Victron Energy MultiPlus-II 48/8000/110-100
Official manufacturer 230V / EU verified Sept. 2, 2026
Identity
| category | inverters |
| manufacturer | Victron Energy B.V. |
| market_version | 230 VAC 50 Hz |
| model | MultiPlus-II 48/8000/110-100 |
| product_family | MultiPlus-II 230V |
| product_status | active |
| region | 230V / EU |
| release_year | UNKNOWN |
| sku | UNKNOWN |
Electrical
| ac_input_frequency | 45 - 65 Hz |
| ac_input_voltage_range | 187 - 265 VAC |
| ac_output_frequency | 50 Hz ± 0,1 % |
| ac_output_voltage | 230 VAC ± 2 % |
| charge_voltage_absorption_v | 57.6 |
| charge_voltage_float_v | 55.2 |
| charge_voltage_storage_v | 52.8 |
| cont_output_power_at_25c_va | 8000 |
| cont_output_power_at_25c_w | 6400 |
| cont_output_power_at_40c_w | 5500 |
| cont_output_power_at_65c_w | 4000 |
| dc_input_voltage_range | 38 - 66 V |
| maximum_charge_current_a | 110 |
| maximum_efficiency_pct | 95 |
| maximum_feed_through_current_a | 100 |
| peak_power_w | 15000 |
| system_dc_voltage_v | 48 |
| transfer_switch_a | 100 |
| zero_load_power_in_aes_mode_w | 19 |
| zero_load_power_w | 29 |
Physical / mechanical
| depth_mm | 206 |
| enclosure_material | Steel, blue RAL 5012 |
| height_mm | 642 |
| mounting_type | ['wall-mount'] |
| terminal_locations | UNKNOWN |
| torque_specs | Battery terminal M8 nut: 12 Nm; AC terminal M8 bolts: 12 Nm |
| weight_kg | 41.2 |
| width_mm | 363 |
Installation
| minimum_clearance | at least 10cm for ventilation purposes under, above and beside the units |
| recommended_dc_cable_cross_section | UNKNOWN |
| remote_on_off | Yes |
Environment
| altitude | UNKNOWN |
| cooling | fan assisted cooling |
| humidity | max 95 % non-condensing |
| ip_rating | IP 22 |
| operating_temperature_range | -40 to +65 °C |
Interfaces & connectors
| bluetooth | UNKNOWN |
| ethernet | UNKNOWN |
| general_purpose_com_port | Yes, 2x |
| modbus | UNKNOWN |
| relay | Programmable relay: Yes — AC rating: 230V / 4 A, DC rating: 4 A up to 35VDC and 1 A up to 60VDC |
| ve_bus | VE.Bus communication port — Three-phase and parallel(6) operation, remote monitoring and system integration |
| ve_can | UNKNOWN |
| ve_direct | UNKNOWN |
Protection
| list | ['a. Output short circuit', 'b. Overload', 'c. Battery voltage too high', 'd. Battery voltage too low', 'e. Temperature too high', 'f. 230 VAC on inverter output', 'g. Input voltage ripple too high'] |
Certifications
| standards | ['EN-IEC 60335-1', 'EN-IEC 60335-2-29', 'EN-IEC 62109-1', 'EN-IEC 62109-2', 'EN 55014-1', 'EN 55014-2', 'EN-IEC 61000-3-2', 'EN-IEC 61000-3-3', 'IEC 61000-6-1', 'IEC 61000-6-2', 'IEC 61000-6-3'] |
Warranty & service
| summary | UNKNOWN |
Documents
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| Maximum feed through current | 100A |
| Zero load power in AES mode | 19W |