Victron Energy Quattro 48/10000/140-100/100

Official manufacturer EU / 230 V verified Sept. 1, 2026

Identity

brand Victron
category inverters
ean UNKNOWN
generation Quattro (VE.Bus); superseded in part by Quattro-II for newer sizes
manufacturer Victron Energy
market_version 230 VAC 50 Hz (adjustable to 60 Hz; 120 V models available on request)
model Quattro 48/10000/140-100/100
mpn QUA481030010
product_family Quattro 3kVA-15kVA 230 V
product_revision firmware xxxx4xx generation (manual title)
product_status active
region EU / 230 V
release_year UNKNOWN
sku QUA481030010 (Quattro 48/10000/140-100/100 230V VE.Bus)

Electrical

ac_coupling_support True
backup_eps_output_support True
battery_support True
battery_type Lead-acid / Lithium-ion (lithium via VE.Bus BMS or a CAN-bus BMS on a GX device)
battery_voltage_class LV
battery_voltage_max_v 60
battery_voltage_min_v 38
Quattro 3kVA - 15kVA Datasheet (EN) — INVERTER 'Input voltage range (VDC)' = 38-60 V
communication_can N/A on the inverter itself (VE.Bus is native; BMS-Can/CAN is provided by a GX device)
communication_ethernet N/A on the inverter itself (via GX device)
communication_rs485 UNKNOWN
communication_wifi N/A on the inverter itself (Wi-Fi via GX device; Bluetooth via optional VE.Bus Smart Dongle)
ct_support UNKNOWN for this model (the MultiPlus-II datasheet documents an optional 100 A external AC current sensor; the Quattro datasheet row was not transcribed)
generator_input_support True
grid_certifications ['EN-IEC 60335-1', 'EN-IEC 60335-2-29', 'EN-IEC 62109-1', 'EN 55014-1', 'EN 55014-2', 'EN-IEC 61000-3-2', 'EN-IEC 61000-3-3', 'IEC 61000-6-1', 'IEC 61000-6-2', 'IEC 61000-6-3', 'Road vehicles: ECE R10-4 (12 V and 24 V models only - not applicable to this 48 V model)', "Anti-islanding: datasheet says 'See our website'"]
grid_export_control Yes - ESS grid feed-in / zero-feed-in is configured in the GX device (ESS assistant); not a standalone inverter function
home_assistant_integration UNKNOWN
max_ac_power_kw 20
Quattro 3kVA - 15kVA Datasheet (EN) — INVERTER 'Peak power (W)' = 20000
max_battery_charge_current_a 140
Quattro 3kVA - 15kVA Datasheet (EN) — CHARGER 'Charge current house battery (A)' = 140
max_battery_charge_power_kw UNKNOWN
max_battery_discharge_current_a UNKNOWN as a battery current rating; datasheet gives 'Input current (A DC) 235' at full inverter load
max_dc_voltage_v N/A
max_input_current_per_mppt_a N/A
max_pv_input_power_w N/A
max_short_circuit_current_per_mppt_a N/A
modbus_rtu UNKNOWN
modbus_tcp Not native to the inverter. Modbus-TCP is a GX-device service ('Modbus-TCP is a feature on all our GX devices eg Cerbo GX, and Venus GX'), disabled by default; VE.Bus Multis and Quattros are exposed at registers 3-60. A GX device is a hard prerequisite.
mppt_max_voltage_v N/A
mppt_min_voltage_v N/A
num_mppt 0
officially_supported_battery_brands See Victron's official Battery Compatibility pages (Pylontech page fetched: 'All Multi, MultiPlus, MultiGrid and Quattro are compatible' at matching battery voltage).
phase_type single-phase (stackable to split-phase / three-phase via VE.Bus)
pv_inputs_per_mppt N/A (no integrated PV input on this model)
rated_ac_power_kw 8
Quattro 3kVA - 15kVA Datasheet (EN) — INVERTER 'Cont. output power at 25 C' = 10000 VA / 8000 W (48/10000/140-100/100 column)
smart_meter_support Yes via GX device (Victron energy meters); not documented in this datasheet
startup_voltage_v N/A
sunspec_support UNKNOWN
topology hybrid (inverter/charger only - no built-in PV MPPT; PV connects via external Victron MPPT solar charger DC-coupled, or an AC-coupled PV inverter). Two AC inputs with integrated transfer switch (grid + generator).

