Identity

category inverters
manufacturer Victron Energy B.V.
market_version 230 VAC 50 Hz
model MultiPlus-II 230V 48/6k5/100-50
product_family MultiPlus-II 230V (4k/4k5/6k5/10k family)
product_status active
region 230V / EU
release_year UNKNOWN
sku UNKNOWN

Electrical

ac_output_frequency 50 Hz ± 0.1 %
ac_output_voltage 230 VAC ± 2 %
battery_temperature_sensor Optional (ASS000001000)
charge_voltage_absorption_v 57.6
charge_voltage_float_v 55.2
charge_voltage_storage_v 52.8
cont_output_power_at_25c_va UNKNOWN
cont_output_power_at_25c_w 6000
cont_output_power_at_40c_w 5700
cont_output_power_at_65c_w 4600
dc_input_voltage_range 40-66 V
maximum_ac_input_current_a 50
maximum_charge_current_at_25c_a 100
maximum_efficiency_pct 96
peak_power 11 kW/1min
system_dc_voltage_v 48
transfer_switch_a 50
zero_load_power_in_aes_mode_w 18
zero_load_power_w 28

Physical / mechanical

depth_mm 150
enclosure_material Steel, blue RAL 5012
height_mm 644
mounting_type ['wall-mount']
terminal_locations Battery connection: M8 bolts. AC connection: M6 bolts
torque_specs UNKNOWN
weight_kg 29
width_mm 320

Installation

minimum_clearance UNKNOWN
recommended_dc_cable_cross_section UNKNOWN
remote_on_off UNKNOWN

Environment

altitude UNKNOWN
cooling UNKNOWN
humidity max 95 % (non-condensing)
ip_rating IP21
operating_temperature_range -40 to +65 °C

Interfaces & connectors

bluetooth UNKNOWN
ethernet UNKNOWN
general_purpose_com_port Yes, 2x
modbus UNKNOWN
relay Programmable relay: Yes
ve_bus Yes (parallel/three-phase, remote monitoring, system integration)
ve_can UNKNOWN
ve_direct UNKNOWN

Protection

list ['output short circuit', 'overload', 'battery voltage too high', 'battery voltage too low', 'temperature too high', '230 VAC on inverter output', 'input voltage ripple too high']

Certifications

standards ['EN-IEC 60335-1', 'EN-IEC 60335-2-29', 'EN-IEC 62109-1', 'EN-IEC 62109-2', 'EN 55014-1', 'EN 55014-2', 'EN-IEC 61000-3-2', 'EN-IEC 61000-3-3', 'IEC 61000-6-1', 'IEC 61000-6-2', 'IEC 61000-6-3', 'IEC 62040', 'IEC 62116']

Warranty & service

summary UNKNOWN

Documents

datasheet Datasheet MultiPlus-II inverter/charger 4k 4k5 6k5 10k rev UNKNOWN

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Battery connectionM8 bolts
Battery temperature sensorOptional (ASS000001000)
Peak power11 kW/1min