Victron Energy Quattro 48/10000/140-100/100
Official manufacturer EU / 230 V verified Sept. 1, 2026
Quattro family product page hero image (family photo; not model-specific)
Dimension drawing covering QUA481030010 Quattro 48/10000/140-100/100 230V VE.Bus (PDF, not a raster image)
Quattro family product page second view
Identity
| brand | Victron |
| category | inverters |
| ean | UNKNOWN |
| generation | Quattro (VE.Bus); superseded in part by Quattro-II for newer sizes |
| manufacturer | Victron Energy |
| market_version | 230 VAC 50 Hz (adjustable to 60 Hz; 120 V models available on request) |
| model | Quattro 48/10000/140-100/100 |
| mpn | QUA481030010 |
| product_family | Quattro 3kVA-15kVA 230 V |
| product_revision | firmware xxxx4xx generation (manual title) |
| product_status | active |
| region | EU / 230 V |
| release_year | UNKNOWN |
| sku | QUA481030010 (Quattro 48/10000/140-100/100 230V VE.Bus) |
Electrical
| ac_coupling_support | True |
| backup_eps_output_support | True |
| battery_support | True |
| battery_type | Lead-acid / Lithium-ion (lithium via VE.Bus BMS or a CAN-bus BMS on a GX device) |
| battery_voltage_class | LV |
| battery_voltage_max_v | 60 |
| battery_voltage_min_v |
38
Quattro 3kVA - 15kVA Datasheet (EN) — INVERTER 'Input voltage range (VDC)' = 38-60 V
|
| communication_can | N/A on the inverter itself (VE.Bus is native; BMS-Can/CAN is provided by a GX device) |
| communication_ethernet | N/A on the inverter itself (via GX device) |
| communication_rs485 | UNKNOWN |
| communication_wifi | N/A on the inverter itself (Wi-Fi via GX device; Bluetooth via optional VE.Bus Smart Dongle) |
| ct_support | UNKNOWN for this model (the MultiPlus-II datasheet documents an optional 100 A external AC current sensor; the Quattro datasheet row was not transcribed) |
| generator_input_support | True |
| grid_certifications | ['EN-IEC 60335-1', 'EN-IEC 60335-2-29', 'EN-IEC 62109-1', 'EN 55014-1', 'EN 55014-2', 'EN-IEC 61000-3-2', 'EN-IEC 61000-3-3', 'IEC 61000-6-1', 'IEC 61000-6-2', 'IEC 61000-6-3', 'Road vehicles: ECE R10-4 (12 V and 24 V models only - not applicable to this 48 V model)', "Anti-islanding: datasheet says 'See our website'"] |
| grid_export_control | Yes - ESS grid feed-in / zero-feed-in is configured in the GX device (ESS assistant); not a standalone inverter function |
| home_assistant_integration | UNKNOWN |
| max_ac_power_kw |
20
Quattro 3kVA - 15kVA Datasheet (EN) — INVERTER 'Peak power (W)' = 20000
|
| max_battery_charge_current_a |
140
Quattro 3kVA - 15kVA Datasheet (EN) — CHARGER 'Charge current house battery (A)' = 140
|
| max_battery_charge_power_kw | UNKNOWN |
| max_battery_discharge_current_a | UNKNOWN as a battery current rating; datasheet gives 'Input current (A DC) 235' at full inverter load |
| max_dc_voltage_v | N/A |
| max_input_current_per_mppt_a | N/A |
| max_pv_input_power_w | N/A |
| max_short_circuit_current_per_mppt_a | N/A |
| modbus_rtu | UNKNOWN |
| modbus_tcp | Not native to the inverter. Modbus-TCP is a GX-device service ('Modbus-TCP is a feature on all our GX devices eg Cerbo GX, and Venus GX'), disabled by default; VE.Bus Multis and Quattros are exposed at registers 3-60. A GX device is a hard prerequisite. |
| mppt_max_voltage_v | N/A |
| mppt_min_voltage_v | N/A |
| num_mppt | 0 |
| officially_supported_battery_brands | See Victron's official Battery Compatibility pages (Pylontech page fetched: 'All Multi, MultiPlus, MultiGrid and Quattro are compatible' at matching battery voltage). |
| phase_type | single-phase (stackable to split-phase / three-phase via VE.Bus) |
| pv_inputs_per_mppt | N/A (no integrated PV input on this model) |
| rated_ac_power_kw |
8
Quattro 3kVA - 15kVA Datasheet (EN) — INVERTER 'Cont. output power at 25 C' = 10000 VA / 8000 W (48/10000/140-100/100 column)
|
| smart_meter_support | Yes via GX device (Victron energy meters); not documented in this datasheet |
| startup_voltage_v | N/A |
| sunspec_support | UNKNOWN |