Physical / mechanical

bracket_dimensions_mm N/A
cable_entry_positions UNKNOWN
cable_gland_sizes UNKNOWN
depth_mm 280
diameter_mm N/A
din_rail_type N/A
enclosure_material aluminium
height_mm 470
housing_color blue RAL 5012
mounting_bolt_size UNKNOWN (a hook and two holes are provided at the back of the casing)
mounting_hole_diameter_mm 6.4 (drawing annotation '6.4 (14x)')
Dimension drawing - Quattro 24/8kVA 230V, 48/8kVA 230V, 48/10kVA 230V, 48/5kVA 120V — dimension drawing annotation '6.4 (14x)'
mounting_hole_spacing_mm UNKNOWN (dimension drawing QUA481030010 carries 336 / 312 / 249 / 174 mm horizontal dimension chains, but the drawing does not label which chain is the mounting-hole pitch)
mounting_plate_dimensions_mm UNKNOWN
mounting_type ['wall']
rack_units N/A
screw_sizes Battery M8; AC M6
shipping_weight_kg UNKNOWN
terminal_locations Battery: four M8 bolts (2 plus and 2 minus connections). AC: M6 bolts for AC-in-1, AC-in-2, AC-out-1 and AC-out-2.
torque_specs Battery connections (M8 cable lugs): maximum torque 14 Nm. AC connections (M6 cable lugs): maximum torque 7 Nm.
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) — manual p.11 sections 4.2/4.3 - battery M8 max 14 Nm, AC M6 max 7 Nm
weight_kg 45
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) — manual section 8 spec table: 'Weight (kg) 45' for the 48/10000/140 column
width_mm 350
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) — manual section 8 spec table: 'Dimensions (hxwxd mm) 470x350x280' for the 48/10000/140 column; dimension drawing gives 348 x 467 x 281 mm overall

Installation

altitude_derating_note UNKNOWN
clearance_bottom_mm 100
clearance_front_mm UNKNOWN
clearance_left_mm 100
clearance_right_mm 100
clearance_top_mm 100
cooling_airflow_requirements Fan-assisted forced-air cooling; 10 cm free space all round
direct_sunlight_restriction UNKNOWN
indoor_outdoor indoor only (IP20)
installation_humidity_range UNKNOWN
installation_temperature_range_c UNKNOWN
max_installation_altitude_m 2000
minimum_wall_thickness_mm UNKNOWN
mounting_orientation Vertical wall mounting preferred for optimal cooling; hook and two holes on the back of the casing; do not place directly above the batteries
orientation_allowed ['vertical (wall)']
orientation_forbidden ['directly above the batteries']
surface_requirements Dry, well-ventilated location as close as possible to the batteries; heat-resistant surroundings with no chemicals, plastics, curtains or textiles nearby
two_person_lift_required UNKNOWN (45 kg)
ventilation_requirements 'The device should be surrounded by a free space of at least 10 cm for cooling purposes'

Environment

cooling_method forced air (fan assisted)
corrosion_class UNKNOWN
fan_replaceable UNKNOWN
ik_rating UNKNOWN
ip_rating IP20
Quattro 3kVA - 15kVA Datasheet (EN) — ENCLOSURE 'Protection category' = 'IP20, pollution degree 2, OVC III'
max_altitude_m 2000
nema_rating UNKNOWN
noise_level_db UNKNOWN
operating_temperature_c -20 to +60; output derates with temperature - 8000 W at 25 C, 6500 W at 40 C, 4500 W at 65 C
pollution_degree 2
relative_humidity max. 95 % (non-condensing)
salt_mist_resistance UNKNOWN
storage_temperature_c UNKNOWN
uv_resistance UNKNOWN

