ANMASystem BuildingAutomation, Network, Monitoring & Analytics
PREMIUM

Knowledge BaseBatteries

Dyness Tower Pro TP19

Verified distributor global (EN documentation) verified Sept. 2, 2026

Unresolved safety-relevant conflict
Two sources give different figures for a value on this product and nobody has resolved it. The specifications below are shown as recorded, but this product must not be treated as verified for engineering purposes until the conflict is closed.

Identity

category batteries
ean UNKNOWN
generation Tower Pro (successor generation to the Tower T7-T21 series)
hardware_revision UNKNOWN
legacy_name UNKNOWN
manufacturer Dyness (Dyness Digital Energy Technology Co., LTD)
market_version EN
model Tower Pro TP19
mpn UNKNOWN
product_family Dyness Tower Pro (TP7 / TP11 / TP15 / TP19 / TP23, 192-576 V HV)
product_status UNKNOWN
product_status_detail current
product_status_evidence Live official product page with full specification table at https://dyness.com/tower-pro-high-voltage-storage-battery-for-household-use (accessed 2026-09-02); an official datasheet revision dated 2025-10-30 is linked from that page.
region global (EN documentation)
release_year UNKNOWN
sku UNKNOWN
subcategory high-voltage residential stacked battery SYSTEM (Base + BDU control unit + N HV9640 modules)
variant_note SYSTEM-level record. Tower Pro TP19 = 5 x HV9640 battery modules on one Base + BDU. The 19.2 kWh / 480 V figures are SYSTEM figures; the module is 96 V / 40 Ah / 3.84 kWh (see the separate HV9640 record). Tower Pro is a 1C system (max charge and discharge power in kW equals the rated energy in kWh); the older Tower series is not.

Electrical

cell_chemistry LiFePO4 (manual: 'LFP' / 'Li-ion (LFP)')
cell_type UNKNOWN
continuous_charge_current_a 20
continuous_discharge_current_a 20
continuous_power_kw 19.2
cycle_life 8000
depth_of_discharge_pct 95
max_charge_current_a 40
max_charge_power_kw 19.2
max_discharge_current_a 40
max_discharge_power_kw 19.2
max_parallel_units 12
max_series_units 6
modules_per_tower_max 6
modules_per_tower_min 2
nominal_capacity_ah 40
nominal_energy_kwh 19.2
nominal_voltage_v 480
operating_voltage_max_v 540
operating_voltage_min_v 420
parallel_supported True
peak_charge_current_a UNKNOWN
peak_discharge_current_a UNKNOWN
peak_power_kw UNKNOWN
round_trip_efficiency_pct 95
series_supported True
system_energy_max_kwh 276.48
system_energy_min_kwh 7.68
usable_energy_kwh 18.24

Physical / mechanical

color UNKNOWN
cooling_method UNKNOWN
depth_mm 310
enclosure_material UNKNOWN
height_mm 1451
installation_notes Manual clearance diagram: 300 mm lateral clearance on each side; not in direct sunlight, rain or snow; not against flammable walls. Grounding resistance requirement quoted as '<=100 mOhm' (system) and '<1 Ohm' (installation).
ip_rating IP55
mounting_type floor-standing stacked tower (BDU control module on top of N stacked HV9640 modules, on a base)
rack_units UNKNOWN
shipping_weight_kg UNKNOWN
weight_kg 206.0
width_mm 587

Installation

clearance_notes 300 mm lateral clearance on each side (manual clearance diagram)
indoor_outdoor indoor and outdoor (IP55)
notes Parallel connection prerequisites (manual): same model and same capacity, inter-cluster voltage difference <20 V, all clusters at 100% SOC, additions at intervals <6 months, start Slave first and Host last. Grounding: '<=100 mOhm' system / '<1 Ohm' installation.
parallel_hub_required No - clusters daisy-chain via the BDU 'Parallel 1#' and 'Parallel 2#' RJ45 ports

Environment

indoor_outdoor indoor and outdoor (IP55); official page claims 'operation from -20C to 55C'
max_altitude_m UNKNOWN
operating_humidity UNKNOWN
operating_temperature_charge_max_c 55
operating_temperature_charge_min_c 0
operating_temperature_discharge_max_c 55
operating_temperature_discharge_min_c -10
operating_temperature_max_c 55
operating_temperature_min_c -20
pollution_degree II (HV9640 module table)
storage_humidity <65% RH
storage_temperature_max_c 45
storage_temperature_min_c 5

