Fortress Power eVault MAX 18.5 kWh
Official manufacturer NA (US) verified Sept. 1, 2026
UNKNOWN
Identity
| category | batteries |
| ean | UNKNOWN |
| generation | MAX |
| manufacturer | Fortress Power |
| market_version | US |
| model | eVault MAX 18.5 kWh |
| mpn | UNKNOWN |
| product_family | eVault / eVault MAX |
| product_revision | UNKNOWN |
| product_status | active |
| region | NA (US) |
| release_year | UNKNOWN |
| sku | UNKNOWN |
Electrical
| bms_architecture | {'type': 'integrated BMS per cabinet; Battery ID 0 for a single unit, IDs 1-20 in parallel', 'separate_master_bmu_required': False, 'modules_per_stack': 'N/A (single self-contained cabinet)', 'max_parallel_groups': '20 units, 370 kWh total'} |
| chemistry | LFP (LiFePO4) - 'Tier 1 Automotive Prismatic - LiFePO4' |
| communication_can | True |
| communication_rs485 | True |
| firmware_requirements | UNKNOWN (installation manual references per-inverter firmware versions for SMA and Victron without giving numbers) |
| max_continuous_charge_current_a |
180
eVault MAX 18.5 Lithium Battery Storage - technical datasheet — datasheet, 'Maximum Charge Current 180A' (recommended 150A)
|
| max_continuous_discharge_current_a |
180
eVault MAX 18.5 Lithium Battery Storage - technical datasheet — datasheet, 'Recommended Continuous Discharge 180A (9.2 kW)'
|
| max_continuous_power_kw | 9.2 |
| max_parallel_units | 20 |
| max_series_units | N/A (LV parallel only) |
| min_series_units_hv | N/A |
| nominal_energy_kwh | 18.5 |
| nominal_voltage_v | 51.2 |
| officially_supported_inverter_brands | ['Fortress Power', 'Schneider Electric', 'OutBack Power', 'Sol-Ark', 'Studer Innotec', 'Magnum/Sensata', 'Victron Energy', 'Hoymiles', 'EG4', 'SMA', 'Midnite Solar', 'Morningstar', 'Phocos', 'Growatt', 'LuxPower'] |
| officially_supported_inverter_models |
['Fortress ENVY 8kW / 10kW / 12kW / Duo 21 (AC or DC coupled)', 'Fortress Solo 6.5K (AC or DC coupled)', 'Fortress EdgeOn Duo 9 / Duo 15 (AC or DC coupled)', 'Schneider Electric XW Pro 6848, XW+ 6848, XW+ 5548, SW 4048 (AC or DC coupled)', 'OutBack Power Radian 8048A, Radian 4048A, SkyBox SBX 5048, VFXR 3648A, FXR 3048A', 'Sol-Ark 5K, 8K, 12K, 15K, 18K', 'Studer Innotec AJ 400-48, AJ 700-48, XTS series 1400-8000-48', 'Magnum/Sensata MS 4448, MS 4048', 'Victron Energy Quattro 48V series, MultiPlus models (DC coupled)', 'HOYMILES HAS-3.8LV-USG1 through HAS-11.5LV-USG1', 'EG4 12kPV, 18kPV, FlexBOSS18, FlexBOSS21', 'LuxPower 12k (per installation manual)']
Battery Inverter Compatibility Guide — Battery Inverter Compatibility Guide, eVault MAX 18.5 column
|
| peak_current_a |
230 A (12 kW) for 30 min; 250 A (12.8 kW) surge for 5 s (datasheet) / 'Max. Pulse Current (for 10 sec) 250 A' (brochure) - see data_conflicts
eVault MAX 18.5 Lithium Battery Storage - technical datasheet — datasheet, 'Peak Discharge Rate 230A (12 kW, 30 min)'; 'Maximum Surge Power 250A (12.8 kW, 5 sec)'
|
| supported_inverter_protocols | ["CAN / RS485 (datasheet 'Protocol: CAN/RS485')", 'Communication Box carries five ports: inverter RS-485, inverter CAN, battery parallel communication and USB logging', 'Closed-loop communication is recommended but not required - the battery will also run open-loop'] |
| usable_energy_kwh | 18.43 (rated capacity @0.5C); DoD up to 100% |
| voltage_class | LV |
| voltage_range_v | 46-56 |
Physical / mechanical
| depth_mm | 515 |
| enclosure_material | Industrial Grade Aluminum |
| height_mm | 1073 |
| housing_color | UNKNOWN |
| mounting_bolt_size | two 3/8 in. (M10) threaded terminals with lock washer and nut |
| mounting_type | ['floor'] |
| rack_units | N/A (free-standing cabinet) |
| shipping_weight_kg | UNKNOWN |
| terminal_locations | top-access serviceable design; communication box with five ports next to the battery breaker |
| torque_specs |
installation manual: 'Recommended terminal torque is 10.0-19.1 N.m (7.4-14.1 ft.lb)'; datasheet states 7.0-7.7 N.m - see data_conflicts
Fortress Power eVault MAX Installation Manual — installation manual, terminal torque section
|
| weight_kg | 235.87 |
| width_mm | 515 |
Installation
| cable_requirements | copper cable from 2/0 AWG for runs under 10 ft |
| clearance_back_mm | 51 (2 in.) between the battery pack and the wall |