| topology | hybrid (inverter/charger only - no built-in PV MPPT; PV connects via external Victron MPPT solar charger DC-coupled, or an AC-coupled PV inverter). Two AC inputs with integrated transfer switch (grid + generator). |
Physical / mechanical
| bracket_dimensions_mm | N/A |
| cable_entry_positions | UNKNOWN |
| cable_gland_sizes | UNKNOWN |
| depth_mm | 280 |
| diameter_mm | N/A |
| din_rail_type | N/A |
| enclosure_material | aluminium |
| height_mm | 470 |
| housing_color | blue RAL 5012 |
| mounting_bolt_size | UNKNOWN (a hook and two holes are provided at the back of the casing) |
| mounting_hole_diameter_mm |
6.4 (drawing annotation '6.4 (14x)')
Dimension drawing - Quattro 24/8kVA 230V, 48/8kVA 230V, 48/10kVA 230V, 48/5kVA 120V — dimension drawing annotation '6.4 (14x)'
|
| mounting_hole_spacing_mm | UNKNOWN (dimension drawing QUA481030010 carries 336 / 312 / 249 / 174 mm horizontal dimension chains, but the drawing does not label which chain is the mounting-hole pitch) |
| mounting_plate_dimensions_mm | UNKNOWN |
| mounting_type | ['wall'] |
| rack_units | N/A |
| screw_sizes | Battery M8; AC M6 |
| shipping_weight_kg | UNKNOWN |
| terminal_locations | Battery: four M8 bolts (2 plus and 2 minus connections). AC: M6 bolts for AC-in-1, AC-in-2, AC-out-1 and AC-out-2. |
| torque_specs |
Battery connections (M8 cable lugs): maximum torque 14 Nm. AC connections (M6 cable lugs): maximum torque 7 Nm.
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) — manual p.11 sections 4.2/4.3 - battery M8 max 14 Nm, AC M6 max 7 Nm
|
| weight_kg |
45
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) — manual section 8 spec table: 'Weight (kg) 45' for the 48/10000/140 column
|
| width_mm |
350
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx) — manual section 8 spec table: 'Dimensions (hxwxd mm) 470x350x280' for the 48/10000/140 column; dimension drawing gives 348 x 467 x 281 mm overall
|
Installation
| altitude_derating_note | UNKNOWN |
| clearance_bottom_mm | 100 |
| clearance_front_mm | UNKNOWN |
| clearance_left_mm | 100 |
| clearance_right_mm | 100 |
| clearance_top_mm | 100 |
| cooling_airflow_requirements | Fan-assisted forced-air cooling; 10 cm free space all round |
| direct_sunlight_restriction | UNKNOWN |
| indoor_outdoor | indoor only (IP20) |
| installation_humidity_range | UNKNOWN |
| installation_temperature_range_c | UNKNOWN |
| max_installation_altitude_m | 2000 |
| minimum_wall_thickness_mm | UNKNOWN |
| mounting_orientation | Vertical wall mounting preferred for optimal cooling; hook and two holes on the back of the casing; do not place directly above the batteries |
| orientation_allowed | ['vertical (wall)'] |
| orientation_forbidden | ['directly above the batteries'] |
| surface_requirements | Dry, well-ventilated location as close as possible to the batteries; heat-resistant surroundings with no chemicals, plastics, curtains or textiles nearby |
| two_person_lift_required | UNKNOWN (45 kg) |
| ventilation_requirements | 'The device should be surrounded by a free space of at least 10 cm for cooling purposes' |
Environment
| cooling_method | forced air (fan assisted) |
| corrosion_class | UNKNOWN |
| fan_replaceable | UNKNOWN |
| ik_rating | UNKNOWN |
| ip_rating |
IP20
Quattro 3kVA - 15kVA Datasheet (EN) — ENCLOSURE 'Protection category' = 'IP20, pollution degree 2, OVC III'
|
| max_altitude_m | 2000 |
| nema_rating | UNKNOWN |
| noise_level_db | UNKNOWN |
| operating_temperature_c | -20 to +60; output derates with temperature - 8000 W at 25 C, 6500 W at 40 C, 4500 W at 65 C |
| pollution_degree | 2 |
| relative_humidity | max. 95 % (non-condensing) |
| salt_mist_resistance | UNKNOWN |
| storage_temperature_c | UNKNOWN |
| uv_resistance | UNKNOWN |
Interfaces & connectors
| ac_terminal_type | M6 bolts |
| analog_inputs | 2x general-purpose com. port |
| auxiliary_power_output | Starter-battery charge output: not applicable on 48 V models |
