Fortress Power eVault MAX 18.5 kWh

Official manufacturer NA (US) verified Sept. 1, 2026

Identity

category batteries
ean UNKNOWN
generation MAX
manufacturer Fortress Power
market_version US
model eVault MAX 18.5 kWh
mpn UNKNOWN
product_family eVault / eVault MAX
product_revision UNKNOWN
product_status active
region NA (US)
release_year UNKNOWN
sku UNKNOWN

Electrical

bms_architecture {'type': 'integrated BMS per cabinet; Battery ID 0 for a single unit, IDs 1-20 in parallel', 'separate_master_bmu_required': False, 'modules_per_stack': 'N/A (single self-contained cabinet)', 'max_parallel_groups': '20 units, 370 kWh total'}
chemistry LFP (LiFePO4) - 'Tier 1 Automotive Prismatic - LiFePO4'
communication_can True
communication_rs485 True
firmware_requirements UNKNOWN (installation manual references per-inverter firmware versions for SMA and Victron without giving numbers)
max_continuous_charge_current_a 180
eVault MAX 18.5 Lithium Battery Storage - technical datasheet — datasheet, 'Maximum Charge Current 180A' (recommended 150A)
max_continuous_discharge_current_a 180
eVault MAX 18.5 Lithium Battery Storage - technical datasheet — datasheet, 'Recommended Continuous Discharge 180A (9.2 kW)'
max_continuous_power_kw 9.2
max_parallel_units 20
max_series_units N/A (LV parallel only)
min_series_units_hv N/A
nominal_energy_kwh 18.5
nominal_voltage_v 51.2
officially_supported_inverter_brands ['Fortress Power', 'Schneider Electric', 'OutBack Power', 'Sol-Ark', 'Studer Innotec', 'Magnum/Sensata', 'Victron Energy', 'Hoymiles', 'EG4', 'SMA', 'Midnite Solar', 'Morningstar', 'Phocos', 'Growatt', 'LuxPower']
officially_supported_inverter_models ['Fortress ENVY 8kW / 10kW / 12kW / Duo 21 (AC or DC coupled)', 'Fortress Solo 6.5K (AC or DC coupled)', 'Fortress EdgeOn Duo 9 / Duo 15 (AC or DC coupled)', 'Schneider Electric XW Pro 6848, XW+ 6848, XW+ 5548, SW 4048 (AC or DC coupled)', 'OutBack Power Radian 8048A, Radian 4048A, SkyBox SBX 5048, VFXR 3648A, FXR 3048A', 'Sol-Ark 5K, 8K, 12K, 15K, 18K', 'Studer Innotec AJ 400-48, AJ 700-48, XTS series 1400-8000-48', 'Magnum/Sensata MS 4448, MS 4048', 'Victron Energy Quattro 48V series, MultiPlus models (DC coupled)', 'HOYMILES HAS-3.8LV-USG1 through HAS-11.5LV-USG1', 'EG4 12kPV, 18kPV, FlexBOSS18, FlexBOSS21', 'LuxPower 12k (per installation manual)']
Battery Inverter Compatibility Guide — Battery Inverter Compatibility Guide, eVault MAX 18.5 column
peak_current_a 230 A (12 kW) for 30 min; 250 A (12.8 kW) surge for 5 s (datasheet) / 'Max. Pulse Current (for 10 sec) 250 A' (brochure) - see data_conflicts
eVault MAX 18.5 Lithium Battery Storage - technical datasheet — datasheet, 'Peak Discharge Rate 230A (12 kW, 30 min)'; 'Maximum Surge Power 250A (12.8 kW, 5 sec)'
supported_inverter_protocols ["CAN / RS485 (datasheet 'Protocol: CAN/RS485')", 'Communication Box carries five ports: inverter RS-485, inverter CAN, battery parallel communication and USB logging', 'Closed-loop communication is recommended but not required - the battery will also run open-loop']
usable_energy_kwh 18.43 (rated capacity @0.5C); DoD up to 100%
voltage_class LV
voltage_range_v 46-56

Physical / mechanical

depth_mm 515
enclosure_material Industrial Grade Aluminum
height_mm 1073
housing_color UNKNOWN
mounting_bolt_size two 3/8 in. (M10) threaded terminals with lock washer and nut
mounting_type ['floor']
rack_units N/A (free-standing cabinet)
shipping_weight_kg UNKNOWN
terminal_locations top-access serviceable design; communication box with five ports next to the battery breaker
torque_specs installation manual: 'Recommended terminal torque is 10.0-19.1 N.m (7.4-14.1 ft.lb)'; datasheet states 7.0-7.7 N.m - see data_conflicts
Fortress Power eVault MAX Installation Manual — installation manual, terminal torque section
weight_kg 235.87
width_mm 515