Interfaces & connectors

ac_terminal_type M6 bolts
analog_inputs 2x general-purpose com. port
auxiliary_power_output Starter-battery charge output: not applicable on 48 V models
backup_eps_terminal AC-out-1 (uninterrupted); AC-out-2 (auxiliary, 50 A, drops on battery operation and reconnects ~2 minutes after AC returns)
battery_terminal_type Four M8 bolts (2 plus and 2 minus connections)
bluetooth Optional, via VE.Bus Smart Dongle
can N/A on the inverter (BMS-Can is on the GX device)
cellular N/A (GX device + GX LTE 4G)
cloud_api N/A on the inverter (VRM via GX device)
digital_inputs 2x general-purpose com. port
dry_contacts Remote on-off
ethernet N/A on the inverter (via GX device)
generator_start_contact Yes, via a programmable relay
generator_terminal AC-in-1 is the priority input, intended for a generator; AC-in-2 for shore/mains. Programmable relays can drive genset start/stop.
local_api N/A on the inverter
modbus_rtu UNKNOWN
modbus_tcp Only through a GX device; disabled by default
mqtt UNKNOWN on the inverter; MQTT is a GX-device service
ocpp N/A
programmable_relay Yes, 3x - default alarm relay; settable for genset start/stop, DC under-voltage and other functions
protocol_notes Native bus is VE.Bus only ('For parallel and three phase operation, remote monitoring and system integration'), plus 2x general-purpose com. port and remote on-off. All IP networking and Modbus-TCP come from a GX device.
pv_connector_type N/A (no PV input)
rapid_shutdown_interface N/A
relay_outputs 3x programmable relay - AC rating 230 V / 4 A; DC rating 4 A up to 35 VDC, 1 A up to 60 VDC
Quattro 3kVA - 15kVA Datasheet (EN) — GENERAL 'Programmable relay 3x'; footnote 6 gives the AC/DC ratings
rs232 UNKNOWN
rs485 UNKNOWN
smart_load_output AC-out-2 auxiliary output, 50 A
sunspec UNKNOWN
usb N/A on the inverter (MK3-USB required for configuration over VE.Bus)
wifi N/A on the inverter (via GX device)
zigbee UNKNOWN

Controls & display

audible_alarm UNKNOWN
buttons On / Off / Charger-only rocker switch
display_type none (LED indicators only)
leds Front-panel LED indicators (exact set not transcribed from the fetched sources)
local_display False
mobile_app VictronConnect (VE.Bus Smart Dongle); VRM app with a GX device
remote_display_option Digital Multi Control panel (VE.Bus RJ45); GX Touch with a Cerbo GX
status_indicators LEDs; full status via VictronConnect or a GX device
touchscreen False
web_interface Via GX device (Remote Console) / VRM Portal

Protection

afci N/A
anti_islanding Datasheet: 'See our website'
ground_fault_protection Ground relay (automatic N-PE bonding when no external AC source is present)
insulation_monitoring UNKNOWN
integrated_breakers_fuses No - external DC fuse required (400 A recommended for this model)
integrated_dc_switch False
over_current Overload (protection key b)
over_temperature Temperature too high (protection key e)
over_voltage Battery voltage too high (protection key c)
overvoltage_category OVC III
protection_class Safety class I
residual_current_monitoring UNKNOWN - an earth-leakage circuit breaker is required on AC-out-2 (and on AC-out-1)
reverse_polarity UNKNOWN
short_circuit Output short circuit (protection key a); 'Maximum output fault current 100 A 1 sec'
surge_protection UNKNOWN
under_voltage Battery voltage too low (protection key d)

Certifications

emc ['EN 55014-1', 'EN 55014-2', 'EN-IEC 61000-3-2', 'EN-IEC 61000-3-3', 'IEC 61000-6-1', 'IEC 61000-6-2', 'IEC 61000-6-3']
grid_codes ["Anti-islanding: datasheet defers to the Victron certificate library ('See our website')"]
other ['Road vehicles ECE R10-4 - applies to 12 V and 24 V models only, NOT to this 48 V model']
regional ['CE (implied by EN-IEC compliance; CE mark not quoted verbatim in the fetched sources)']
safety ['EN-IEC 60335-1', 'EN-IEC 60335-2-29', 'EN-IEC 62109-1']