Interfaces & connectors

bluetooth UNKNOWN
can True
communication_ports BDU: 'Parallel 1#', 'Parallel 2#' (multi-cluster RJ45), 'Inverter CAN/RS485' RJ45, WiFi antenna
dry_contact UNKNOWN
ethernet UNKNOWN
modbus_rtu UNKNOWN
modbus_tcp UNKNOWN
protocol_notes Inverter CAN/RS485 RJ45 pinout (manual Table 2-8): PIN1 Orange/White 485_B, PIN2 Orange 485_A, PIN3 Green/White Reserved, PIN4 Blue CANH, PIN5 Blue/White CANL, PIN6 Green NC, PIN7 Brown/White NC, PIN8 Brown NC. NOTE the 485_A/485_B pin order is the reverse of the Tower (non-Pro) manual - do not assume the two are interchangeable.
rs232 Datasheet 'Communication' row reads 'CAN/RS485/RS232'; the user manual documents only CAN and RS485 on the BDU inverter RJ45
rs485 True
usb UNKNOWN
wifi Yes - the BDU carries a 'WiFi antenna' and a 'WiFi status light' (manual Table 2-5)

Protection

fire_suppression Aerosol fire extinguishing equipped (datasheet 'Fire Protection'); official page claims '5-second fire extinguishing'
notes Optional PTC heating: activates below 2 C, exits above 5 C, powered from the inverter or the battery itself, cut off when SOC<20%.
overcurrent BDU DC breaker described as 'Master switch; short circuit protection'
short_circuit_current_ka 1.5

Certifications

emc_certifications CE-EMC
safety_certifications VDE2510-50 / IEC62619 / IEC63056 / IEC62477 / IEC62040; manual also names TUV certification
standards UN38.3/VDE2510-50/IEC62619/IEC63056/IEC62477/IEC62040/CE-EMC/ROHS
transport_certifications UN38.3

Warranty & service

conditions UNKNOWN
summary Datasheet 'Warranty' row: '10/15 Years (optional)'. Etronixcenter adds '10 years on the BMS' and a '15-year manufacturer warranty on the batteries'.
years 10 (15 optional)

Documents

compatibility_list {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Dyness Tower Pro Series Compatibility List 2025-10-16 - official — located, not retrieved rev 20251016
datasheet {# Located but never retrieved: listed, but deliberately not linked, and it backs no stored value. #} Dyness Tower Pro Datasheet EN 2025-10-30 (DynessTowerProDatasheetEN20251030.pdf) - official, linked from the Tower Pro product page — located, not retrieved rev 2025-10-30
datasheet Dyness Tower Pro datasheet-EN V1.0-20240520 - distributor mirror on zuidwestsolar.nl rev V1.0-20240520
datasheet Dyness Tower Pro datasheet-EN V1.0-20240520 - second distributor mirror on rayshine-solar.com (corroborating copy) rev V1.0-20240520
distributor_listing 7SUN distributor listing: Battery module - DYNESS - HV9640 - PRO - 3.84 kWh - HV rev UNKNOWN
distributor_listing Etronixcenter distributor listing: Dyness Tower PRO Base + BDU (ref. DY-002) rev UNKNOWN
distributor_listing Solartraders distributor listing: Dyness Tower Pro BDU Battery Management System rev UNKNOWN
product_page Dyness Tower Pro official product page (HTML, dyness.com without www) rev UNKNOWN
user_manual Tower Pro USER MANUAL Battery System Tower Pro T-TP7/TP11/TP15/TP19/TP23 - distributor mirror on cdn.prod.website-files.com rev UNKNOWN

Recorded conflicts

environment.operating_temperature_discharge_min_c Review required
-10 — Tower Pro User Manual Table 2-1 'Discharge temperature range [C]' = -10~55 / -20~55 with heating
0 — Tower Pro datasheet V1.0-20240520 'Discharging Temperature' = '0~55C/-20~55C (with heating function)'
electrical.operating_voltage_max_v Review required
540 — Tower Pro User Manual Table 2-1 'Voltage range [V/DC]' = 420-540
547 — Tower Pro datasheet V1.0-20240520 'Operating Voltage Range' = 420-547V
physical.weight_kg Review required
206.0 — Tower Pro User Manual Table 2-1 'Weight [kg]' and Tower Pro datasheet V1.0-20240520 'Net Weight' (two independent distributor mirrors agree)
231.0 — Dyness Tower Pro official product page, technical specification table 'Net Weight'

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Battery system charge voltage [V/DC]540 V
Charge current standard [A]8 A
Charge rate claim (official page)'maximum 1C charge and discharge' / 'One hour to fully charge the battery'
Discharge current standard [A]8 A
Discharge minimum voltage [V/DC]420 V
Grounding resistance'<=100mOhm' (system) / '<1Ohm' (installation requirement)
Heating function (official page + datasheet)PTC Heating (optional); activates below 2 C, exits above 5 C, cut off at SOC<20%
Max depth of discharge100%
OTA Remote UpgradeAvailable (datasheet); official page 'remote upgrade (optional)'
Pre-storage SOC50-55%; activate every 10 months; SOC calibration at least once every 2 weeks; storage beyond 3 months needs attention
Short circuit current [kA]1.5 kA
WAKE button'Press and hold this button for 5s to start the battery system'
identity.product_statuscurrent