Electrical
| current_transformer_secondary_a |
1 or 5
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| device_role |
ATS controller for remotely operated transfer switching equipment
ATyS C65 ATS Controller - advanced functionalities
|
| digital_inputs |
6, fully programmable
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| digital_outputs |
6, fully programmable
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| door_cutout_mm |
220 x 160
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| frequency_limits_hz |
45 - 65
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| impulse_withstand_kv |
8/6
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| modbus_baud_rate |
programmable 1200 - 115200 bps
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| official_product_url |
https://emea.socomec.com/en/p/atys-c65
ATyS C65 ATS Controller - advanced functionalities — inventory record source_url
|
| output_relay_rating |
8 A AC 15
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| overvoltage_category |
CAT 3
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| phase_count | 1 |
| pole_count | 3 |
| power_consumption_w |
< 10 W
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| rated_current_a | 1600.0 |
| rated_voltage_v | 400.0 |
| supply_voltage_ac_v |
110 - 480 V AC +/-20%
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| supply_voltage_dc_v |
24 V DC
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| switching_time_ms | 50.0 |
| weight_g |
1080
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
Physical / mechanical
| mounting | DIN-rail / Panel mount |
Environment
| ip_rating |
IP65
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| operating_temperature_c |
-30 to +70
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
| operating_temperature_max_c | 60.0 |
| operating_temperature_min_c | -25.0 |
Interfaces & connectors
| communications |
RS485
disputed
ATyS C65 ATS Controller - advanced functionalities
|
| documented_ports | [{'port_role': 'RS485', 'port_label_from_manual': 'RS485 Modbus', 'port_type': 'RS485', 'direction': 'bidirectional', 'electrical_domain': 'communication', 'quantity': 1, 'document': 0, 'page': 'Product page - communication', 'quote': 'RS485 Modbus communication'}] |
| protocols |
['Modbus RTU']
ATyS C65 ATS Controller - advanced functionalities
|
Certifications
| standards |
['IEC 61010-2-201', 'IEC 60947-6-1', 'GB/T 14048.11 Annexe C']
ATyS C65 ATS Controller - catalogue pages (PCG023 EN V01)
|
Documents
installation_manual
ATyS C55_C65 - ATS Controller - installation and operating manual (EN)
product_page
ATyS C65 ATS Controller - advanced functionalities
Recorded conflicts
interfaces.communications Review required
RS485 — stored value
RS485 (2 to 3 half duplex wires) MODBUS RTU; Ethernet with embedded web server, SNMP, BACnet — Interface type RS485. 2 to 3 half duplex wires / Protocol MODBUS RTU / Web server included with Ethernet, SNMP, BACnet
Detected during import deep-enrich-2026-09-batch01
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| builder_completeness | partial |
| region_notes | Control unit only, no power path. Declared to IEC 61010-2-201, IEC 60947-6-1 and GB/T 14048.11 Annex C, i.e. the same article is sold worldwide. |