| backup_eps_terminal | AC-out-1 (uninterrupted); AC-out-2 (auxiliary, 50 A, drops on battery operation and reconnects ~2 minutes after AC returns) |
| battery_terminal_type | Four M8 bolts (2 plus and 2 minus connections) |
| bluetooth | Optional, via VE.Bus Smart Dongle |
| can | N/A on the inverter (BMS-Can is on the GX device) |
| cellular | N/A (GX device + GX LTE 4G) |
| cloud_api | N/A on the inverter (VRM via GX device) |
| digital_inputs | 2x general-purpose com. port |
| dry_contacts | Remote on-off |
| ethernet | N/A on the inverter (via GX device) |
| generator_start_contact | Yes, via a programmable relay |
| generator_terminal | AC-in-1 is the priority input, intended for a generator; AC-in-2 for shore/mains. Programmable relays can drive genset start/stop. |
| local_api | N/A on the inverter |
| modbus_rtu | UNKNOWN |
| modbus_tcp | Only through a GX device; disabled by default |
| mqtt | UNKNOWN on the inverter; MQTT is a GX-device service |
| ocpp | N/A |
| programmable_relay | Yes, 3x - default alarm relay; settable for genset start/stop, DC under-voltage and other functions |
| protocol_notes | Native bus is VE.Bus only ('For parallel and three phase operation, remote monitoring and system integration'), plus 2x general-purpose com. port and remote on-off. All IP networking and Modbus-TCP come from a GX device. |
| pv_connector_type | N/A (no PV input) |
| rapid_shutdown_interface | N/A |
| relay_outputs |
3x programmable relay - AC rating 230 V / 4 A; DC rating 4 A up to 35 VDC, 1 A up to 60 VDC
Quattro 3kVA - 15kVA Datasheet (EN) — GENERAL 'Programmable relay 3x'; footnote 6 gives the AC/DC ratings
|
| rs232 | UNKNOWN |
| rs485 | UNKNOWN |
| smart_load_output | AC-out-2 auxiliary output, 50 A |
| sunspec | UNKNOWN |
| usb | N/A on the inverter (MK3-USB required for configuration over VE.Bus) |
| wifi | N/A on the inverter (via GX device) |
| zigbee | UNKNOWN |
Controls & display
| audible_alarm | UNKNOWN |
| buttons | On / Off / Charger-only rocker switch |
| display_type | none (LED indicators only) |
| leds | Front-panel LED indicators (exact set not transcribed from the fetched sources) |
| local_display | False |
| mobile_app | VictronConnect (VE.Bus Smart Dongle); VRM app with a GX device |
| remote_display_option | Digital Multi Control panel (VE.Bus RJ45); GX Touch with a Cerbo GX |
| status_indicators | LEDs; full status via VictronConnect or a GX device |
| touchscreen | False |
| web_interface | Via GX device (Remote Console) / VRM Portal |
Protection
| afci | N/A |
| anti_islanding | Datasheet: 'See our website' |
| ground_fault_protection | Ground relay (automatic N-PE bonding when no external AC source is present) |
| insulation_monitoring | UNKNOWN |
| integrated_breakers_fuses | No - external DC fuse required (400 A recommended for this model) |
| integrated_dc_switch | False |
| over_current | Overload (protection key b) |
| over_temperature | Temperature too high (protection key e) |
| over_voltage | Battery voltage too high (protection key c) |
| overvoltage_category | OVC III |
| protection_class | Safety class I |
| residual_current_monitoring | UNKNOWN - an earth-leakage circuit breaker is required on AC-out-2 (and on AC-out-1) |
| reverse_polarity | UNKNOWN |
| short_circuit | Output short circuit (protection key a); 'Maximum output fault current 100 A 1 sec' |
| surge_protection | UNKNOWN |
| under_voltage | Battery voltage too low (protection key d) |
Certifications
| emc | ['EN 55014-1', 'EN 55014-2', 'EN-IEC 61000-3-2', 'EN-IEC 61000-3-3', 'IEC 61000-6-1', 'IEC 61000-6-2', 'IEC 61000-6-3'] |
| grid_codes | ["Anti-islanding: datasheet defers to the Victron certificate library ('See our website')"] |
| other | ['Road vehicles ECE R10-4 - applies to 12 V and 24 V models only, NOT to this 48 V model'] |
| regional | ['CE (implied by EN-IEC compliance; CE mark not quoted verbatim in the fetched sources)'] |
| safety | ['EN-IEC 60335-1', 'EN-IEC 60335-2-29', 'EN-IEC 62109-1'] |
Warranty & service