| clearance_left_mm | 25 minimum (1 in. per UL9540A large-scale fire testing); 127 (5 in.) recommended between units |
| clearance_right_mm | 25 minimum; 127 recommended |
| indoor_outdoor | IP55 rated |
| installation_temperature_range_c | do not charge below 0 C (32 F); optimal ambient 15-35 C (59-95 F) |
| lifetime_temperature_limit | do not operate at an average temperature exceeding 30 C / 86 F over the life of the battery |
| max_installation_altitude_m | UNKNOWN |
| mounting_orientation | upright, floor standing ('do not transport battery upside down') |
Environment
| charge_temperature_c | 0 to +49 (32 F to 120 F) |
| cooling_method | UNKNOWN |
| discharge_temperature_c | -20 to +60 (-4 F to 140 F) |
| ip_rating | IP55 |
| max_altitude_m | UNKNOWN |
| relative_humidity | 5%-75% |
| storage_temperature_c | UNKNOWN (store out of direct sunlight) |
Interfaces & connectors
| battery_terminal_type | M10 (3/8 in.) threaded studs, ring terminals 1/2 in. or larger |
| can | yes (inverter CAN port on the communication box) |
| protocol_notes | Battery ID must be 0 for a single unit; IDs 1-20 for parallel systems. |
| rs485 | yes (inverter RS-485 port on the communication box) |
| usb | yes - USB logging port |
Protection
| bms_charge_disconnect | >56 V |
| cell_balancing | UNKNOWN |
| integrated_breakers_fuses |
250 A DC battery breaker integrated in the communication box
Fortress Power eVault MAX Installation Manual — installation manual, '250A breaker'
|
| over_current | over current protection for discharge via thermal control |
| over_temperature | yes |
| over_voltage | Over Voltage Fault 58.4 +/- 0.4 V; recovery 54.0 +/- 0.4 V |
| short_circuit | yes |
| under_voltage | Low Voltage Fault 43.2 +/- 0.4 V; recovery 43.2 +/- 0.4 V; battery low voltage protection <46 V, recovery 47 V |
Certifications
| emc | [] |
| note | 'The eVault MAX has been listed to UL9540 standards as a DC ESS... It has passed the UL9540a large-scale fire testing.' |
| other | ['CEC', 'SGIP'] |
| regional | [] |
| safety | ['UL 1642', 'UL 1973', 'UL 9540', 'UL 9540A'] |
| transport | [] |
Warranty & service
| conditions | 10 years with unlimited partial cycles |
| cycle_life | 8,000 cycles @ 80% DoD |
| design_life_years | UNKNOWN |
| round_trip_efficiency | >98% (brochure) / 98% @0.5C (datasheet) |
| standard_years | 10 |
Packaging & logistics
| gross_weight_kg | UNKNOWN (unit weight 235.87 kg / 520 lbs) |
| transport_restrictions | UNKNOWN in the fetched documents; the manual requires end-of-life batteries to be transported at 30% state of charge, <52 V resting |
Documents
Recorded conflicts
peak_current_a Review required
250 A / 12.8 kW for 5 seconds — technical datasheet, 'Maximum Surge Power'
250 A for 10 seconds — brochure, 'Max. Pulse Current (for 10 sec) [A] 250'
brochure and datasheet state different surge durations
physical.torque_specs Review required
7.0-7.7 N.m — eVault MAX 18.5 technical datasheet
10.0-19.1 N.m (7.4-14.1 ft.lb) — Fortress Power eVault MAX Installation Manual (2023-01)
datasheet and installation manual disagree; the installation manual is the later and more specific document. SAFETY-RELEVANT - installers should follow the installation manual.
peak_current_a Review required
250 A / 12.8 kW for 5 seconds — technical datasheet, 'Maximum Surge Power'
250 A for 10 seconds — brochure, 'Max. Pulse Current (for 10 sec) [A] 250'
brochure and datasheet state different surge durations
physical.torque_specs Review required
7.0-7.7 N.m — eVault MAX 18.5 technical datasheet
10.0-19.1 N.m (7.4-14.1 ft.lb) — Fortress Power eVault MAX Installation Manual (2023-01)
datasheet and installation manual disagree; the installation manual is the later and more specific document. SAFETY-RELEVANT - installers should follow the installation manual.
Additional documented parameters
Recorded verbatim from the source; no schema field exists for these yet.
| Cell Type | Tier 1 Automotive Prismatic - LiFeP04 |
| Lifetime average temperature limit | Do Not Operate the eVault Max at an average temperature exceeding 30C / 86F over the life of the battery |
| Recommended Charge Voltage | 54.4V |
| Recommended Low Voltage Disconnect | 48V |
| UL9540A spacing | minimum required spacing distance between units and walls is 1 inch per UL9540a large scale fire testing |