Installation

cable_requirements copper cable from 2/0 AWG for runs under 10 ft
clearance_back_mm 51 (2 in.) between the battery pack and the wall
clearance_left_mm 25 minimum (1 in. per UL9540A large-scale fire testing); 127 (5 in.) recommended between units
clearance_right_mm 25 minimum; 127 recommended
indoor_outdoor IP55 rated
installation_temperature_range_c do not charge below 0 C (32 F); optimal ambient 15-35 C (59-95 F)
lifetime_temperature_limit do not operate at an average temperature exceeding 30 C / 86 F over the life of the battery
max_installation_altitude_m UNKNOWN
mounting_orientation upright, floor standing ('do not transport battery upside down')

Environment

charge_temperature_c 0 to +49 (32 F to 120 F)
cooling_method UNKNOWN
discharge_temperature_c -20 to +60 (-4 F to 140 F)
ip_rating IP55
max_altitude_m UNKNOWN
relative_humidity 5%-75%
storage_temperature_c UNKNOWN (store out of direct sunlight)

Interfaces & connectors

battery_terminal_type M10 (3/8 in.) threaded studs, ring terminals 1/2 in. or larger
can yes (inverter CAN port on the communication box)
protocol_notes Battery ID must be 0 for a single unit; IDs 1-20 for parallel systems.
rs485 yes (inverter RS-485 port on the communication box)
usb yes - USB logging port

Protection

bms_charge_disconnect >56 V
cell_balancing UNKNOWN
integrated_breakers_fuses 250 A DC battery breaker integrated in the communication box
Fortress Power eVault MAX Installation Manual — installation manual, '250A breaker'
over_current over current protection for discharge via thermal control
over_temperature yes
over_voltage Over Voltage Fault 58.4 +/- 0.4 V; recovery 54.0 +/- 0.4 V
short_circuit yes
under_voltage Low Voltage Fault 43.2 +/- 0.4 V; recovery 43.2 +/- 0.4 V; battery low voltage protection <46 V, recovery 47 V

Certifications

emc []
note 'The eVault MAX has been listed to UL9540 standards as a DC ESS... It has passed the UL9540a large-scale fire testing.'
other ['CEC', 'SGIP']
regional []
safety ['UL 1642', 'UL 1973', 'UL 9540', 'UL 9540A']
transport []

Warranty & service

conditions 10 years with unlimited partial cycles
cycle_life 8,000 cycles @ 80% DoD
design_life_years UNKNOWN
round_trip_efficiency >98% (brochure) / 98% @0.5C (datasheet)
standard_years 10

Packaging & logistics

gross_weight_kg UNKNOWN (unit weight 235.87 kg / 520 lbs)
transport_restrictions UNKNOWN in the fetched documents; the manual requires end-of-life batteries to be transported at 30% state of charge, <52 V resting

Documents

compatibility-list Battery Inverter Compatibility Guide rev UNKNOWN
datasheet eVault MAX 18.5 Lithium Battery Storage - technical datasheet rev UNKNOWN
datasheet eVault MAX 18.5 kWh product page rev UNKNOWN
datasheet eVault Max 18.5 brochure rev UNKNOWN
installation-manual Fortress Power eVault MAX Installation Manual rev UNKNOWN

Recorded conflicts

peak_current_a Review required
250 A / 12.8 kW for 5 seconds — technical datasheet, 'Maximum Surge Power'
250 A for 10 seconds — brochure, 'Max. Pulse Current (for 10 sec) [A] 250'
brochure and datasheet state different surge durations
physical.torque_specs Review required
7.0-7.7 N.m — eVault MAX 18.5 technical datasheet
10.0-19.1 N.m (7.4-14.1 ft.lb) — Fortress Power eVault MAX Installation Manual (2023-01)
datasheet and installation manual disagree; the installation manual is the later and more specific document. SAFETY-RELEVANT - installers should follow the installation manual.
peak_current_a Review required
250 A / 12.8 kW for 5 seconds — technical datasheet, 'Maximum Surge Power'
250 A for 10 seconds — brochure, 'Max. Pulse Current (for 10 sec) [A] 250'
brochure and datasheet state different surge durations
physical.torque_specs Review required
7.0-7.7 N.m — eVault MAX 18.5 technical datasheet
10.0-19.1 N.m (7.4-14.1 ft.lb) — Fortress Power eVault MAX Installation Manual (2023-01)
datasheet and installation manual disagree; the installation manual is the later and more specific document. SAFETY-RELEVANT - installers should follow the installation manual.

Additional documented parameters

Recorded verbatim from the source; no schema field exists for these yet.

Cell TypeTier 1 Automotive Prismatic - LiFeP04
Lifetime average temperature limitDo Not Operate the eVault Max at an average temperature exceeding 30C / 86F over the life of the battery
Recommended Charge Voltage54.4V
Recommended Low Voltage Disconnect48V
UL9540A spacingminimum required spacing distance between units and walls is 1 inch per UL9540a large scale fire testing