| conditions | 'industry-leading 5-year standard warranty and global repair service' (Quattro product page) |
| cycle_life | N/A |
| design_life_years | UNKNOWN |
| extended_options_years | UNKNOWN |
| fan_replaceable | UNKNOWN |
| field_replaceable_parts | ['UNKNOWN'] |
| fuse_replaceable | UNKNOWN |
| service_intervals | UNKNOWN |
| standard_years | 5 |
Packaging & logistics
| gross_weight_kg | UNKNOWN |
| package_depth_mm | UNKNOWN |
| package_height_mm | UNKNOWN |
| package_width_mm | UNKNOWN |
| transport_restrictions | UNKNOWN |
| units_per_pallet | UNKNOWN |
Documents
dimensional-drawing
Dimension drawing - Quattro 24/8kVA 230V, 48/8kVA 230V, 48/10kVA 230V, 48/5kVA 120V
rev UNKNOWN
installation-manual
Quattro 5k / 8k / 10k / 15k 100-100A 230V Manual (firmware xxxx4xx)
rev firmware xxxx4xx
Documented compatibility
Documented pairings only. A product absent here has no fetched document naming the pairing — that is not a statement that it fails.
inverter_battery
Pylontech US3000C
COMPATIBLEofficially-verified
Victron Energy official battery compatibility page for Pylontech, https://www.victronenergy.com/live/battery_compatibility:pylontech_phantom (fetched 2026-09-01)
Pylontech Force H2
COMPATIBLEofficially-verified
Victron Energy official battery compatibility page for Pylontech, https://www.victronenergy.com/live/battery_compatibility:pylontech_phantom (fetched 2026-09-01)
BYD Battery-Box Premium LVS (4.0-24.0 family, 16.0 kWh representative)
COMPATIBLEmanufacturer-documented
BYD Battery-Box Premium LVS Minimum Configuration List V1.11 (2024-01-16)
Pytes V5 / V5-alpha (printed as V5° / V5°α)
COMPATIBLEofficially-verified
Pytes Inverter Compatibility List V.20230819, https://www.pytesess.com/ueditor/php/upload/file/20240705/1720170604646137.pdf (fetched 2026-09-01)
Pytes E-Box 48100R
COMPATIBLEofficially-verified
Pytes Inverter Compatibility List V.20230819, https://www.pytesess.com/ueditor/php/upload/file/20240705/1720170604646137.pdf (fetched 2026-09-01)
BSLBATT B-LFP48-200E (19-inch rack battery, 10.24 kWh)
COMPATIBLEmanufacturer-documented
BSLBATT B-LFP48 Rack Battery Pack User Manual V2.7 CAN/RS485 protocol tables, https://bslbatt.com/wp-content/uploads/2024/09/B-LFP48-User-Manual-V2.7-Rack-Battery-Pack.pdf (fetched 2026-09-01)
BSLBATT B-LFP48-100E (3U Server Rack Battery)
COMPATIBLEmanufacturer-documented
BSLBATT B-LFP48 Rack Battery Pack User Manual V2.7 CAN/RS485 protocol tables, https://bslbatt.com/wp-content/uploads/2024/09/B-LFP48-User-Manual-V2.7-Rack-Battery-Pack.pdf (fetched 2026-09-01)
EG4 LifePower4 48V (v2)
COMPATIBLEmanufacturer-documented
EG4 LifePower4 48V V2 & V3 Quick Start Guide protocol tables 11.1/11.2, https://eg4electronics.com/wp-content/uploads/2024/06/EG4-LifePower4-Quick-Start-Guide.pdf (fetched 2026-09-01)
EG4 WallMount Indoor 280Ah (14.3 kWh)
COMPATIBLEmanufacturer-documented
EG4 Indoor 280Ah Battery Quick Start Guide protocol tables (p.26-28), https://eg4electronics.com/wp-content/uploads/2024/04/EG4%C2%AE-Indoor-280Ah-Battery-Quick-Start-Guide.pdf (fetched 2026-09-01)
Fortress Power eVault MAX 18.5 kWh
COMPATIBLEofficially-verified
Fortress Power Battery Inverter Compatibility Guide, https://www.fortresspower.com/dealers/inverter-compatibility/ (fetched 2026-09-01)
Recorded conflicts
physical.weight_kg / physical dimensions Resolved — imported outcome unspecified
45 kg, 470 x 350 x 280 mm (hxwxd) — Quattro 5k/8k/10k/15k 230V manual, section 8 spec table, per-column transcription (fetched 2026-09-01); corroborated by the QUA481030010 dimension drawing at 348 x 467 x 281 mm overall
51 kg, 444 x 328 x 240 mm — First extraction pass of the Quattro 3kVA-15kVA datasheet ENCLOSURE row (fetched 2026-09-01)
column misalignment while extracting a nine-column ENCLOSURE row from the datasheet PDF; a repeat extraction of the same row produced a differently shifted mapping, confirming the datasheet row cannot be reliably column-mapped by text extraction. The manual and the model-specific dimension drawing agree.