Warranty & service

conditions 'industry-leading 5-year standard warranty and global repair service' (Quattro product page)
cycle_life N/A
design_life_years UNKNOWN
extended_options_years UNKNOWN
fan_replaceable UNKNOWN
field_replaceable_parts ['UNKNOWN']
fuse_replaceable UNKNOWN
service_intervals UNKNOWN
standard_years 5

Packaging & logistics

gross_weight_kg UNKNOWN
package_depth_mm UNKNOWN
package_height_mm UNKNOWN
package_width_mm UNKNOWN
transport_restrictions UNKNOWN
units_per_pallet UNKNOWN

Documents

compatibility-list Victron Energy battery compatibility - Pylontech rev UNKNOWN
datasheet Quattro 3kVA - 15kVA Datasheet (EN) rev UNKNOWN
dimensional-drawing Dimension drawing - Quattro 24/8kVA 230V, 48/8kVA 230V, 48/10kVA 230V, 48/5kVA 120V rev UNKNOWN
installation-manual Parallel, split- and three-phase VE.Bus systems rev UNKNOWN
installation-manual Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) rev firmware xxxx4xx
modbus-manual GX device Modbus-TCP manual / FAQ rev UNKNOWN
product-page Quattro product page rev UNKNOWN

Documented compatibility

Documented pairings only. A product absent here has no fetched document naming the pairing — that is not a statement that it fails.

inverter_battery

Pylontech US3000C COMPATIBLEofficially-verified
Victron Energy official battery compatibility page for Pylontech, https://www.victronenergy.com/live/battery_compatibility:pylontech_phantom (fetched 2026-09-01)
Pylontech Force H2 COMPATIBLEofficially-verified
Victron Energy official battery compatibility page for Pylontech, https://www.victronenergy.com/live/battery_compatibility:pylontech_phantom (fetched 2026-09-01)
BYD Battery-Box Premium LVS (4.0-24.0 family, 16.0 kWh representative) COMPATIBLEmanufacturer-documented
BYD Battery-Box Premium LVS Minimum Configuration List V1.11 (2024-01-16)
Pytes V5 / V5-alpha (printed as V5° / V5°α) COMPATIBLEofficially-verified
Pytes Inverter Compatibility List V.20230819, https://www.pytesess.com/ueditor/php/upload/file/20240705/1720170604646137.pdf (fetched 2026-09-01)
Pytes E-Box 48100R COMPATIBLEofficially-verified
Pytes Inverter Compatibility List V.20230819, https://www.pytesess.com/ueditor/php/upload/file/20240705/1720170604646137.pdf (fetched 2026-09-01)
BSLBATT B-LFP48-200E (19-inch rack battery, 10.24 kWh) COMPATIBLEmanufacturer-documented
BSLBATT B-LFP48 Rack Battery Pack User Manual V2.7 CAN/RS485 protocol tables, https://bslbatt.com/wp-content/uploads/2024/09/B-LFP48-User-Manual-V2.7-Rack-Battery-Pack.pdf (fetched 2026-09-01)
BSLBATT B-LFP48-100E (3U Server Rack Battery) COMPATIBLEmanufacturer-documented
BSLBATT B-LFP48 Rack Battery Pack User Manual V2.7 CAN/RS485 protocol tables, https://bslbatt.com/wp-content/uploads/2024/09/B-LFP48-User-Manual-V2.7-Rack-Battery-Pack.pdf (fetched 2026-09-01)
EG4 LifePower4 48V (v2) COMPATIBLEmanufacturer-documented
EG4 LifePower4 48V V2 & V3 Quick Start Guide protocol tables 11.1/11.2, https://eg4electronics.com/wp-content/uploads/2024/06/EG4-LifePower4-Quick-Start-Guide.pdf (fetched 2026-09-01)
EG4 WallMount Indoor 280Ah (14.3 kWh) COMPATIBLEmanufacturer-documented
EG4 Indoor 280Ah Battery Quick Start Guide protocol tables (p.26-28), https://eg4electronics.com/wp-content/uploads/2024/04/EG4%C2%AE-Indoor-280Ah-Battery-Quick-Start-Guide.pdf (fetched 2026-09-01)
Fortress Power eVault MAX 18.5 kWh COMPATIBLEofficially-verified
Fortress Power Battery Inverter Compatibility Guide, https://www.fortresspower.com/dealers/inverter-compatibility/ (fetched 2026-09-01)

