⚡ANMASystem BuildingAutomation, Network, Monitoring & Analytics
★PREMIUM

Knowledge Base › Backup Switching Devices

Official manufacturer GLOBAL verified Sept. 25, 2026

Identity

category backup_switching_devices
manufacturer Socomec
model 16000035
product_status active
region GLOBAL
variant —

Electrical

compatible_transfer_switches ATyS r, ATyS S and ATyS d M
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
device_role ATS controller for remotely operated transfer switching equipment
ATyS C35 ATS controller - digital functions
digital_inputs 4 fixed, 3 programmable
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
digital_outputs 4 fixed, 1 programmable
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
door_cutout_mm 138 x 92
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
frequency_limits_hz 45 - 65
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
impulse_withstand_kv 6/4
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
modbus_baud_rate 2400-38400
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
official_product_url https://emea.socomec.com/en/p/atys-c35
ATyS C35 ATS controller - digital functions — inventory record source_url
overvoltage_category CAT 3
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
phase_count 1
pole_count 3
power_consumption_w < 10 W
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
rated_current_a 1600.0
rated_voltage_v 400.0
supply_voltage_ac_v 184 - 300 VAC
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
supply_voltage_dc_v 10-30 VDC
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
switching_time_ms 50.0
weight_g 845
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)

Installation

mounting DIN rail or door mounting
ATyS C35 ATS controller - digital functions

Environment

operating_temperature_c -25 ... +70
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)

Interfaces & connectors

communications RS485
ATyS C35 ATS controller - digital functions
documented_ports [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Product page - communication', 'quote': 'RS485 Modbus communication'}]
protocols ['Modbus RTU']
ATyS C35 ATS controller - digital functions

Certifications

standards ['IEC 61010-2-201', 'IEC 60947-6-1', 'GB/T 14048.11 Annexe C']
ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)

Documents

application_note ATS controller for Transfer Switching Equipment (brochure EN)
compatibility_list ATS Controller - selection guide (PCG034 EN V01)
datasheet ATyS C35 ATS Controller - catalogue pages (PCG131 EN V01)
product_page ATyS C35 ATS controller - digital functions
quick_start_guide ATyS C35 ATS Controller - quick start guide

Recorded conflicts

interfaces.communications Resolved — kept current value
RS485 — stored value
RS485, 2 to 3 half duplex wires, MODBUS RTU — RS485 wires: 2 to 3 half duplex wires / Protocol: MODBUS RTU
Detected during import deep-enrich-2026-09-batch01

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

builder_completenesspartial
region_notesControl unit only, no power path. Declared to IEC 61010-2-201, IEC 60947-6-1 and GB/T 14048.11 Annex C, i.e. the same article is sold worldwide.