three_phase_max_units_total Review required
18 — Quattro 5k/8k/10k/15k 230V manual, section 4.4.8 ('up to 6 sets of three units')
15 — Victron 'Parallel, split- and three-phase VE.Bus systems' live manual: 'maximum of five units in parallel, on each of the three phases: 15 units in total' (with 15 kVA Quattros: 4 per phase, 12 total)
the product manual states the topological maximum of the parallel mechanism; the VE.Bus systems manual states the currently supported system limit and is the more recent and more specific document. Use 15 for design.
physical.weight_kg / physical dimensions Resolved — imported outcome unspecified
45 kg, 470 x 350 x 280 mm (hxwxd) — Quattro 5k/8k/10k/15k 230V manual, section 8 spec table, per-column transcription (fetched 2026-09-01); corroborated by the QUA481030010 dimension drawing at 348 x 467 x 281 mm overall
51 kg, 444 x 328 x 240 mm — First extraction pass of the Quattro 3kVA-15kVA datasheet ENCLOSURE row (fetched 2026-09-01)
column misalignment while extracting a nine-column ENCLOSURE row from the datasheet PDF; a repeat extraction of the same row produced a differently shifted mapping, confirming the datasheet row cannot be reliably column-mapped by text extraction. The manual and the model-specific dimension drawing agree.
three_phase_max_units_total Review required
18 — Quattro 5k/8k/10k/15k 230V manual, section 4.4.8 ('up to 6 sets of three units')
15 — Victron 'Parallel, split- and three-phase VE.Bus systems' live manual: 'maximum of five units in parallel, on each of the three phases: 15 units in total' (with 15 kVA Quattros: 4 per phase, 12 total)
the product manual states the topological maximum of the parallel mechanism; the VE.Bus systems manual states the currently supported system limit and is the more recent and more specific document. Use 15 for design.
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| AC-in-1 / AC-in-2 protection | each protected by a fuse or magnetic circuit breaker of 100 A or less; AC-in-1 has priority when both inputs are live |
| Battery cable cross-section per terminal | 2x 50 mm2 (0-5 m); 2x 150 mm2 (5-10 m) |
| Cold-start caveat | the unit may not start if only AC-in-2 has power and the DC battery voltage is 10% or more below nominal |
| Cont. output power at 25 C (apparent) | 10000 VA |
| Cont. output power at 40 C / 65 C | 6500 W / 4500 W |
| Input current (A DC) | 235 |
| Maximum continuous output current (A~) | 37 |
| Maximum efficiency | 96 % |
| Maximum feed-through current (two AC inputs) | 2x100 A |
| Maximum output fault current | 100 A 1 sec |
| Parallel operation | 'A maximum of 6 units connected in parallel' |
| Power factor range | +/-0.8 |
| Recommended DC fuse | 400 A |
| Recommended battery capacity | 250-1000 Ah |
| Three-phase operation (Quattro manual) | up to 6 sets of three units, i.e. up to 18 units total, 3-phase wye (Y) only, not delta |
| Zero load power / AES / Search | 60 W / 40 W / 15 W |
| conflict.status[physical.weight_kg / physical dimensions] | resolved (manual + model-specific dimension drawing preferred) |