Recorded conflicts

physical.weight_kg / physical dimensions Resolved — imported outcome unspecified
45 kg, 470 x 350 x 280 mm (hxwxd) — Quattro 5k/8k/10k/15k 230V manual, section 8 spec table, per-column transcription (fetched 2026-09-01); corroborated by the QUA481030010 dimension drawing at 348 x 467 x 281 mm overall
51 kg, 444 x 328 x 240 mm — First extraction pass of the Quattro 3kVA-15kVA datasheet ENCLOSURE row (fetched 2026-09-01)
column misalignment while extracting a nine-column ENCLOSURE row from the datasheet PDF; a repeat extraction of the same row produced a differently shifted mapping, confirming the datasheet row cannot be reliably column-mapped by text extraction. The manual and the model-specific dimension drawing agree.
three_phase_max_units_total Review required
18 — Quattro 5k/8k/10k/15k 230V manual, section 4.4.8 ('up to 6 sets of three units')
15 — Victron 'Parallel, split- and three-phase VE.Bus systems' live manual: 'maximum of five units in parallel, on each of the three phases: 15 units in total' (with 15 kVA Quattros: 4 per phase, 12 total)
the product manual states the topological maximum of the parallel mechanism; the VE.Bus systems manual states the currently supported system limit and is the more recent and more specific document. Use 15 for design.
physical.weight_kg / physical dimensions Resolved — imported outcome unspecified
45 kg, 470 x 350 x 280 mm (hxwxd) — Quattro 5k/8k/10k/15k 230V manual, section 8 spec table, per-column transcription (fetched 2026-09-01); corroborated by the QUA481030010 dimension drawing at 348 x 467 x 281 mm overall
51 kg, 444 x 328 x 240 mm — First extraction pass of the Quattro 3kVA-15kVA datasheet ENCLOSURE row (fetched 2026-09-01)
column misalignment while extracting a nine-column ENCLOSURE row from the datasheet PDF; a repeat extraction of the same row produced a differently shifted mapping, confirming the datasheet row cannot be reliably column-mapped by text extraction. The manual and the model-specific dimension drawing agree.
three_phase_max_units_total Review required
18 — Quattro 5k/8k/10k/15k 230V manual, section 4.4.8 ('up to 6 sets of three units')
15 — Victron 'Parallel, split- and three-phase VE.Bus systems' live manual: 'maximum of five units in parallel, on each of the three phases: 15 units in total' (with 15 kVA Quattros: 4 per phase, 12 total)
the product manual states the topological maximum of the parallel mechanism; the VE.Bus systems manual states the currently supported system limit and is the more recent and more specific document. Use 15 for design.

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

AC-in-1 / AC-in-2 protectioneach protected by a fuse or magnetic circuit breaker of 100 A or less; AC-in-1 has priority when both inputs are live
Battery cable cross-section per terminal2x 50 mm2 (0-5 m); 2x 150 mm2 (5-10 m)
Cold-start caveatthe unit may not start if only AC-in-2 has power and the DC battery voltage is 10% or more below nominal
Cont. output power at 25 C (apparent)10000 VA
Cont. output power at 40 C / 65 C6500 W / 4500 W
Input current (A DC)235
Maximum continuous output current (A~)37
Maximum efficiency96 %
Maximum feed-through current (two AC inputs)2x100 A
Maximum output fault current100 A 1 sec
Parallel operation'A maximum of 6 units connected in parallel'
Power factor range+/-0.8
Recommended DC fuse400 A
Recommended battery capacity250-1000 Ah
Three-phase operation (Quattro manual)up to 6 sets of three units, i.e. up to 18 units total, 3-phase wye (Y) only, not delta
Zero load power / AES / Search60 W / 40 W / 15 W
conflict.status[physical.weight_kg / physical dimensions]resolved (manual + model-specific dimension drawing preferred)

Build a system with this product