surface'; a full per-direction diagram mapping was not resolvable from the fetched text
clearance_right_mm UNKNOWN
clearance_top_mm UNKNOWN
dc_connector UNKNOWN
direct_sunlight_restriction 'Prevent direct exposure to sun, rain and snow' (user manual)
indoor_outdoor indoor and outdoor (IP66)
max_installation_altitude_m 4000
mounting_orientation vertical, or with a minimum back tilt of 10 degrees
SG110CX User Manual — mounting chapter: 'Inverter vertically or at a minimum back tilt of 10 degrees. Forward installation or upside down installation is prohibited'
orientation_allowed ['vertical', 'backward tilt >= 10 degrees']
orientation_forbidden ['forward tilt', 'upside down']
surface_requirements UNKNOWN
two_person_lift_required 'at least four installers carry the inverter together' (user manual)

Environment

cooling UNKNOWN
cooling_method smart forced air cooling (fans)
corrosion_class C5 (product page: 'IP66 protection and C5 Anti-corrosion')
fan_replaceable yes (user manual maintenance section 9.2.2)
ip_rating IP66
SG110CX Datasheet (including Premium) — system data 'IP66'
max_altitude_m 4000
SG110CX Datasheet (including Premium) — '4000 m' maximum altitude
noise_db UNKNOWN
noise_level_db UNKNOWN
operating_temperature UNKNOWN
operating_temperature_c -30 to 60 (derating above 50 C per datasheet V1.1.1; the user manual states derating above 45 C - see data_conflicts)
relative_humidity 0 - 95 %, non-condensing
salt_mist_resistance installation within 500 m of the coast is not recommended (user manual)
storage_temperature_c -40 to +70

Interfaces & connectors

ac_terminal_type OT or DT terminal, max. 240 mm2; phase conductors 70-240 mm2; Al and Cu cables supported
SG110CX User Manual — AC cable connection chapter, 'OT or DT terminal (Max. 240 mm2)', phase wires '70~240' mm2
bluetooth yes (commissioning via Bluetooth + app)
can UNKNOWN
digital_inputs DI dry contacts; DRM via RJ45 (pins 5-6 shorting)
display UNKNOWN
ethernet yes (RJ45 network port)
isolarcloud_dependency UNKNOWN
local_communication UNKNOWN
logger_support EyeM4 documented for SG33-110CX (max. 10 devices, daisy chain). Logger1000/Logger1000A-EU rows in the same list name SG150CX and SG33-125CX-P2, NOT SG110CX - NOT_LISTED for SG110CX, which is not the same as incompatible.
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
protocol_notes Datasheet V1.21: 'RS485 / Optional: Wi-Fi, Ethernet'. Logger accessory EyeM4 documented in user manual section 5.13.
pv_connector_type MC4; MC4-Evo2 for >1000 V inputs (user manual)
register_map_availability UNKNOWN
relay_outputs DO dry contact rated 250 Vac / 5 A max or 30 Vdc / 5 A max
rs485 yes (terminal block A / B / GND)
wifi optional module
winet_support yes - Compatibility List 4.3 lists WiNet-S/S2 for 'all SGxxCX/CXP2 models' (max. 1 device, 10 s refresh, WiFi or Ethernet)

Controls & display

display_type LED indicators (no graphic display)
leds LED status indicators
local_display False
mobile_app iSolarCloud (Bluetooth commissioning)
touchscreen False

Protection

afci arc fault / electric arc detection present (fault codes 087-089); listed as optional on the datasheet
anti_islanding yes
dc_reverse_polarity UNKNOWN
dc_switch UNKNOWN
grid_protection UNKNOWN
ground_fault_protection yes (ground fault detection / monitoring)
insulation_monitoring UNKNOWN
integrated_breakers_fuses fuse-free design with smart string current monitoring (product page)
integrated_dc_switch yes - three DC switches, one per terminal group
SG110CX User Manual — three DC switches, one per terminal group
over_current yes (DC overcurrent protection)
over_voltage yes (DC overvoltage protection)
rcmu UNKNOWN
residual_current_monitoring yes (leakage current protection)
reverse_polarity yes (DC reversed polarity protection)
short_circuit yes (AC short circuit protection)
spd UNKNOWN
surge_protection DC Type II and AC Type II standard; DC Type I+II optional

Certifications

emc ['IEC 61000-6-3']
grid_codes ['IEC 61727', 'VDE-AR-N 4110:2018', 'VDE-AR-N 4120:2018', 'EN 50549', 'AS/NZS 4777.2:2015', 'CEI 0-21', 'UTE C15-712-1']
note not re-fetched this session; see the existing ANMA record
other []
regional ['CE']
safety ['IEC 62109', 'IEC 62109-1', 'IEC 62109-2', 'IEC 62116', 'IEC 61683', 'IEC 60068']

Warranty & service

extension_options UNKNOWN
note no warranty statement appears in the fetched datasheet extraction
standard_warranty UNKNOWN

Documents

compatibility-list Sungrow Compatibility List Public 2026 (Version 4.3) rev 4.3
datasheet SG110CX Datasheet rev V1.21
datasheet SG110CX Datasheet (including Premium) rev V1.1.1
product-page SG110CX product page rev live page
product-page Sungrow string inverter product index (official website) rev UNKNOWN
user-manual SG110CX User Manual rev SG110CX-V14 UEN-Ver11-202003 (portal label V1.1)

Recorded conflicts

physical.mounting_type Review required
['wall', 'rack/bracket'] — stored value
['UNKNOWN'] — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
identity.product_status Review required
active — stored value
superseded — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
identity.generation Review required
CX — stored value
CX 1st generation — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
identity.product_family Review required
SG110CX (and SG110CX Premium variant) — stored value
SG110CX (CX 1st-generation commercial multi-MPPT string inverter) — incoming package
Detected during import sungrow-full-portfolio-2026-09-03
environment.operating_temperature_c Review required
-30 to 60 C, derating above 50 C — datasheet V1.1.1 (2021-02-06), system data
-30 to 60 C, derating above 45 C — SG110CX user manual (2020-03), technical data
different document revisions; the 2021 datasheet raises the derating threshold. Both agree on the -30 to 60 C envelope.
environment.operating_temperature_c Review required
-30 to 60 C, derating above 50 C — datasheet V1.1.1 (2021-02-06), system data
-30 to 60 C, derating above 45 C — SG110CX user manual (2020-03), technical data
different document revisions; the 2021 datasheet raises the derating threshold. Both agree on the -30 to 60 C envelope.

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Coastal installationnot recommended within 500 m of the coast
DO relay rating250 Vac max / 5 A; 30 Vdc max / 5 A
Max. AC output current158.8 A
Max. efficiency / European efficiency98.7 % / 98.5 %
Night self consumption< 2 W
Nominal PV input voltage585 V
PID recovery functionYes; applies 500 Vdc by default at night
PV string current monitoringYes (fuse-free design with smart string current monitoring)
Power factor / THD> 0.99 (0.8 leading - 0.8 lagging adjustable); THD < 3 % (at nominal power)
identity.product_statussuperseded - the official 2026 sungrowpower.com string-inverter index no longer lists SG110CX; the 110 kW slot is now filled by SG110CX-P2 (datasheet Version 4, 2026)
manufacturer_legal_entity_as_printedSungrow Power Supply Co., Ltd.

Build a system with this product